16.1.5
Low Pressure Prevention Control (Gas Leakage Detection)
Control start conditions
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.36A and 0.54A
o
(Z35/42/50/71XKEW), between 0.29A and 0.44A (Z20/25XKEW).
During Cooling and Soft Dry operations:
o
Indoor suction temperature - indoor piping temperature is below 4°C.
During Heating operations :
o
Indoor piping temperature - indoor suction is under 5°C.
Control contents
Compressor stops (and restart after 3 minutes).
o
If the conditions above happen 2 times within 20 minutes, the unit will:
o
Stop operation
Timer LED blinks and "F91" indicated.
16.1.6
Low Frequency Protection Control 1
When the compressor operate at frequency lower than 24 Hz continued for 240 minutes, the operation frequency
will be changed to 23 Hz for 2 minutes.
16.1.7
Low Frequency Protection Control 2
When all the below conditions comply, the compressor frequency will change to lower frequency.
Indoor intake air (°C)
Outdoor air (°C)
Indoor heat exchanger (°C)
103°C
99°C
96°C
Comp. temperature
Temperature, T, for:
Compressor = OFF
88°C
Compressor Frequency
Reduce
87°C
Compressor Frequency
Maintain
86°C
Free
Cooling/Soft Dry
T < 14 or T ≥ 30
T < 13 or T ≥ 38
T < 30
97
Heating
T < 14 or T ≥ 28
T < 4 or T ≥ 24
T ≥ 0