Panasonic CU-Z20VKE Series Installation Instruction
Panasonic CU-Z20VKE Series Installation Instruction

Panasonic CU-Z20VKE Series Installation Instruction

Indoor/outdoor unit
Hide thumbs Also See for CU-Z20VKE Series:
Table of Contents

Advertisement

Air conditioner
MODEL NO. :-
CU-Z20, Z25, Z35, Z42, Z50, Z71VKE Series.
Installation Instruction
Required tools for Installation Works
CAUTION
1.
8.
Phillips screw driver
2.
Level gauge
9.
3.
Electric drill, hole core drill
10.
R32
(ø70 mm)
11.
4.
Hexagonal wrench (4 mm)
12.
5.
Spanner
13.
6.
Pipe cutter
14.
REFRIGERANT
7.
Reamer
This Air Conditioner contains and
Explanation of symbols displayed on the indoor unit or outdoor unit.
operates with refrigerant R32.
THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED
This symbol shows that this equipment uses a fl ammable refrigerant. If the refrigerant
BY QUALIFIED PERSONNEL.
WARNING
is leaked, together with an external ignition source, there is a possibility of ignition.
Refer to National, State, Territory and local legislation,
regulations, codes, installation & operation manuals, before
CAUTION
This symbol shows that the Installation Manual should be read carefully.
the installation, maintenance and/or service of this product.
This symbol shows that a service personnel should be handling
CAUTION
this equipment with reference to the Installation Manual.
This symbol shows that there is information included in the Operation
SAFETY PRECAUTIONS
CAUTION
Manual and/or Installation Manual.
Read the following "SAFETY PRECAUTIONS" carefully before installation.
Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.
The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classifi ed by the following indications.
WARNING
This indication shows the possibility of causing death or serious injury.
CAUTION
This indication shows the possibility of causing injury or damage to properties only.
The items to be followed are classifi ed by the symbols:
Symbol with white background denotes item that is PROHIBITED.
Symbol with dark background denotes item that must be carried out.
Carry out test running to confi rm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated in instructions. Please remind the
customer to keep the operating instructions for future reference.
WARNING
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. Any unfi t method or using incompatible material may cause product
damage, burst and serious injury.
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit on veranda of a high rise building, child may climb up to outdoor unit and cross over the handrail causing an
accident.
Do not use unspecifi ed cord, modifi ed cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances. Poor contact, poor insulation or over
current will cause electrical shock or fi re.
Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen.
Do not insert your fi ngers or other objects into the unit, high speed rotating fan may cause injury.
Do not sit or step on the unit, you may fall down accidentally.
Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and prevent breathing.
When installing or relocating air conditioner, do not let any substance other than the specifi ed refrigerant, eg. air etc mix into refrigeration cycle (piping).
Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Do not pierce or burn as the appliance is pressurized. Do not expose the appliance to heat, fl ame, sparks, or other sources of ignition.
Else, it may explode and cause injury or death.
Do not add or replace refrigerant other than specifi ed type. It may cause product damage, burst and injury etc.
For R32 model, use piping, fl are nut and tools which is specifi ed for R32 refrigerant. Using of existing (R22) piping, fl are nut and tools may cause abnormally high pressure in the refrigerant
cycle (piping), and possibly result in explosion and injury.
Thickness for copper pipes used with R32 must be more than 0.8 mm. Never use copper pipes thinner than 0.8 mm.
It is desirable that the amount of residual oil less than 40 mg/10 m.
Engage authorized dealer or specialist for installation. If installation done by the user is incorrect, it will cause water leakage, electrical shock or fi re.
For refrigeration system work, Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fi re.
Use the attached accessories parts and specifi ed parts for installation. Otherwise, it will cause the set to fall, water leakage, fi re or electrical shock.
Install at a strong and fi rm location which is able to withstand weight of the set. If the strength is not enough or installation is not properly done, the set will drop and cause injury.
For electrical work, follow the national regulation, legistration and this installation instructions. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or
defect found in the electrical work, it will cause electrical shock or fi re.
Do not use joint cable for indoor / outdoor connection cable. Use the specifi ed indoor/outdoor connection cable, refer to instruction 5 CONNECT THE CABLE TO THE OUTDOOR UNIT and
connect tightly for indoor/outdoor connection. Clamp the cable so that no external force will have impact on the terminal. If connection or fi xing is not perfect, it will cause heat up or fi re at the
connection.
Wire routing must be properly arranged so that control board cover is fi xed properly. If control board cover is not fi xed perfectly, it will cause fi re or electrical shock.
This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD), with sensitivity of 30mA at 0.1sec or less. Otherwise, it may
cause electrical shock and fi re in case of equipment breakdown or insulation breakdown.
During installation, install the refrigerant piping properly before running the compressor. Operation of compressor without fi xing refrigeration piping and valves at opened position will cause suck-in
of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
During pump down operation, stop the compressor before removing the refrigeration piping. Removal of refrigeration piping while compressor is operating and valves are opened will cause suck-in
of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Tighten the fl are nut with torque wrench according to specifi ed method. If the fl are nut is over-tightened, after a long period, the fl are may break and cause refrigerant gas leakage.
After completion of installation, confi rm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant contacts with fi re.
Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fi re.
Be aware that refrigerants may not contain an odour.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone.
Otherwise, it may cause electrical shock in case of equipment breakdown or insulation breakdown.
CAUTION
Do not install the unit in a place where leakage of fl ammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fi re.
Prevent liquid or vapor from entering sumps or sewers since vapor is heavier than air and may form suffocating atmospheres.
Do not release refrigerant during piping work for installation, re-installation and during repairing refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
Do not touch the sharp aluminium fi n, sharp parts may cause injury.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.
Select an installation location which is easy for maintenance.
Incorrect installation, service or repair of this air conditioner may increase the risk of rupture and this may result in loss damage or injury and/or property.
Power supply connection to the room air conditioner.
Use power supply cord 3 x 1.5 mm² (3/4 ~ 1.75HP), 3 x 2.5 mm² (2.0 ~ 2.5HP) type designation 60245 IEC 57 or heavier cord.
Connect the power supply cord of the air conditioner to the mains using one of the following method.
Power supply point should be in easily accessible place for power disconnection in case of emergency.
In some countries, permanent connection of this air conditioner to the power supply is prohibited.
1) Power supply connection to the receptacle using power plug.
Use an approved 15/16A (3/4 ~ 1.75HP), 16A (2.0HP), 20A (2.5HP) power plug with earth pin for the connection to the socket.
2) Power supply connection to a circuit breaker for the permanent connection.
Use an approved 16A (3/4 ~ 2.0HP), 20A (2.5HP) circuit breaker for the permanent connection. It must be a double pole switch with a minimum 3.0 mm contact gap.
Installation work.
It may need two people to carry out the installation work.
Keep any required ventilation openings clear of obstruction.
PRECAUTION FOR USING R32 REFRIGERANT
The basic installation work procedures are the same as conventional refrigerant (R410A, R22) models.
However, pay careful attention to the following points:
WARNING
The appliance shall be stored, installed and operated in a well ventilated room with indoor fl oor area larger than A
(m²) [refer Table A] and without any continuously operating ignition source.
min
Keep away from open fl ames, any operating gas appliances or any operating electric heater. Else, it may explode and cause injury or death.
Since the working pressure is higher than that of refrigerant R22 models, some of the piping and installation and service tools are special.
Especially, when replacing a refrigerant R22 model with a new refrigerant R32 model, always replace the conventional piping and fl are nuts with the R32 and R410A piping and fl are nuts on the
outdoor unit side.
For R32 and R410A, the same fl are nut on the outdoor unit side and pipe can be used.
The mixing of different refrigerants within a system is prohibited. Models that use refrigerant R32 and R410A have a different charging port thread diameter to prevent erroneous charging with
refrigerant R22 and for safety.
Therefore, check beforehand. [The charging port thread diameter for R32 and R410A is 12.7 mm (1/2 inch).]
Ensure that foreign matter (oil, water, etc.) does not enter the piping.
Also, when storing the piping, securely seal the opening by pinching, taping, etc. (Handling of R32 is similar to R410A.)
Operation, maintenance, repairing and refrigerant recovery should be carried out by trained and certifi ed personnel in the use of fl ammable refrigerants and as recommended by the manufacturer.
Any personnel conducting an operation, servicing or maintenance on a system or associated parts of the equipment should be trained and certifi ed.
Any part of refrigerating circuit (evaporators, air coolers, AHU, condensers or liquid receivers) or piping should not be located in the proximity of heat sources, open fl ames, operating gas appliance
or an operating electric heater.
The user/owner or their authorized representative shall regularly check the alarms, mechanical ventilation and detectors, at least once a year, where as required by national regulations, to ensure
their correct functioning.
A logbook shall be maintained. The results of these checks shall be recorded in the logbook.
In case of ventilations in occupied spaces shall be checked to confi rm no obstruction.
ACXF60-33670-AA_EN.indd 1
ACXF60-33670-AA_EN.indd 1
Before a new refrigerating system is put into service, the person responsible for placing the system in operation should ensure that trained and certifi ed operating personnel are instructed on the
basis of the instruction manual about the construction, supervision, operation and maintenance of the refrigerating system, as well as the safety measures to be observed, and the properties and
handling of the refrigerant used.
The general requirement of trained and certifi ed personnel are indicated as below:
a) Knowledge of legislation, regulations and standards relating to fl ammable refrigerants; and,
b)  D etailed knowledge of and skills in handling fl ammable refrigerants, personal protective equipment, refrigerant leakage prevention, handling of cylinders, charging, leak detection, recovery and
disposal; and,
c) Able to understand and to apply in practice the requirements in the national legislation, regulations and Standards; and,
d) Continuously undergo regular and further training to maintain this expertise.
Air-conditioner piping in the occupied space shall be installed in such a way to protect against accidental damage in operation and service.
Precautions shall be taken to avoid excessive vibration or pulsation to refrigerating piping.
Knife
42 N•m (4.3 kgf•m)
Gas leak detector
55 N•m (5.6 kgf•m)
Ensure protection devices, refrigerating piping and fi ttings are well protected against adverse environmental effects (such as the danger of water collecting and freezing in relief pipes or the
Measuring tape
65 N•m (6.6 kgf•m)
accumulation of dirt and debris).
100 N•m (10.2 kgf•m)
Thermometer
Expansion and contraction of long runs piping in refrigerating systems shall be designed and installed securely (mounted and guarded) to minimize the likelihood hydraulic shock damaging the
15.
Vacuum pump
system.
Megameter
16.
Gauge manifold
Multimeter
Protect the refrigerating system from accidental rupture due to moving furniture or reconstruction activities.
Torque wrench
To ensure no leaking, fi eld-made refrigerant joints indoors shall be tightness tested. The test method shall have a sensitivity of 5 grams per year of refrigerant or better under a pressure of at least 0,25 times the
18 N•m (1.8 kgf•m)
maximum allowable pressure (>1.04MPa, max 4.15MPa). No leak shall be detected.
1. Installation (Space)
Must ensure the installation of pipe-work shall be kept to a minimum. Avoid use dented pipe and do not allow acute bending.
Must ensure that pipe-work shall be protected from physical damage.
Must comply with national gas regulations, state municipal rules and legislation. Notify relevant authorities in accordance with all applicable regulations.
Must ensure mechanical connections be accessible for maintenance purposes.
In cases that require mechanical ventilation, ventilation openings shall be kept clear of obstruction.
When disposal of the product, do follow to the precautions in #12 and comply with national regulations.
In case of fi eld charge, the effect on refrigerant charge caused by the different pipe length has to be quantifi ed, measured and labelled.
Always contact to local municipal offi ces for proper handling.
2. Servicing
2-1. Service personnel
Any qualifi ed person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certifi cate from an industry-accredited assessment authority, which
authorizes their competence to handle refrigerants safely in accordance with an industry recognized assessment specifi cation.
Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the
supervision of the person competent in the use of fl ammable refrigerants.
Servicing shall be performed only as recommended by the manufacturer.
The system is inspected, regularly supervised and maintained by a trained and certifi ed service personnel who is employed by the person user or party responsible.
Ensure the actual refrigerant charge is in accordance with the room size within which the refrigerant containing parts are installed.
Ensure refrigerant charge not to leak.
2-2. Work
Prior to beginning work on systems containing fl ammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised.
For repair to the refrigerating system, the precautions in #2-2 to #2-8 must be followed before conducting work on the system.
Work shall be undertaken under a controlled procedure so as to minimize the risk of a fl ammable gas or vapour being present while the work is being performed.
All maintenance staff and others working in the local area shall be instructed and supervised on the nature of work being carried out.
Avoid working in confi ned spaces. Always ensure away from source, at least 2 meter of safety distance, or zoning of free space area of at least 2 meter in radius.
Wear appropriate protective equipment, including respiratory protection, as conditions warrant.
Keep all sources of ignition and hot metal surfaces away.
2-3. Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially fl ammable atmospheres.
Ensure that the leak detection equipment being used is suitable for use with fl ammable refrigerants, i.e. non sparking, adequately sealed or intrinsically safe.
In case of leakage/spillage happened, immediately ventilate area and stay upwind and away from spill/release.
In case of leakage/spillage happened, do notify persons down wind of the leaking/spill, isolate immediate hazard area and keep unauthorized personnel out.
2-4. Presence of fi re extinguisher
If any hot work is to be conducted on the refrigerating equipment or any associated parts, appropriate fi re extinguishing equipment shall be available at hand.
Have a dry powder or CO
fi re extinguisher adjacent to the charging area.
2
2-5. No ignition sources
No person carrying out work in relation to a refrigerating system which involves exposing any pipe work that contains or has contained fl ammable refrigerant shall use any sources of ignition in
such a manner that it may lead to the risk of fi re or explosion. He/She must not be smoking when carrying out such work.
All possible ignition sources, including cigarette smoking, should be kept suffi ciently far away from the site of installation, repairing, removing and disposal, during which fl ammable refrigerant
can possibly be released to the surrounding space.
Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no fl ammable hazards or ignition risks.
"No Smoking" signs shall be displayed.
2-6. Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work.
A degree of ventilation shall continue during the period that the work is carried out.
The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
2-7. Checks to the refrigerating equipment
Where electrical components are being changed, they shall be fi t for the purpose and to the correct specifi cation.
