Huawei UPS2000-G-3 kVA User Manual page 43

Hide thumbs Also See for UPS2000-G-3 kVA:
Table of Contents

Advertisement

UPS2000-G-3 kVA
User Manual (CTC)
Communication Card Screen
1.
2.
Issue 02 (2019-05-05)
If an SNMP card is connected, set the following parameters:
Figure 4-18 SNMP card settings
IP alloc. parameter
Specifies the DHCP address allocating mode. The options include Manual and
Automatic. The default value is Manual. After the allocating mode is set to
Automatic, an Allocating dialog box is displayed on the screen. If allocation
succeeds, the new IP address is displayed. If allocation fails, the IP address restores
to the default one: 192.168.0.10. If the allocating mode is set to Automatic, you can
only query the IP address but cannot set the IP address manually.
If the UPS monitor does not support the DHCP function, after the DHCP is selected for the SNMP card,
you cannot set the IP address of the SNMP card on the UPS monitor. You are advised to update the
version of the UPS monitor.
IP address parameter
Set an IP address for the SNMP card. The value ranges from 1.0.0.0 to
223.255.255.255. The default value is 192.168.0.10.
Subn. mask parameter
Set a subnet mask for the SNMP card. The value ranges from 0.0.0.0 to
255.255.255.255. The default value is 255.255.255.0.
Gateway parameter
Set a gateway address for the SNMP card. The value ranges from 1.0.0.0 to
223.255.255.255. The default value is 192.168.0.1.
If a Modbus card is connected, the following parameters are displayed:
Figure 4-19 Modbus card settings
Comm. address parameter
Set a communications address for the Modbus card over the dual in-line package
(DIP) switch on the Modbus card. The value cannot be changed on the LCD.
Baud rate parameter
Set a baud rate for the Modbus card over the DIP switch on the Modbus card. The
value cannot be changed on the LCD.
Copyright © Huawei Technologies Co., Ltd.
4 Control Panel
37