The UPS is a large leakage current device. Do not configure a circuit breaker that has the
leakage current protection function. If you need leakage current protection function, use
the earth leakage circuit breaker recommended.
The battery cable cannot be longer than 10 m.
Table 3-2 Recommended power cable specifications
Type
PDU AC input power
cable (L/N/PE)
PDU AC output
power cable
(L/N/PE)
UPS output power
cable (sL/N/PE)
UPS input power
cable (L/N/PE)
UPS battery cable (+,
N, N, –, PE)
Battery cable (+, –)
UPS CAN
communications
cable
Battery CAN
communications
cable
PDU PE
Battery PE
Issue 02 (2019-05-05)
Cross-sectional
Area
2
25 mm
2
6 mm
2
6 mm
2
6 mm
2
6 mm
2
6 mm
Ethernet cable
Ethernet cable
2
25 mm
2
6 mm
Copyright © Huawei Technologies Co., Ltd.
Terminal Type
2
25 mm
M6 OT
terminal
2
6 mm
M4 OT
terminal
2
OT-6 mm
-M4
terminal/OT-6
2
mm
-M6
terminal/OT-6
2
mm
-M6 90° terminal
2
OT-6 mm
-M4
2
terminal/6 mm
M6
OT terminal
2
OT-6 mm
-M6
terminal /OT-6
2
mm
-M6 90° terminal
2
/OT-16 mm
-M6
terminal
2
OT-6 mm
-M6
terminal /OT-6
2
mm
-M4 terminal
RJ45 terminal
RJ45 terminal
25 mm2 M6 OT
terminal
6 mm2 M6 OT
terminal
3 Installation
Torque for
Tightening Bolts
4.8 N· m
2.8 N· m
2.8 N· m
2.8 N· m
2.8 N· m
2.8 N· m
-
-
4.8 N· m
4.8 N· m
20