At all times the manufacturer's maintenance and service guidelines shall be followed.
If in doubt consult the manufacturer's technical department for assistance.
The following checks shall be applied to installations using fl ammable refrigerants.
- The actual refrigerant charge is in accordance with the room size within which the refrigerant containing parts are installed.
- The ventilation machinery and outlets are operating adequately and are not obstructed.
- If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant.
- Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected.
- Refrigerating pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components
are constructed of materials which are inherently resistant to being corroded or are properly protected against being so corroded.
2-8. Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures.
Initial safety checks shall include but not limit to:-
- That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking.
- That there is no live electrical components and wiring are exposed while charging, recovering or purging the system.
- That there is continuity of earth bonding.
At all times the manufacturer's maintenance and service guidelines shall be followed.
If in doubt consult the manufacturer's technical department for assistance.
If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with.
If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used.
The owner of the equipment must be informed or reported so all parties are advised thereinafter.
3. Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc.
If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a
potentially hazardous situation.
Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall
include damage to cables, excessive number of connections, terminals not made to original specifi cation, damage to seals, incorrect fi tting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of fl ammable atmospheres.
Replacement parts shall be in accordance with the manufacturer's specifi cations.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment.
Intrinsically safe components do not have to be isolated prior to working on them.
4. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while live in the presence of a fl ammable atmosphere.
The test apparatus shall be at the correct rating.
Replace components only with parts specifi ed by the manufacturer. Unspecifi ed parts by manufacturer may result ignition of refrigerant in the atmosphere from a leak.
5. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects.
The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
6. Detection of fl ammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching or detection of refrigerant leaks.
A halide torch (or any other detector using a naked fl ame) shall not be used.
7. The following leak detection methods are deemed acceptable for all refrigerant systems.
No leaks shall be detected when using detection equipment with a sensitivity of 5 grams per year of refrigerant or better under a pressure of at least 0,25 times the maximum allowable pressure
(>1.04MPa, max 4.15MPa) for example, a universal sniffer.
Electronic leak detectors may be used to detect fl ammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration.
(Detection equipment shall be calibrated in a refrigerant-free area.)
Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used.
Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum)
is confi rmed.
Leak detection fl uids are also suitable for use with most refrigerants, for example, bubble method and fl uorescent method agents. The use of detergents containing chlorine shall be avoided as
the chlorine may react with the refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked fl ames shall be removed/extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from
the leak. The precautions in #8 must be followed to remove the refrigerant.
8. Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used.
However, it is important that best practice is followed since fl ammability is a consideration.
The following procedure shall be adhered to:
• remove refrigerant -> • purge the circuit with inert gas -> • evacuate -> • purge with inert gas -> • open the circuit by cutting or brazing
The refrigerant charge shall be recovered into the correct recovery cylinders.
The system shall be purged with OFN to render the appliance safe. (remark: OFN = oxygen free nitrogen, type of inert gas)
This process may need to be repeated several times.
Compressed air or oxygen shall not be used for this task.
Purging shall be achieved by breaking the vacuum in the system with OFN and continuing to fi ll until the working pressure is achieved, then venting to atmosphere, and fi nally pulling down to a vacuum.
This process shall be repeated until no refrigerant is within the system.
When the fi nal OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.
This operation is absolutely vital if brazing operations on the pipe work are to take place.
Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and there is ventilation available.
9. Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed.
- Ensure that contamination of different refrigerants does not occur when using charging equipment.
- Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
- Cylinders shall be kept in an appropriate position according to the instructions.
- Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
- Label the system when charging is complete (if not already).
- Extreme care shall be taken not to over fi ll the refrigerating system.
Prior to recharging the system it shall be pressure tested with OFN (refer to #7).
The system shall be leak tested on completion of charging but prior to commissioning.
A follow up leak test shall be carried out prior to leaving the site.
Electrostatic charge may accumulate and create a hazardous condition when charging and discharging the refrigerant.
To avoid fi re or explosion, dissipate static electricity during transfer by grounding and bonding containers and equipment before charging/discharging.
10. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its details.
It is recommended good practice that all refrigerants are recovered safely.
Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant.
It is essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
mechanical handling equipment is available, if required, for handling refrigerant cylinders;
all personal protective equipment is available and being used correctly;
the recovery process is supervised at all times by a competent person;
recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various
parts of the system.
Electrostatic charge may accumulate and create a hazardous condition when charging or discharging the refrigerant.
To avoid fi re or explosion, dissipate static electricity during transfer by grounding and bonding containers and equipment before charging/discharging.
11. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant.
The label shall be dated and signed.
Ensure that there are labels on the equipment stating the equipment contains fl ammable refrigerant.
12. Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed.
Ensure that the correct number of cylinders for holding the total system charge are available.
All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant).
Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order.
Recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of concerning the equipment that is at hand and shall be suitable for the
recovery of fl ammable refrigerants.
In addition, a set of calibrated weighing scales shall be available and in good working order.
Hoses shall be complete with leak-free disconnect couplings and in good condition.
Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release.
Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged.
Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that fl ammable refrigerant does not remain within the lubricant.
The evacuation process shall be carried out prior to returning the compressor to the suppliers.
Only electric heating to the compressor body shall be employed to accelerate this process.
When oil is drained from a system, it shall be carried out safely.
Attached accessories
No.
Accessories part
CAUTION
Drain elbow
1
  If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed.
  There should not be any animal or plant which could be affected by hot air discharged.
  Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
  Do not place any obstacles which may cause a short circuit of the discharged air.
  If piping length is over the [piping length for additional gas], additional refrigerant should be added as shown in the table.
Table A
Capacity W
Model
(HP)
3/4HP
Z20***, XZ20***
Z25***, XZ25***
1.0HP
Z35***, XZ35***
1.5HP
Z42***
1.75HP
Z50***, XZ50***
2.0HP
2.5HP
Z71***
(*) Systems with total refrigerant charge, m
1
SELECT THE BEST LOCATION
(Refer to "Select the best location" section)
2
INSTALL THE OUTDOOR UNIT
After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1.
Fix the unit on concrete or rigid frame fi rmly and horizontally by bolt nut (ø10 mm).
2.
When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand fi rmly with bolt, screws or nails.
A
3
CONNECT THE PIPING
Connecting The Piping to Indoor
For connection joint location at outside building
Please make flare after inserting flare nut (locate
at joint portion of tube assembly) onto the copper
pipe. (In case of using long piping)
Connect the piping
Align the center of piping and suffi ciently
tighten the fl are nut with fi ngers.
Further tighten the fl are nut with torque
wrench in specifi ed torque as stated in the
table.
Spanner or
Wrench
Connecting The Piping to Outdoor
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge.
Make fl are after inserting the fl are nut (locate at valve)
onto the copper pipe. Align center of piping to valve
and then tighten with torque wrench to the specifi ed
torque as stated in the table.
5
CONNECT THE CABLE TO THE OUTDOOR UNIT
1.
Remove the control board cover from the unit by loosening the screw.
Connection cable between indoor unit and outdoor unit shall be approved polychloroprene
2.
sheathed 4 x 1.5 mm
60245 IEC 57 or heavier cord. Do not use joint connection cable. Replace the wire if the existing
wire (from concealed wiring, or otherwise) is too short.
Terminals on the outdoor unit
Colour of wires (connection cable)
Terminals on the indoor unit
3.
Secure the cable onto the control board with the holder (clamper).
4.
Attach the control board cover back to the original position with screw.
5.
For wire stripping and connection requirement, refer to instruction
This equipment must be properly earthed.
DISPOSAL OF OUTDOOR UNIT DRAIN WATER
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with instructions.
h) Do not over fi ll cylinders. (No more than 80 % volume liquid charge).
If a drain elbow is used, the unit should be placed on a stand which
i)
Do not exceed the maximum working pressure of the cylinder, even temporarily.
is taller than 3 cm.
j)
When the cylinders have been fi lled correctly and the process completed, make
sure that the cylinders and the equipment are removed from site promptly and all
If the unit is used in an area where temperature falls below 0°C for 2 or 3
isolation valves on the equipment are closed off.
days in succession, it is recommended not to use a drain elbow, for the
k) Recovered refrigerant shall not be charged into another refrigerating system
drain water freezes and the fan will not rotate.
unless it has been cleaned and checked.
Example: For Z20***
If the unit is installed at 10 m distance, the quantity of additional refrigerant should be 25 g .... (10-7.5) m x
Qty.
10 g/m = 25 g.
A
= (
m
/ (2.5 x (LFL)
min
c
1
A
= Required minimum room area, in m²
min
m
= Refrigerant charge in appliance, in kg
c
LFL = Lower fl ammability limit (0.307 kg/m³)
SELECT THE BEST LOCATION
h
= Installation height of the appliance (1.8 m for wall mounted)
0
SF
= Safety factor with a value of 0.75
OUTDOOR UNIT
**
The required minimum room area,
A
=
/ (SF x LFL x h
m
min
c
The higher value shall be taken when determining the room area.
It is advisable to
avoid more than 2
blockage directions.
Piping
Max.
For better ventilation
Piping size
Std.
Max.
Min. Piping
Max. Piping
Additional
Length for
Refrigerant
Length
Elevation
Length
Length
Refrigerant
Indoor A
min
(m²)
& multiple-outdoor
add. gas
Charge
(m)
(m)
(m)
(m)
(g/m)
Gas
Liquid
(m)
(kg)
installation, please
consult authorized
15
3
15
10
7.5
0.78
Not applicable (*)
9.52mm
dealer/specialist.
15
3
15
10
7.5
0.93
Not applicable (*)
(3/8")
15
3
15
10
7.5
0.93
Not applicable (*)
6.35mm
This illustration is for
5
12.7mm
15
3
15
10
7.5
0.97
Not applicable (*)
(1/4")
explanation purposes only.
(1/2")
15
3
30
15
7.5
1.49
Not applicable (*)
15.88mm
20
3
30
25
10
1.87
4.5120
(5/8")
, lower than 1.84kg are not subjected to any room area requirements.
c
OUTDOOR UNIT
AIR PURGING METHOD IS PROHIBITED FOR R32 SYSTEM
4
AIR TIGHTNESS TEST ON THE REFRIGERATING SYSTEM
Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation.
There is no extra refrigerant in the outdoor unit for air purging.
Before system is charged with refrigerant and before the refrigerating system is put into operation, below site
test procedure and acceptance criteria shall be vertifi ed by the certifi ed technicians, and/or the installer.
Be sure to check whole system for gas leakage.
B
Model
A
B
C
D
Z20***
(Step 1-2)
Z25***
570 mm
105 mm
18.5 mm
320 mm
Z35***
Z42***
540 mm
160 mm
18.5 mm
330 mm
Z50***
613 mm
131 mm
24 mm
360.5 mm
Z71***
(Step 3-4)
(Step 5-7)
For connection joint location at inside building
Refer to indoor installation instruction.
YES
(Step 8)
(Step 9-12)
NO
Torque
wrench
(Step 13)
Do not overtighten, overtightening may cause
gas leakage.
Piping size
Torque
6.35 mm (1/4")
[18 N•m (1.8 kgf•m)]
(Step 3-4)
9.52 mm (3/8")
[42 N•m (4.3 kgf•m)]
12.7 mm (1/2")
[55 N•m (5.6 kgf•m)]
15.88 mm (5/8")
[65 N•m (6.6 kgf•m)]
19.05 mm (3/4")
[100 N•m (10.2 kgf•m)]
(Step 14-18)
Notes:
Recommended use of any of the following leak detector,
2
(3/4 ~ 1.75HP) or 4 x 2.5 mm
2
(2.0 ~ 2.5HP) fl exible cord, type designation
I) Universal Sniffer leak detector
II) Electronic halogen leak detector
III) Ultrasonic Leak Detector
S1
2
3
6
L
1
N
S1
2
3
PIPING INSULATION
5
of indoor unit.
WARNING
Earth wire shall be Yellow/Green (Y/G) in
1.
Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram.
colour and longer than other AC wires for
Please wrap the insulated piping end to prevent water from going inside the piping.
safety reason.
2.
If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using
POLY-E FOAM with thickness 6 mm or above.
CHECK ITEMS
Is there any gas leakage at fl are nut
connections?
Has the heat insulation been carried out at fl are
nut connection?
Is the connection cable being fi xed to terminal
board fi rmly?
Hose
Drain elbow 1
Is the connection cable being clamped fi rmly?
Install the hose at an angle so that the
water smoothly fl ows out.
(5/4)
x h
)) ²
** not less than safety factor margin
0
A
, shall also be governed by the safety factor margin formula below :
min
)
0
Connection cable
Liquid side piping (
)
Gas side piping (
)
Additional drain hose
(
)
Installation parts you
should purchase (
)
1)
Connect a charging hose with a push pin to the Low side of a charging set
and the service port of the 3-way valve.
2)
Attach the gauge manifold set correctly and tightly. Make sure that both
valves of the manifold gauge (low pressure and high pressure) is in close
position.
3)
Connect the center hose of the manifold gauge to a vacuum pump.
4)
Turn on the power switch of the vacuum pump, then turn open the low
side manifold gauge valve and make sure that the needle in the gauge
moves from 0cmHg (0 MPa) to –76 cmHg (–0.1 MPa). This process
continues for approximately ten minutes. Then close the low side manifold
gauge valve.
5)
Remove the vacuum pump from the centre hose and connect the center
hose to cylinder of any applicable inert gas as test gas.
6)
Charge test gas into the system and wait until the pressure within the
system to reach min. 1.04MPa (10.4barg).
7)
Wait and monitor the pressure reading on the gauges. Check if there
is any pressure drop. Waiting time depends on the size of the system.
8)
If there is any pressure drop, perform step 9-12. If there is no pressure drop,
perform step 13.
9)
Use Gas Leak Detector to check for leaks. Must use the detection
equipment with a sensitivity of 5 grams per year of test gas or better.
10) Move the probe along the air conditioning system to check for leaks,
and mark for repair.
11) Any leak detected and marked shall be repaired.
12) After repair, repeat evacuation steps 3-4 and tightness test steps 5-7.
Check the pressure drop as in step 8.
13) If no leak,
Recover the test
Liquid side
Indoor unit
Outdoor unit
gas. Perform
Two-way valve
evacuation of
steps 3-4.
Close
Then proceed to
Gas side
step 14.
Three-way valve
Tank
OPEN
Cylinder
Close
Vacuum
Inert
CLOSE
pump
gas
14) Disconnect the
charging hose from the service port of the 3-way valve.
15) Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a
torque wrench.
16) Remove the valve caps of both of the 2-way valve and 3-way valve.
17) Open both of the valves, using a hexagonal wrench (4mm).
18) Mount back the valve caps onto the 2-way valve and the 3-way valve to
complete this process.
Is the earth wire connection properly done?
Is the power supply voltage complied with rated
value?
Is there any abnormal sound?
Is the cooling/heating operation normal?
Is the thermostat operation normal?
ENGLISH
ACXF60-33670-AA
PRINTED IN MALAYSIA
10/29/2018 5:28:29 PM
10/29/2018 5:28:29 PM

