Huawei UPS2000-G-3 kVA User Manual page 75

Hide thumbs Also See for UPS2000-G-3 kVA:
Table of Contents

Advertisement

UPS2000-G-3 kVA
User Manual (CTC)
Alarm
Alarm
ID
Name
(Alarm
ID-Alar
m
Cause)
0040-05
Rectifier
fault
0040-06
Rectifier
fault
0040-07
Rectifier
fault
0040-09
Rectifier
fault
Issue 02 (2019-05-05)
Alarm
Alarm
Level
Clear
Mode
Critical
Manual
clear/Power
-off
clear/Auto
matic clear
Critical
Power-off
clear
Critical
Automatic
clear
Critical
Power-off
clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the System
The UPS shuts down.
The UPS transfers to another
working mode or shuts down.
The UPS shuts down.
The UPS transfers to another
working mode or shuts down.
The UPS shuts down.
The UPS transfers to another
working mode or shuts down.
The charger stops working.
The rectifier transfers to
battery mode, and the power
supply is not affected.
If no battery is installed, the
UPS shuts down.
The UPS transfers to another
working mode or shuts down.
A Alarm Handling
Repair Proposal
UPS.
Enable the transformer
mode.
Contact Huawei
technical support for
repair.
Possible cause: The
hardware is damaged.
Measure: Contact Huawei
technical support for repair.
Possible cause: The
hardware is damaged.
Measure: Contact Huawei
technical support for repair.
Possible causes:
The ambient
temperature exceeds
40° C.
The air channel is
blocked.
The fan is abnormal.
Measures:
Decrease the ambient
temperature.
Keep the air intake and
exhaust vents of the
UPS unobstructed.
Clean off the foreign
objects around the fan.
If the alarm persists,
contact Huawei
technical support for
repair.
Possible cause: The
rectifier is faulty.
Measure: Contact Huawei
technical support for repair.
69