UPS2000-G-3 kVA
User Manual (CTC)
Alarm
Alarm
ID
Name
(Alarm
ID-Alar
m
Cause)
0340-01
Maint.
breaker
ON
Flash
61440-01
fault
Issue 02 (2019-05-05)
Alarm
Alarm
Level
Clear
Mode
Minor
Automatic
clear
Automatic
Critical
clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the System
The UPS transfers to bypass
mode.
Files may be damaged.
A Alarm Handling
Repair Proposal
is in battery self-check
state.
Reduce the load or
replace the UPS with a
larger-capacity UPS.
Possible cause: The
maintenance circuit breaker
is ON during UPS
maintenance.
Measure: Switch off the
maintenance circuit breaker
after maintenance.
Possible cause: The flash
memory cannot be properly
read or written.
Measure: Contact Huawei
technical support for repair.
82