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic CU-Z20VKE Series

  • Page 1 Before a new refrigerating system is put into service, the person responsible for placing the system in operation should ensure that trained and certifi ed operating personnel are instructed on the 12. Recovery basis of the instruction manual about the construction, supervision, operation and maintenance of the refrigerating system, as well as the safety measures to be observed, and the properties and •...
  • Page 2 – This Air Conditioner contains and operates with refrigerant R32. THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED BY QUALIFIED PERSONNEL. Refer to Commonwealth, State, Territory and local legislation, regulations, codes, installation & operation manuals, before the installation, maintenance and/or service of this product. © Panasonic Corporation 2018.
  • Page 3 CAUTION Before performing any of the electrical installation works, please verify on which of the intended connection use. Generally there are 2 types of indoor-outdoor connections: ○ Single Connection (Single Indoor Unit connects with Single Outdoor Unit) ○ Multiple Connection (Multiple Indoor Unit connect with Single Outdoor Unit) Both connections have different connecting methods.
  • Page 4: Table Of Contents

    TABLE OF CONTENTS PAGE PAGE Safety Precautions ..........5 13.4 New installation, Relocation, Repairing of       Refrigerant Cycle System The Precaution for Using R32 Refrigerant ....8     Procedures ..........64   Specifications ........... 12     13.5 Piping installation of R32 ......
  • Page 5   CS-XZ50VKEW ........148   19.3 Outdoor Electronic Controller Removal   Procedure ..........156   19.4 ‘Panasonic Comfort Cloud’ App Setting   Procedure [After Replace Main Printed Circuit Board or Change the Indoor Unit] ............159   Technical Data ..........171     20.1 Cool Mode Performance Data ....171...
  • Page 6: Safety Precautions

    1. Safety Precautions  Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.  Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed. ...
  • Page 7 WARNING Do not perform flare connection inside a building or dwelling or room, when joining the heat exchanger of indoor unit with interconnecting piping. Refrigerant connection inside a building or dwelling or room must be made by brazing or welding. Joint connection of indoor unit by flaring method can only be made at outdoor or at outside of a building or dwelling or room.
  • Page 8 CAUTION Do not touch the sharp aluminium fin, sharp parts may cause injury. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture. Select an installation location which is easy for maintenance. Incorrect installation, service or repair of this air conditioner may increase the risk of rupture and this may result in loss damage or injury and/or property.
  • Page 9: Precaution For Using R32 Refrigerant

    2. Precaution for Using R32 Refrigerant  The basic installation work procedures are the same as conventional refrigerant (R410A, R22) models. However, pay careful attention to the following points: WARNING Since the working pressure is higher than that of refrigerant R22 models, some of the piping and installation and service tools are special.
  • Page 10 CAUTION 2-5. No ignition sources  No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. He/She must not be smoking when carrying out such work.
  • Page 11 CAUTION Leak detection methods  Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re- calibration. (Detection equipment shall be calibrated in a refrigerant-free area.)  Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. ...
  • Page 12 CAUTION Labelling  Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant.  The label shall be dated and signed.  Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. Recovery ...
  • Page 13: Specifications

