UPS2000-G-3 kVA
User Manual (CTC)
Alarm
Alarm
ID
Name
(Alarm
ID-Alar
m
Cause)
0134-01
Ambient
overhum
idity
0135-01
Ambient
underhu
midity
Issue 02 (2019-05-05)
Alarm
Alarm
Level
Clear
Mode
Minor
Minor
Copyright © Huawei Technologies Co., Ltd.
Impact on the System
A Alarm Handling
Repair Proposal
threshold (default value:
0º C).
The temperature and
humidity transducer is
faulty.
Measures:
Check the ambient
temperature in the UPS
equipment room.
Replace the temperature
and humidity
transducer.
Possible causes:
The ambient humidity
in the UPS equipment
room exceeds the alarm
threshold (default value:
90%).
The temperature and
humidity transducer is
faulty.
Measures:
Check the ambient
humidity of the UPS
equipment room.
Replace the temperature
and humidity
transducer.
Possible causes:
The ambient humidity
in the UPS equipment
room is below the alarm
threshold (default value:
10%).
The temperature and
humidity transducer is
faulty.
Measures:
Check the ambient
humidity of the UPS
equipment room.
Replace the temperature
80