Huawei UPS2000-G-3 kVA User Manual page 73

Hide thumbs Also See for UPS2000-G-3 kVA:
Table of Contents

Advertisement

UPS2000-G-3 kVA
User Manual (CTC)
Alarm
Alarm
ID
Name
(Alarm
ID-Alar
m
Cause)
0032-01
Batt.
OVP
0034-01
Remaini
ng cap.
warning
Issue 02 (2019-05-05)
Alarm
Alarm
Level
Clear
Mode
Critical
Automatic
clear
Minor
Automatic
clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the System
An alarm is generated, and
the battery lifespan is
affected.
If no action is taken,
continued discharge will
result in system shutdown
due to EOD.
A Alarm Handling
Repair Proposal
temperature.
Keep the air intake and
exhaust vents of the
UPS unobstructed.
Clean off the foreign
objects around the fan.
If the alarm persists,
contact Huawei
technical support for
repair.
Possible causes:
The configured number
of batteries is less than
the actual number.
The actual number of
batteries does not meet
specifications.
The charger is
abnormal.
Measures:
Check that the
configured number of
batteries matches the
actual number.
Check that the actual
number of batteries
meets requirements.
Disconnected the
external battery charger,
check whether the alarm
is cleared. If not,
contact Huawei
technical support for
repair.
Possible cause:
The battery discharge
lasts too long.
The mains input is
abnormal.
The number of batteries
or battery capacity is
incorrectly set.
67