    3. Specifications Indoor CS-Z20VKEW / CS-XZ20VKEW CS-Z25VKEW / CS-XZ25VKEW Model Outdoor CU-Z20VKE CU-Z25VKE Performance Test Condition EUROVENT EUROVENT Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 0.75 2.05 2.40 0.85 2.50 3.20 Capacity BTU/h 2560 6990 8180...
  • Page 14 Indoor CS-Z20VKEW / CS-XZ20VKEW CS-Z25VKEW / CS-XZ25VKEW Model Outdoor CU-Z20VKE CU-Z25VKE Type Hermetic Motor (Rotary) Hermetic Motor (Rotary) Compressor Motor Type Brushless Motor (6-poles) Brushless Motor (6-poles) Output Power Type Cross-Flow Fan Cross-Flow Fan Material ASG20K1 ASG20K1 Motor Type DC Motor (8-poles) DC Motor (8-poles) Input Power 47.3...
  • Page 15 Indoor CS-Z20VKEW / CS-XZ20VKEW CS-Z25VKEW / CS-XZ25VKEW Model Outdoor CU-Z20VKE CU-Z25VKE Height mm (inch) 295 (11-5/8) / 542 (21-11/32) 295 (11-5/8) / 542 (21-11/32) (I/D / O/D) Width Dimension Unit mm (inch) 919 (36-3/16) / 780 (30-23/32) 919 (36-3/16) / 780 (30-23/32) (I/D / O/D) Depth mm (inch)
  • Page 16 Indoor CS-Z35VKEW / CS-XZ35VKEW CS-Z42VKEW Model Outdoor CU-Z35VKE CU-Z42VKE Performance Test Condition EUROVENT EUROVENT Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 0.85 3.50 4.00 0.85 4.20 5.00 Capacity BTU/h 2900 11900 13600 2900 14300 17100 Kcal/h...
  • Page 17 Indoor CS-Z35VKEW / CS-XZ35VKEW CS-Z42VKEW Model Outdoor CU-Z35VKE CU-Z42VKE Type Hermetic Motor (Rotary) Hermetic Motor (Rotary) Compressor Motor Type Brushless Motor (6-poles) Brushless Motor (6-poles) Output Power Type Cross-Flow Fan Cross-Flow Fan Material ASG20K1 ASG20K1 Motor Type DC Motor (8-poles) DC Motor (8-poles) Input Power 47.3...
  • Page 18 Indoor CS-Z35VKEW / CS-XZ35VKEW CS-Z42VKEW Model Outdoor CU-Z35VKE CU-Z42VKE Height mm (inch) 295 (11-5/8) / 542 (21-11/32) 295 (11-5/8) / 619 (24-3/8) (I/D / O/D) Width Dimension Unit mm (inch) 919 (36-3/16) / 780 (30-23/32) 919 (36-3/16) / 824 (32-15/32) (I/D / O/D) Depth mm (inch)
  • Page 19 Indoor CS-Z50VKEW / CS-XZ50VKEW CS-Z71VKEW Model Outdoor CU-Z50VKE CU-Z71VKE Performance Test Condition EUROVENT EUROVENT Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 0.98 5.00 6.00 0.98 7.10 8.50 Capacity BTU/h 3340 17100 20500 3340 24200 29000 Kcal/h...
  • Page 20 Indoor CS-Z50VKEW / CS-XZ50VKEW CS-Z71VKEW Model Outdoor CU-Z50VKE CU-Z71VKE Type Hermetic Motor (Rotary) Hermetic Motor (Rotary) Compressor Motor Type Brushless (4-poles) Brushless (4-poles) Output Power 1.70k Type Cross-Flow Fan Cross-Flow Fan Material ASG33 ASG33 Motor Type DC Motor (8-poles) DC Motor (8-poles) Input Power 89.0 105.0...
  • Page 21 Indoor CS-Z50VKEW / CS-XZ50VKEW CS-Z71VKEW Model Outdoor CU-Z50VKE CU-Z71VKE Height mm (inch) 302 (11-29/32) / 695 (27-3/8) 302 (11-29/32) / 695 (27-3/8) (I/D / O/D) Width Dimension Unit mm (inch) 1120 (44-1/8) / 875 (34-15/32) 1120 (44-1/8) / 875 (34-15/32) (I/D / O/D) Depth mm (inch)
  • Page 22  Multi Split Combination Possibility: A single outdoor unit enables air conditioning of up to two separate rooms for CU-2Z35TBE, CU-2Z41TBE, CU-2Z50TBE. A single outdoor unit enables air conditioning of up to three separate rooms for CU-3Z68TBE, CU-3Z52TBE. OUTDOOR UNIT CONNECTABLE INDOOR UNIT CU-2Z35TBE CU-2Z41TBE...
  • Page 23  Multi Split Combination Possibility: A single outdoor unit enables air conditioning of up to four separate rooms for CU-4Z68TBE, CU-4Z80TBE. A single outdoor unit enables air conditioning of up to five separate rooms for CU-5Z90TBE. OUTDOOR UNIT CONNECTABLE INDOOR UNIT CU-4Z68TBE CU-4Z80TBE CU-5Z90TBE...
  • Page 24  Multi Split Combination Possibility: A single outdoor unit enables air conditioning of up to two separate rooms for CU-2E12SBE, CU-2E15SBE, CU-2E18SBE. A single outdoor unit enables air conditioning of up to three separate rooms for CU-3E23SBE, CU-3E18PBE. OUTDOOR UNIT CONNECTABLE INDOOR UNIT CU-2E12SBE* CU-2E15SBE*...
  • Page 25  Multi Split Combination Possibility: A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E23PBE, CU-4E27PBE. A single outdoor unit enables air conditioning of up to five separate rooms for CU-5E34PBE. OUTDOOR UNIT CONNECTABLE INDOOR UNIT CU-4E23PBE* CU-4E27PBE* CU-5E34PBE*...
  • Page 26: Features

    4. Features  Inverter Technology Wider output power range Energy saving Quick Cooling Quick Heating More precise temperature control  Environment Protection Non-ozone depletion substances refrigerant (R32)  Long Installation Piping Long piping up to 15 meters (0.75 ~ 1.75HP), 20 meters (2.0HP) and 30 meters (2.5HP) during single split connection only ...
  • Page 27: Location Of Controls And Components

    5. Location of Controls and Components Indoor Unit Front panel Aluminium fin Auto OFF/ON button Use when remote control is misplaced or a malfunction occurs. Horizontal airflow direction louver Do not adjust by hand. Human activity sensor Sunlight Sensor and Vertical airflow direction louver Remote Control Receiver Do not adjust by hand.
  • Page 28: Dimensions

    6. Dimensions Indoor Unit 6.1.1 CS-Z20VKEW CS-Z25VKEW CS-Z35VKEW CS-Z42VKEW CS-XZ20VKEW CS-XZ25VKEW CS-XZ35VKEW <Top View> <Side View> <Front View> <Side View> Air intake direction 2 ±0.5 2 ±0.5 Left piping Air outlet Right piping hole direction hole <Bottom View> <Remote Control> Gas side <Rear View>...
  • Page 29 6.1.2 CS-Z50VKEW CS-Z71VKEW CS-XZ50VKEW <Top View> <Side View> <Front View> <Side View> Air intake 1120 direction Left piping Air outlet Right piping direction hole hole <Bottom View> <Remote Control> Liquid side <Rear View> Gas side <Remote Control Holder> (41-61) Relative position between the indoor unit and the installation plate <Front View> 741.4 16.5 Installation...
  • Page 30: Outdoor Unit

    Outdoor Unit 6.2.1 CU-Z20VKE CU-Z25VKE CU-Z35VKE <Top View> Space necessary for installation 67.6 (104.7) 570.3 104.9 60.5 100 mm 100 mm 1000 mm 2-way valve at Liquid side Anchor Bolt Pitch (High Pressure) × 3-way valve at Gas side (Low Pressure) <Side View>...
  • Page 31 6.2.3 CU-Z50VKE CU-Z71VKE <Top View> Space necessary for installation (131) 34.7 100 mm 100 mm 1000 mm Anchor Bolt Pitch 360.5 × 613 2-way valve at Liquid side (High Pressure) 3-way valve at Gas side (Low Pressure) <Front View> <Side View> <Side View>...
  • Page 32: Refrigeration Cycle Diagram

    7. Refrigeration Cycle Diagram CS-Z20VKEW CU-Z20VKE CS-Z25VKEW CU-Z25VKE CS-Z35VKEW CU-Z35VKE CS-Z42VKEW CU-Z42VKE CS-XZ20VKEW CU-Z20VKE CS-XZ25VKEW CU-Z25VKE CS-XZ35VKEW CU-Z35VKE INDOOR OUTDOOR LIQUID EXPANSION TEMP. SIDE VALVE MUFFLER STRAINER SENSOR 2-WAY VALVE PIPE TEMP. INTAKE SENSOR 2 TEMP. SENSOR CONDENSER PIPE TEMP. PIPE SENSOR 1 TEMP.
  • Page 33: Cs-Z50Vkew Cu-Z50Vke Cs-Z71Vkew Cu-Z71Vke Cs-Xz50Vkew Cu-Z50Vke

    CS-Z50VKEW CU-Z50VKE CS-Z71VKEW CU-Z71VKE CS-XZ50VKEW CU-Z50VKE INDOOR OUTDOOR LIQUID EXPANSION SIDE MUFFLER VALVE STRAINER 2-WAY (Z71VKE only) PROCESS VALVE TUBE TEMP. PIPE SENSOR TEMP. CONDENSER INTAKE SENSOR 2 TEMP. SENSOR PIPE TEMP. PIPE SENSOR 1 TEMP. SENSOR HEAT EXCHANGER (EVAPORATOR) SIDE 4-WAYS VALVE 3-WAY...
  • Page 34: Block Diagram

    8. Block Diagram CS-Z20VKEW CU-Z20VKE CS-XZ20VKEW CU-Z20VKE...
  • Page 35: Cs-Xz35Vkew Cu-Z35Vke

    CS-Z25VKEW CU-Z25VKE CS-Z35VKEW CU-Z35VKE CS-Z42VKEW CU-Z42VKE CS-XZ25VKEW CU-Z25VKE CS-XZ35VKEW CU-Z35VKE...
  • Page 36: Cs-Z50Vkew Cu-Z50Vke Cs-Z71Vkew Cu-Z71Vke

    CS-Z50VKEW CU-Z50VKE CS-Z71VKEW CU-Z71VKE...
  • Page 37: Wiring Connection Diagram

    9. Wiring Connection Diagram Indoor Unit...
  • Page 38: Outdoor Unit

    Outdoor Unit 9.2.1 CU-Z20VKE YELLOW (YEL) TO INDOOR UNIT BLUE (BLU) RED (RED) REACTOR (TRADEMARK) TERMINAL BOARD COMPRESSOR TERMINAL THE PARENTHESIZED LETTERS IS INDICATED ON TERMINAL COVER FUSE105 RAT2 RAT1 DATA (15A 250V) (GRY) (GRY) (RED) OUTDOOR AIR TEMP. SENSOR (THERMISTOR) NOISE FILTER t°...
  • Page 39 9.2.2 CU-Z25VKE CU-Z35VKE CU-Z42VKE CU-Z50VKE CU-Z71VKE YELLOW (YLW) OR (C) REMARKS BLU: BLUE BLUE BLK: BLACK TO INDOOR UNIT (BLU) (RED) WHT: WHITE OR (R) OR (S) RED: RED YLW: YELLOW (TRADEMARK) TERMINAL REACTOR GRY: GRAY COMPERSSOR TERMINAL BOARD GRN: GREEN THE PARENTHESIZED LETTERS IS INDICATED ON TERMINAL COVER RAT2...
  • Page 40: Electronic Circuit Diagram

