5.2.1 Starting the UPS in Normal Mode

Procedure
Step 1 Press and hold the MANUAL ON/OFF button on each lithium battery for at least 5s and less
than 15s to activate the lithium battery.
Step 2 Close the upstream AC input circuit breaker for the UPS based on site requirements.
The initialization screen is displayed.
Step 3 The UPS enters bypass mode. When the initialization is complete, perform the following
operations:
Step 4 Choose Settings > Battery Parameters, and set the Input power limiting based on the
actual situation.
Issue 02 (2019-05-05)
Set Voltage level and Frequency level based on the rated voltage and frequency. In the
case of single-phase output, set Voltage level to 100 V (default), 110 V, or 120 V.
Battery parameters are configurable in non-battery mode or non-battery ECO mode.
Set Battery capacity to the total capacity of all batteries actually connected. The value
ranges from 100 Ah to 1000 Ah. The default value is 100 Ah.
The preset password is 000001, used to enter the Settings menu.
The default feature code is 999999, used to restore the preset password.
Initial startup
On the Settings wizard screen, set the language (the preset language is English), system
parameters, and battery parameters. Press
Figure 5-1 Settings wizard
Non-initial startup
When the initialization is complete, the standby screen is displayed. On the standby
screen, press
to enter the main menu. Choose Main Menu > Settings > System
Parameters > Output to view output settings.
Copyright © Huawei Technologies Co., Ltd.
. The standby screen is displayed.