    10. Electronic Circuit Diagram 10.1 Indoor Unit F303 CN-NANO ELECTRONIC CONTROLLER (SUB) 12V_1 (YLW) 500mA R108 -20V (WHT) NANOE R109 (WHT) GENERATOR 4.7k 100mA C401 4.7k 12V_2 5V_3 100mA 5V_3 RY-PWR C400 R406 R401 CN-WLAN R405 NONE (BLK) CN-WLAN RY-PWR (WHT) RY-PWR2 C402...
  • Page 41: Outdoor Unit

    10.2 Outdoor Unit 10.2.1 CU-Z20VKE TO INDOOR UNIT REACTOR TERMINAL BOARD FUSE105 RAT2 RAT1 DATA (15A 250V) (GRY) (GRY) (RED) CN-TH R206 R205 (WHT) 15.8k OUTDOOR AIR TEMP. SENSOR t° (THERMISTOR) PIPING TEMP. SENSOR t° (THERMISTOR) NOISE FILTER COMMUNICATION CIRCUIT COMP.
  • Page 42 10.2.2 CU-Z25VKE CU-Z35VKE CU-Z42VKE CU-Z50VKE CU-Z71VKE TO INDOOR UNIT TERMINAL REACTOR BOARD RAT2 RAT1 DATA (GRY) (GRY) (RED) COMMUNICATION NOISE FILTER CIRCUIT FUSE 5 AC-BLK CIRCUIT (20A 250V) 15.8k (BLK) 470u FUSE 1 FOR Z25/35/42VK (20A 250V) FUSE 6 FUSE 8 FOR Z50/71VK OUTDOOR AIR TEMP.
  • Page 43: Printed Circuit Board

    11. Printed Circuit Board 11.1 Indoor Unit 11.1.1 Main Printed Circuit Board AC303 RY-PWR CN-FM CN-DATA2 CN-CNT CN-STM2 CN-STM3 CN-DATA1 CN-STM1 CN-RMT CN-TH CN-DATA3 CN-DISP CN-RCV JP1 (Random Auto Restart enable/disable)
  • Page 44 11.1.2 Indicator Printed Circuit Board (CS-Z20/25/35/42VKEW) LED205 LED203 LED201 LED206 LED204 LED202 CN-DISP 11.1.3 Receiver Printed Circuit Board (CS-Z20/25/35/42VKEW) CN-RCV 11.1.4 Sub Printed Circuit Board AC302 AC306 ACL501 CN-NANO...
  • Page 45 11.1.5 Indicator & Receiver Printed Circuit Board (CS-Z50/71VKEW) LED205 LED203 LED201 LED206 LED204 LED202 CN-DISP...
  • Page 46: Outdoor Unit

    11.2 Outdoor Unit 11.2.1 Main Printed Circuit Board 11.2.1.1 CU-Z20VKE POWER TRANSISTOR (IPM) CN-MTR2 CN-MTR1 CN-HOT CN-TH CN-TANK CN-STM AC-WHT DATA AC-BLK...
  • Page 47 11.2.1.2 CU-Z25VKE CU-Z35VKE CU-Z42VKE POWER TRANSISTOR (IPM) CN-MTR2 CURRENT TRANSFORMER (CT) CN-MTR1 CN-STM1 CN-TH1 CN-HOT DATA CN-TANK AC-WHT AC-BLK...
  • Page 48 11.2.1.3 CU-Z50VKE CU-Z71VKE POWER TRANSISTOR (IPM) CN-MTR2 CURRENT TRANSFORMER (CT) CN-MTR1 CN-STM1 CN-TH1 CN-HOT DATA CN-TANK AC-WHT AC-BLK...
  • Page 49: Installation Instruction

    12. Installation Instruction 12.1 Select the Best Location 12.1.1 Indoor Unit 12.1.2 Indoor/Outdoor Unit Installation  Diagram Do not install the unit in excessive oil fume area such as kitchen, workshop and etc.  There should not be any heat source or steam Piping direction (Front side) near the unit.
  • Page 50: Indoor Unit

    12.2 Indoor Unit 12.2.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent it from vibration. Ceiling Wall Wall More than 1 More than 1 2 screw More Indoor unit than 2 Installation 266 mm plate 1 266 mm...
  • Page 51 12.2.2 To Drill a Hole in the Wall and Install a Sleeve of Piping Wall Indoor Outdoor Insert the piping sleeve to the hole. Fix the bushing to the sleeve. 15 mm Cut the sleeve until it extrudes about 15 mm Approx.
  • Page 52 12.2.3 Indoor Unit Installation ● Do not turn over the unit without it’s shock absorber during pull out the piping. It may cause intake grille damage. ● Use shock absorber during pull out the piping to protect the intake grille from damage. Piping Piping Shock absorber...
  • Page 53 Exchange the drain hose and the cap Rear view for left piping installation Connection cable Piping More than 950 mm (1/2 ~ 1.75HP) or Drain hose 1150 mm (2.0 ~ 2.5HP) Connection cable Drain hose Drain hose Drain cap Sleeve for piping hole Adjust the piping slightly downwards.
  • Page 54 Remove the tapes and connect the power supply cord and connection cable between indoor unit and outdoor unit according to the diagram below. Terminals on the outdoor unit Colour of wires (connection cable) Terminals on the indoor unit (Power supply cord) Connection for multi inverter model (Outdoor power Terminals on the isolating devices...
  • Page 55 12.2.4.1 Wire Stripping Connecting and Requirement RISK OF FIRE JOINING OF WARNING WIRES MAY CAUSE OVERHEATING AND FIRE. Wire stripping Do not joint wires No loose strand when inserted Indoor/outdoor connection Use complete wire without joining. terminal board Use approved socket and plug with earth pin. 5 mm or more Wire connection in this area must follow to national (gap between wires)
  • Page 56 12.2.5.2 Connecting the Piping to Outdoor Decide piping length and then cut by using pipe cutter. Do not overtighten, overtightening may cause gas leakage. Remove burrs from cut edge. Piping size Torque Make flare after inserting the flare nut (locate at valve) onto the copper pipe.
  • Page 57 12.2.6 How to Take Out Front Grille Please follow the steps below to take out front grille if Screw necessary such as when servicing. Front Set the vertical airflow direction louvers to the grille horizontal position. Vane (Move the Remove the 2 caps (1/2 ~ 1.75HP) or 3 caps vane to (2.0 ~ 2.5HP) on the front grille as shown in downward)
  • Page 58 12.2.9 How to Replace Network Adapter  Remove the front grille (refer how to take out front grille) from the unit.  Remove the network adapter box by releasing the hook (Figure 1.0).  Remove the cover by unclipping it and pulling it out (Figure 1.1). ...
  • Page 59: Installation And Servicing Air Conditioner Using R32

    13. Installation and Servicing Air Conditioner using R32 13.1 About R32 Refrigerant For air conditioning refrigerants such as R410A, the refrigerants were collected back in order to prevent their air dissipation, to curbe the global warming impact, in case they were released into the atmosphere. In the “4th Environmental Basic Plan”, 80% reduction of greenhouse gas emissions by 2050 is required, and due to this requirement, further reduction in the emission of high greenhouse effect gas, such as CFCs, is required.
  • Page 60 2. Characteristic of Pressure As shown in Table 2, R32 does not have much difference in vapor pressure at the same refrigerant temperature comparing to R410A, but comparing to R22, it is higher at 1.6 times more. Thus, the same as in case of R410A, it is necessary to do installation and service using high-pressure tools and components.
  • Page 61: Refrigerant Piping Installation • Tools Used In Services

    13.3 Refrigerant piping installation • Tools used in services 13.3.1 Required Tools R32 refrigerant air conditioners use the common parts as R410A air conditioners for two-way valves and three-way valves (diameters of service ports); thus, they maintain commonality in the maintenance of the compressive strength, the size of pipe flaring, and the size of flare nuts as R410A.
  • Page 62 3. Torque wrenches (diameters 1/2, 5/8) Manifold gauges / Charging hoses In order to strengthen the compressive strength, the diameters of wrenches change depending on the flare nut sizes. Torque wrenches Differences in charging hoses Differences in torque wrenches (common R410A) Normal 5.1 MPa 3.4 MPa...
  • Page 63 7. HFC refrigerant_Electric gas leakage tester 9. Refrigerant cylinders R32 refrigerant is often used for other mixed Refrigerant cylinders for R410A are painted in pink, refrigerant (R410A, R404A, R407C etc.). Therefore, and the ones for R32 are painted in other colors that the usage of existing HFC detectors is possible, but in might subject to change according to the international order to detect more accurately, we recommend to...
  • Page 64 11. Tools used for refrigerant piping installations and services Tools for R410A Common with R32 Possibility of usage for R22 ○ ○ Pipe cutters, reamers or scrapers ○ ○ Flare tools (clutch type) ○ ○ Torque wrench (1/4, 3/8) ○ ×...
  • Page 65: New Installation, Relocation, Repairing Of Refrigerant Cycle System The Procedures

    13.4 New installation, Relocation, Repairing of Refrigerant Cycle System The Procedures Relocation Repairing refrigerant cycle Installation Indoor / outdoor units and piping Pump down Refrigerant recovery • Displacing pipes and wires, and displacing indoor / outdoor units Prevention of impurity •...
  • Page 66: Piping Installation Of R32

    13.5 Piping installation of R32 13.5.1 Pipe materials used and flaring Copper pipes are used for refrigerant piping. Pipes Pipe thickness which comply with JIS Regulations need to be used. Room air conditioners which use R410A and R32 O and OL materials Thickness (mm) have higher pressure;...
  • Page 67: Installation, Relocation, And Service

    13.6 Installation, Relocation, and Service 13.6.1 Air purge and gas leak test for new installation (using new refrigerant pipes) using vacuum pump (From the point of view of global environment protection, do not release CFCs into the atmosphere during installation work) 1.
  • Page 68 13.6.2 Process of refrigerant recovery 1. Connect the center charging hose of manifold gauge to the in-let side of recovery device. 2. Connect the valves of the discharge side of recovery device and liquid side of refrigerant cylinder with red hose (charging hose).
  • Page 69 13.6.3 Relocation 1. Removing the air conditioning unit a) Recovery of outdoor unit refrigerant by pumping down Press “forced cooling button” (as a general rule, since 1998 the name of cooling testing button is changed, and this name is unified within the air conditioning industry), and then you are able to start cooling operation in which the room temperature is low, and you can recover the refrigerant from the outdoor unit.
  • Page 70 13.6.6 Re-insertion of refrigerant in service When re-insertion is needed, follow the procedures to ensure the insertion of new refrigerant at correct amount. 1. Attach charging hose (blue) to the service port of the outdoor unit. 2. Attach charging hose (red) to the vacuum pump. Fully open the 2-way and 3-way valves. 3.
  • Page 71: Repairing Of Refrigerant Cycle / Brazing Point

    13.7 Repairing of refrigerant cycle / Brazing point 13.7.1 Preparation for repairing of refrigerant cycle / brazing Brazing which is a technique needed for repairing refrigerant cycle requires advanced technique and experience, and this brazing procedure can only be performed by the workers who completed “Gas Welding Skill Training” regulated by the Occupational Safety and Health Act, and went through the training programs of refrigerant operations.
  • Page 72 2. Cylinder without adjustment valve side gauge pressure is adjusted by the adjuster. Check the both side valves of the torch and open the cylinder valve to check the remaining refrigerant in the cylinder. Caution: Do not attach oil component on the connection port of the adjuster. Especially, use an oxygen cylinder adjuster which is no oil substance type.
  • Page 73 13.7.5 Types of flame Types of flame change based on the proportion of propane and oxygen. [Neutral Flame] Perform brazing with this flame (This is a flame when oxygen and propane are mixed at proper proportion, and has lesser effect on the brazed metals) White core flame 10 ~ 15 mm...
  • Page 74 13.7.7 Selection of brazing material Use BAg brazing material (silver solder) to increase the welding performance. Tensile strength Composition of ingredients (%) Temperature (°C) Characteristics (Reference) Category Standard Brazing Base Number Solidus Liquidus Kgf•cm applications temp material Liquidity is good at low temperature, 49.0 14.5...
  • Page 75 13.7.10 Checking of brazing (insert) points 1. No impurity on the brazing point Gap 0.025 ~ 0.05 mm If dirt or oil is attached on the brazing point, the brazing filler metal does not reach to junction, and Inner diameter ø6.45 it may cause poor welding.
  • Page 76 (Reference) Melting temperature of copper • • • • • • • Approx. 1083°C Maximum temperature obtained in propane and oxygen • • • • • • • Approx. 1083°C The important point is to heat the bonding part uniformly within a short period of time until reaching to the brazing temperature in the following manner.
  • Page 77: Reference> Analysis Method For No Error Code, No Cooling / No Warming

    13.8 <Reference> Analysis method for no error code, no cooling / no warming 13.8.1 Preparation for appropriate diagnosis In order to obtain appropriate operation characteristics, minimum 15 minutes or more operation time [testing operation (rated operation)] is required. 1. Method of rated operation (rated operation) For the models which have two buttons of “emergency operation and forced cooling operation”, press forced cooling button once.
  • Page 78 1. Measuring temperature 1) Indoor unit suction temperature, release temperature, temperature difference, → Measure by thermometer 2) 2-way valve pipe temperature in cooling mode is low temperature (benchmark:5 ~ 10°C), in heating mode is medium temperature (benchmark:25 ~ 35°C). 3) 3-way valve pipe temperature in cooling mode is low temperature (benchmark:7 ~ 15°C) in heating mode is high temperature (benchmark:38 ~ 50°C).
  • Page 79: Operation Control

    14. Operation Control 14.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
  • Page 80: Indoor Fan Motor Operation

    14.1.5 Automatic Operation  This mode can be set using remote control and the operation is decided by remote control setting temperature, remote control operation mode and indoor intake air temperature.  During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the indoor intake air temperature.
  • Page 81: Outdoor Fan Motor Operation

    [Heating]  According to indoor pipe temperature, automatic heating fan speed is determined as follows. B. Feedback control  Immediately after the fan motor started, feedback control is performed once every second.  During fan motor on, if fan motor feedback ≥ 2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error counter increase, fan motor is then stop and restart.
  • Page 82: Airflow Direction

    14.4 Airflow Direction  There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).  Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using remote control).
  • Page 83 Side View (Inner Vane) Reference point 128º (Z20/25/35/42VK & XZ20/25/35VK) 148º (Z50/71VK & XZ50VK) Step 1 Stopper Step 2 Step 3 Closed Position Step 4 Step 5 Side View (Outer Vane) Closed Stopper Position 156º (Z20/25/35/42VK & XZ20/25/35VK) 101º (Z50/71VK & XZ50VK) Reference point Step 1 Step 2...
  • Page 84 14.4.2 Horizontal Airflow  Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the angles as stated below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below.
  • Page 85: Quiet Operation (Cooling Mode/Cooling Area Of Dry Mode)

    14.5 Quiet Operation (Cooling Mode/Cooling Area of Dry Mode)  Purpose To provide quiet cooling operation compare to normal operation.  Control condition Quiet operation start condition  When “POWERFUL/QUIET” button at remote control is pressed twice. QUIET will be shown on remote control display. Quiet operation stop condition ...
  • Page 86: Timer Control

    14.8 Timer Control  There are 2 sets of ON and OFF timer available to turn the unit ON or OFF at different preset time.  If more than one timer had been set, the upcoming timer will be displayed and will activate in sequence. 14.8.1 ON Timer Control ...
  • Page 87: Auto Restart Control

    Control pattern:  Cooling mode Sleep Function activated Unit Off Normal Setting +1°C Temperature +1°C -2°C +1°C minutes minutes minutes minutes minutes minutes Setting Set Speed Set Speed Set Speed Set Speed Set Speed Fan Speed 0.5 hr 1.0 hr 2.0 hr Selection of 3.0 hr...
  • Page 88: Indication Panel

    14.11 Indication Panel POWER TIMER nanoe X Color White White White White Wireless LAN Mode Light ON Operation ON Timer Setting ON nanoe ON Wireless LAN Mode Light OFF Operation OFF Timer Setting OFF nanoe OFF Note:  If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation mode judgment, or ON timer sampling.
  • Page 89  Power failure During nanoe X individual operation, if power failure occurs, after power resumes, nanoe X individual operation resumes immediately. During combination operation, if power failure occurs, after power resumes, combination operation resume immediately.  nanoe X check mode To enable nanoe X check mode, during nanoe X operation ON:...
  • Page 90: Mild Dry Cooling Operation

    However, there is no guarantee that the APP will work well with all Android OS version.  The Network Adaptor is designed specifically as a terminal for Panasonic Comfort Cloud app.  The Wireless LAN network coverage must reach the air conditioner installation location.
  • Page 91   Google Play Open Open App Store   Search for Panasonic Comfort Cloud app. Search for Panasonic Comfort Cloud app.   Download and install. Download and install. Note  The app user interface image may change for version upgrade without notification.
  • Page 92  Cancel Condition: From the module the reply data or the regularly sending data (normal data) is recognized by ID micon. Wireless LAN LED Timer LED When failure canceled Light up No light  Failure communication parameter setting. H85 communication error: time/retry counter 10 min/3 count Wireless LAN disconnection judgment time 300 sec...
  • Page 93: Operation Control (For Multi Split Connection)

    15. Operation Control (For Multi Split Connection) During multi split connection, indoor unit’s operation controls are same with single split connection unless specified in this chapter. 15.1 Cooling operation 15.1.1 Thermostat control  Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting temperature <...
  • Page 94: Automatic Operation

    15.4 Automatic Operation  This mode can be set using remote control and the operation is decided by remote control setting temperature, remote control operation mode, indoor intake and outdoor air temperature.  During operation mode judgment, indoor fan motor (with speed of -Lo) and outdoor fan motor are running for 30 seconds to detect the indoor intake and outdoor air temperature.
  • Page 95: Protection Control

    16. Protection Control 16.1 Protection Control for All Operations 16.1.1 Restart Control (Time Delay Safety Control)  The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by pressing OFF/ON button at remote control within this period. ...
  • Page 96 Compressor = OFF 103°C 88°C Compressor Frequency Reduce 99°C 87°C Compressor Frequency Maintain 96°C 86°C Free Comp. temperature 16.1.5 Low Pressure Prevention Control (Gas Leakage Detection)  Control start conditions For 5 minutes, the compressor continuously operates and outdoor total current is between 0.36A and 0.54A (Z25/35/42/50/71VKE), between 0.29A and 0.44A (Z20VKE).
  • Page 97: Protection Control For Cooling & Soft Dry Operation

    16.2 Protection Control for Cooling & Soft Dry Operation 16.2.1 Outdoor Air Temperature Control  The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below.  This control will begin 1 minute after the compressor starts. ...
  • Page 98: Protection Control For Heating Operation

    16.2.5 Dew Prevention Control 1  To prevent dew formation at indoor unit discharge area.  This control will be activated if: Outdoor air temperature and Indoor pipe temperature judgment by microcontroller is fulfilled. When Cooling or Dry mode is operated more than 20 minutes or more. ...
  • Page 99 16.3.4 Low Temperature Compressor Oil Return Control  In heating operation, if the outdoor temperature falls below -10°C when compressor starts, the compressor frequency will be regulated up to 600 seconds. 16.3.5 Cold Draught Prevention Control  When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced. 16.3.6 Deice Operation ...
  • Page 100: Servicing Mode

    17. Servicing Mode 17.1 Auto OFF/ON Button AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto OFF/ON button is pressed. This operation can be used to operate air conditioner with limited function if remote control is misplaced or malfunction. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE) The Test Run operation will be activated if the Auto OFF/ON button is pressed continuously for more than 5 seconds.
  • Page 101: Heat Only Operation

    REMOTE CONTROL RECEIVING SOUND OFF/ON MODE The Remote Control Receiving Sound OFF/ON Mode will be activated if the Auto OFF/ON button is pressed continuously for more than 16 seconds (4 “beep” sounds will occur at 16th seconds to identify the Remote Control Receiving Sound Off/On Mode is in standby condition) and press “AC Reset”...
  • Page 102 17.2.2 Operation mode during Heating Only Operation  The table below shows the operation mode comparison when Heating Only Operation Mode Activated and Deactivated. Operation Heating Only Operation Mode Activated Heating Only Operation Mode Deactivated Mode After 30s sampling, the unit will judge the operation After 30s sampling, regardless of the indoor intake or mode base on remote controller temperature setting and AUTO...
  • Page 103: Remote Control Button

    17.3 Remote Control Button 17.3.1 SET Button  To check remote control transmission code and store the transmission code to EEPROM. Press “Set” button by using pointer. Press “Timer Set” button until a “beep” sound is heard as confirmation of transmission code change. LCD returns to original display if remote control does not operate for 30 seconds.
  • Page 104  To limit set temperature range for COOL & DRY, HEAT mode. Press “Set” button by using pointer. Press TEMP increment or decrement button to choose No. 3. Press Timer increment or decrement button to select desired temperature low limit of set temperature for COOL &...
  • Page 105 Press Timer Set button to confirm high limit selection. Press TEMP increment or decrement button to choose No. 5. Press Timer increment or decrement button to select desired temperature low limit of set temperature for HEAT mode. Normal display mode Press SW to enter customer zone &...
  • Page 106 17.3.2 RESET (RC)  To clear and restore the remote control setting to factory default. Press once to clear the memory 17.3.3 RESET (RC)  To restore the unit’s setting to factory default. Press once to restore the unit’s setting. 17.3.4 TIMER ...
  • Page 107 17.3.7 Customization mode LCD display area: Customization display area (highlighted in color) Function Options (If any) Cannot enter this customization mode under the following conditions: 1 Operation ON. 2 Under [Real/ON/OFF] time setting mode. To enter Customer zone: Normal display Customer Zone mode [range (1~49)]...
  • Page 108 Customization list table: Note: The functions described in the table may not be applicable to the model and may subject to change without further notice. Customization Options Remark Name Remote control number selection A, B, C, D Solar radiation sensitivity level adjustment 1, 2, 3, 4, 5 [iAUTO-X/iAUTO/iCOMF, Cool &...
  • Page 109: Troubleshooting Guide

    18. Troubleshooting Guide 18.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no Normal Pressure and Outlet Air Temperature (Standard) electrical problems before inspecting the refrigeration cycle. Gas Pressure Outlet air Temperature Such problems include insufficient insulation, problem with the (kg/cm (°C) power source, malfunction of a compressor and a fan.
  • Page 110 18.1.1 Relationship Between the Condition of the Air Conditioner and Pressure and Electric Current Cooling Mode Heating Mode Condition of the Electric current Electric current air conditioner Low Pressure High Pressure Low Pressure High Pressure during operation during operation Insufficient refrigerant ...
  • Page 111: Breakdown Self Diagnosis Function

    18.2 Breakdown Self Diagnosis Function 18.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code)  Once abnormality has occurred during operation, the unit will stop its operation, and Timer LED blinks.  Although Timer LED goes off when power supply is turned off, if the unit is operated under a breakdown condition, the LED will light up again.
  • Page 112: Error Codes Table

    18.3 Error Codes Table Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation No memory of failure — Normal operation — — Indoor fan only  Indoor/outdoor wire terminal Indoor/outdoor operation can Indoor/outdoor After operation for ...
  • Page 113 Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation  Check indoor/outdoor Wrong wiring and connection wire and connection Abnormal wiring or — — connecting pipe, expansion pipe piping connection valve abnormality  Expansion valve and lead wire and connector ...
  • Page 114: Self-Diagnosis Method

    18.4 Self-diagnosis Method 18.4.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions  During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused  Faulty indoor unit PCB.
  • Page 115 18.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched) Malfunction Decision Conditions  During startup, error code appears when different types of indoor and outdoor units are interconnected. Malfunction Caused  Wrong models interconnected.  Wrong indoor unit or outdoor unit PCBs mounted. ...
  • Page 116 18.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 117 18.4.4 H15 (Compressor Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection.  Faulty sensor.
  • Page 118 18.4.5 H16 (Outdoor Current Transformer) Malfunction Decision Conditions  An input current, detected by Current Transformer CT, is below threshold value when the compressor is operating at certain frequency value for 3 minutes. Malfunction Caused  Lack of gas  Broken CT (current transformer) ...
  • Page 119 18.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions  The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550 rpm or < 50 rpm) Malfunction Caused ...
  • Page 120 18.4.7 H23 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 121 18.4.8 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 122 18.4.9 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 123 18.4.10 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 124 18.4.11 H32 (Outdoor Heat Exchanger Temperature Sensor 2 Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor heat exchanger temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection.
  • Page 125 18.4.12 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions  The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused  Wrong models interconnected.  Wrong indoor unit and outdoor unit PCBs used.  Indoor unit or outdoor unit PCB defective.
  • Page 126 18.4.13 H34 (Outdoor Heat Sink Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor heat sink temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 127 18.4.14 H36 (Outdoor Gas Pipe Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 128 18.4.15 H37 (Outdoor Liquid Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions  During startup and operation of cooling and heating, the temperatures detected by the outdoor liquid pipe temperature sensor are used to determine sensor errors. Malfunction Caused  Faulty connector connection. ...
  • Page 129 18.4.16 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions  The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused  Operation stops due to short circuit inside the fan motor winding. ...
  • Page 130 18.4.17 H98 (Error Code Stored in Memory and no alarm is triggered / no TIMER LED flashing) Malfunction Decision Conditions  Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation. ...
  • Page 131 18.4.18 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Conditions  Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C) Malfunction Caused ...
  • Page 132 18.4.19 F11 (4-way Valve Switching Failure) Malfunction Decision Conditions  When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during cooling and compressor operating, the 4-way valve is detected as malfunction. Malfunction Caused ...
  • Page 133 18.4.20 F17 (Indoor Standby Units Freezing Abnormality) Malfunction Decision Conditions  When the different between indoor intake air temperature and indoor pipe temperature is above 10°C or indoor pipe temperature is below -1.0°C. Remark: When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor unit and H39 to other indoor unit(s).
  • Page 134 18.4.21 F90 (Power Factor Correction Protection) Malfunction Decision Conditions  To maintain DC voltage level supply to power transistor.  To detect high DC voltage level after rectification. Malfunction Caused  During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at the outdoor unit main PCB senses abnormal DC voltage level for power transistors.
  • Page 135 18.4.22 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions  The input current is low while the compressor is running at higher than the setting frequency. Malfunction Caused  Lack of gas.  3-way valve close. Troubleshooting...
  • Page 136 18.4.23 F93 (Compressor Rotation Failure) Malfunction Decision Conditions  A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused  Compressor terminal disconnect  Faulty Outdoor PCB  Faulty compressor Troubleshooting...
  • Page 137 18.4.24 F95 (Outdoor High Pressure Protection: Cooling or Soft Dry) Malfunction Decision Conditions  During operation of cooling or soft dry, when outdoor unit heat exchanger high temperature data is detected by the outdoor unit heat exchanger thermistor. Malfunction Caused ...
  • Page 138 18.4.25 F96 (IPM Overheating) Malfunction Decision Conditions  During operating of cooling and heating, when IPM temperature data (100°C) is detected by the IPM temperature sensor. Multi Models only Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated. Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is detected by the heat sink temperature sensor.
  • Page 139 18.4.26 F97 (Compressor Overheating) Malfunction Decision Conditions  During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the compressor tank temperature sensor. Malfunction Caused  Faulty compressor tank temperature sensor  2/3 way valve closed ...
  • Page 140 18.4.27 F98 (Input Over Current Detection) Malfunction Decision Conditions  During operation of cooling and heating, when an input over-current (X value in Total Running Current Control) is detected by checking the input current value being detected by current transformer (CT) with the compressor running.
  • Page 141 18.4.28 F99 (DC Peak Detection) Malfunction Decision Conditions During startup and operation of cooling and heating, when inverter DC peak data is received by the outdoor internal DC Peak sensing circuitry. Malfunction Caused  DC current peak due to compressor failure. ...
  • Page 142: Disassembly And Assembly Instructions

    19. Disassembly and Assembly Instructions WARNING High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 19.1 CS-Z20VKEW CS-Z25VKEW CS-Z35VKEW CS-Z42VKEW CS-XZ20VKEW CS-XZ25VKEW CS-XZ35VKEW 19.1.1...
  • Page 143 19.1.1.3 To Remove Electronic Controller 3 Hooks (Top, left and right hand side) Remove control board cover by releasing 3 hooks. Figure 2 Remove earth wires. Pull out the 10. Detach all connectors as labelled from the electronic electronic controller. Then pull out the controller halfway.
  • Page 144 19.1.1.4 To Remove Discharge Grille Remove the screw and pull out the HVU unit. HVU unit Remove the screw and pull out the WIFI module. Figure 6 13. Pull out and remove the drain hose from the discharge grille. 14. Then pull the discharge grille downward gently to dismantle it.
  • Page 145 19.1.1.6 To Remove Cross Flow Fan and Indoor Fan Motor Figure 9 18. Remove the bearing by pulling it gently. 17. Remove the screw from the evaporator. Figure 10...
  • Page 146 Evaporator 19. Push the holdfast to the left and lift up the evaporator. 21. Fan motor can be removed after Cross flow fan the removal of the cross flow fan. Reminder: To reinstall the fan motor, adjust the fan motor connector to 90° towards you before fixing control board.
  • Page 147 19.1.1.7 To Assemble the Front Grille Receiver PCB CAUTION Do not directly fix the front grille complete, to avoid hitting the Receiver PCB. Figure 13 Gently assemble the right side of the front grille first then fix the left side. Figure 14...
  • Page 148 19.1.1.8 To Assemble the Intake Grille Hook Intake Grille Align the intake grille hooks into the slot. Hook Place in the hook to the slot. Then slightly bend the intake grille and push in the hooks into the slot. Figure 15...
  • Page 149: Cs-Z50Vkew Cs-Z71Vkew Cs-Xz50Vkew

    WARNING High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 19.2 CS-Z50VKEW CS-Z71VKEW CS-XZ50VKEW 19.2.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 19.2.1.1...
  • Page 150 19.2.1.3 To Remove Electronic Controller 3 Hooks (left and right hand side) Remove control board cover by releasing 4 hooks. Figure 2 Remove earth wires. Pull out the 10. Detach all connectors as labelled from the electronic electronic controller. Then pull out the controller halfway.
  • Page 151 19.2.1.4 To Remove Discharge Grille Remove the screw and pull out the HVU unit. HVU unit Remove the screw and pull out the WIFI module. Figure 6 13. Pull out and remove the drain hose from the discharge grille. 14. Then pull the discharge grille downward gently to dismantle it.
  • Page 152 19.2.1.6 To Remove Cross Flow Fan and Indoor Fan Motor 16. Remove the screw that holding the cross flow fan and fan motor axis. Figure 9 18. Remove the bearing by pulling it gently. 17. Remove the screw from the evaporator. Figure 10...
  • Page 153 Evaporator 19. Push the holdfast to the left and lift up the evaporator. 21. Fan motor can be removed after Cross flow fan the removal of the cross flow fan. Reminder: To reinstall the fan motor, adjust the fan motor connector to 90° towards you before fixing control board.
  • Page 154 19.2.1.7 To Assemble the Front Grille Receiver PCB CAUTION Do not directly fix the front grille complete, to avoid hitting the Receiver PCB. Figure 13 Gently assemble the right side of the front grille first then fix the left side. Figure 14...
  • Page 155 19.2.1.8 To Assemble the Intake Grille Hook Intake Grille Align the intake grille hooks into the slot. Hook Place in the hook to the slot. Then slightly bend the intake grille and push in the hooks into the slot. Figure 15...
  • Page 156 Unclip & pull down Remove the top casing by pressing the side of the network adapter box. Press Press After that, network adapter can be easily replaced. Reminder: Serviceman or owner must setting again Panasonic Comfort Cloud app after replace Wireless LAN Module.
  • Page 157: Outdoor Electronic Controller Removal Procedure

    19.3 Outdoor Electronic Controller Removal Procedure 19.3.1 CU-Z20VKE CU-Z25VKE CU-Z35VKE Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove the Control Board as follows: Screws Top Panel Release 3 Terminal Screws Connectors, L, N and Earth Wire Screw.
  • Page 158 19.3.2 CU-Z42VKE Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove the Control Board as follows: Fig. 4 Fig. 1 Remove the 8 screws of the Front Panel. Fig. 2 Fig.
  • Page 159 19.3.3 CU-Z50VKE CU-Z71VKE Caution! When handling electronic controller, be careful of electrostatic discharge. Remove the 5 screws of the Top Panel. Remove 2 screws for the plate of Terminal Board Cover. Top Panel Screw Plate of Terminal Board Cover Screws Screws Screws Fig.
  • Page 160: Panasonic Comfort Cloud' App Setting Procedure [After Replace Main Printed Circuit Board Or Change The Indoor Unit]

    19.4 ‘Panasonic Comfort Cloud’ App Setting Procedure [After Replace Main Printed Circuit Board or Change the Indoor Unit] 19.4.1 Initial Setup (Method 1) My house My house Menu Home My House Living room Living room Owner 30.0 C 16.May 15:50 16.May 15:50...
  • Page 161 Setting Connection Network Connection Guide Connection Guide Connection Guide Step 1 Step 1 Step 2 Step 2 Step 3 Step 3 Step 1 Step 2 Step 3 Step 1 Step 3 Step 2 Make sure smartphone is connected to same wireless network.
  • Page 162 Connection network using WPS mode (Method 1) Connection Guide Connection Guide Connection Guide Step 1 Step 3 Step 1 Step 2 Step 3 Step 2 Step 1 Step 2 Step 3 If Wireless LAN LED is OFF during the connec on setup, please press “Wireless LAN”...
  • Page 163 Copy password and next CANCEL CONNECT HUAWEI-E5377-F108 MF910_84AA17 Cancel (go back to previous screen) English (UK) Done 3. Copy the password for later use. Select “Panasonic-CS-wirelessAP” from smartphones Wireless LAN setting and enter the copied password. Return to “Panasonic Comfort Cloud” app.
  • Page 164 Select your wireless router Select your wireless router Select your wireless router Network name (SSID) Network name (SSID) router SSID1 Panasonic-factory-wireless-ap-00 Panasonic-factory-wireless-ap-00 Enter the password of the selected router SSID2 Security wireless router. router SSID3 WPA2...
  • Page 165  By registered the new name of air- conditioner, the function of “Panasonic Comfort Cloud” app is ready to be used. My house Device password setting Step 1 Step 2...
  • Page 166 19.4.2 ‘Panasonic Comfort Cloud’ App Setting Procedure [After Replace Wireless LAN Module] 19.4.2.1 Initial Setup (Method 1) My house My house Menu Home My House Living room Living room Owner 30.0 C 16.May 15:50 16.May 15:50 User list Bedroom 1...
  • Page 167 19.4.2.2 Initial Setup (Method 2) My house My house Home Menu My House Living room Living room Owner 30.0 C 16.May 15:50 16.May 15:50 User list Bedroom 1 Change password Cool Cool Replace device Change router settings Device list Group list Application settings User’s manual Terms of use...
  • Page 168 19.4.2.3 Setting Connection Network Connection Guide Connection Guide Connection Guide Step 1 Step 1 Step 2 Step 2 Step 3 Step 3 Step 1 Step 3 Step 1 Step 3 Step 2 Step 2 Make sure smartphone is connected to same wireless network.
  • Page 169 Press and hold “Wireless LAN” bu on for 5 secs un l easy se “ ” 1 SSID: Panasonic-CS-wirelessAP Press “up” or “down” bu on un l Advance Password: Rac8pswi se ng “2” is shown. Point remote control to air-condi oner and press “SET”...
  • Page 170 MF910_84AA17 Cancel (go back to previous screen) English (UK) Done 2. Copy the password for later use. Select “Panasonic-CS-wirelessAP” from smartphones Wireless LAN setting and enter the copied password. Return to “Panasonic Comfort Cloud” app. Connection Guide Connection Guide Connection Guide...
  • Page 171 19.4.2.6 Select the Air Conditioner and Set the Password Connection Guide Connection Guide My house Step 1 Step 3 Step Step Step Step 2 Master room *If Wireless LAN LED is OFF, please press Select the air-condi oner for registra on “Wireless LAN”...
  • Page 172: Technical Data

    20. Technical Data Technical data provided are based on the air conditioner running under free frequency. 20.1 Cool Mode Performance Data Unit setting: Standard piping length, Hi Fan, Cool mode at 16°C Voltage: 230V 20.1.1 CS-Z20VKEW/CU-Z20VKE CS-XZ20VKEW/CU-Z20VKE Indoor (°C) Outdoor DB (°C) 19.0 2304 2100 332 2315 2114 330 2324 2083 332 2258 2095 386 2542 2262 264 2369 2211 350 2050 2022 450 22.0 2541 1690 335 2501 1688 365 2513 1684 355 2614 1727 307 2799 1837 252 2596 1736 345 2315 1627 454 15.7 2058 2037 355 2073 2071 339 2052 2051 371 2065 2036 362 2290 2187 272 2124 2119 353 1879 1860 452...
  • Page 173 20.1.4 CS-Z42VKEW/CU-Z42VKE Indoor (°C) Outdoor DB (°C) 19.0 4805 3187 892 4827 3207 887 4847 3160 892 4709 3179 1038 5301 3432 709 4942 3355 941 4200 3095 1240 22.0 5300 2564 902 5215 2562 981 5241 2556 954 5451 2621 827 5838 2787 679 5415 2634 929 4828 2469 1221 15.7 4292 3155 955 4324 3142 912 4281 3112 998 4307 3089 973 4776 3318 732 4430 3215 950 3918 3079 1216 18.4 4745 2543 892 4779 2539 863 4811 2555 892 4630 2511 1017 5076 2658 714 4832 2623 942 4344 2460 1217 13.3 3812 2951 1092 3777 2913 913 4077 3093 955 3956 2984 997 4493 3314 749 4080 3135 953 3640 2937 1213...
  • Page 174: Heat Mode Performance Data

    20.2 Heat Mode Performance Data Unit setting: Standard piping length, Hi Fan, Heat mode at 30°C Voltage: 230V 20.2.1 CS-Z20VKEW/CU-Z20VKE CS-XZ20VKEW/CU-Z20VKE Indoor (°C) Outdoor WB (°C) 2026 2207 2817 2688 2861 2029 2380 2900 2800 2976 1912 2501 2919 3073 3154 20.2.2 CS-Z25VKEW/CU-Z25VKE CS-XZ25VKEW/CU-Z25VKE...
  • Page 175 20.2.6 CS-Z71VKEW/CU-Z71VKE Indoor (°C) Outdoor WB (°C) 4538 2049 5721 2505 7114 2532 8068 2349 8298 2338 4690 1974 6310 2500 7390 2520 8600 2350 8977 2338 5067 1869 6526 2495 7933 2140 8471 2337 9601 2348 TC - Total Cooling Capacity (W) SHC - Sensible Heat Capacity (W) - Input Power (W)
  • Page 176: Service Data

    21. Service Data Service data provided are based on the air conditioner running under rated frequency during forced cooling / forced heating mode. 21.1 Cool Mode Outdoor Air Temperature Characteristic Condition Indoor room temperature: 27°C Dry Bulb/19°C Wet Bulb Unit setting: Standard piping length, forced cooling at 16°C, Hi fan Compressor frequency: Rated for cooling operation Piping length: 5m Voltage: 230V...
  • Page 177 21.1.2 CS-Z25VKEW CU-Z25VKE CS-XZ25VKEW CU-Z25VKE 20.00 18.00 16.00 14.00 12.00 Outdoor Air Temperature (°C) 3.00 2.80 2.60 2.40 2.20 2.00 1.80 1.60 1.40 1.20 1.00 Outdoor Air Temperature (°C) 1.40 1.30 1.20 1.10 1.00 0.90 0.80 Outdoor Air Temperature (°C)
  • Page 178 21.1.3 CS-Z35VKEW CU-Z35VKE CS-XZ35VKEW CU-Z35VKE 16.00 15.50 15.00 14.50 14.00 13.50 13.00 12.50 12.00 11.50 11.00 Outdoor Air Temperature (°C) 5.00 4.50 4.00 3.50 3.00 2.50 2.00 1.50 Outdoor Air Temperature (°C) 1.10 1.05 1.00 0.95 0.90 0.85 0.80 Outdoor Air Temperature (°C)
  • Page 179 21.1.4 CS-Z42VKEW CU-Z42VKE 13.00 12.50 12.00 11.50 11.00 10.50 10.00 Outdoor Air Temperature (°C) 7.00 6.50 6.00 5.50 5.00 4.50 4.00 3.50 3.00 2.50 Outdoor Air Temperature (°C) 1.12 1.08 1.04 1.00 0.96 0.92 0.88 0.84 0.80 Outdoor Air Temperature (°C)
  • Page 180 21.1.5 CS-Z50VKEW CU-Z50VKE CS-XZ50VKEW CU-Z50VKE 18.0 17.0 16.0 15.0 14.0 13.0 12.0 Outdoor Air Temperature (°C) 8.00 7.00 6.00 5.00 4.00 3.00 2.00 Outdoor Air Temperature (°C) 1.10 1.00 0.90 Outdoor Air Temperature (°C)
  • Page 181 21.1.6 CS-Z71VKEW CU-Z71VKE 16.0 15.0 14.0 13.0 12.0 Outdoor Air Temperature (°C) 12.00 11.00 10.00 9.00 8.00 7.00 6.00 5.00 Outdoor Air Temperature (°C) 1.10 1.00 0.90 Outdoor Air Temperature (°C)
  • Page 182: Heat Mode Outdoor Air Temperature Characteristic

    21.2 Heat Mode Outdoor Air Temperature Characteristic Condition Indoor room temperature: 20°C Dry Bulb/ -°C Wet Bulb Unit setting: Standard piping length, forced heating at 30°C, Hi fan Compressor frequency: Rated for Heating operation Piping length: 5m Voltage: 230V 21.2.1 CS-Z20VKEW CU-Z20VKE CS-XZ20VKEW CU-Z20VKE Outdoor Air Temperature (°C) 3.00...
  • Page 183 21.2.2 CS-Z25VKEW CU-Z25VKE CS-XZ25VKEW CU-Z25VKE Outdoor Air Temperature (°C) 3.70 3.50 3.30 3.10 2.90 2.70 2.50 2.30 2.10 Outdoor Air Temperature (°C) 2.80 2.60 2.40 2.20 2.00 1.80 1.60 1.40 1.20 1.00 0.80 Outdoor Air Temperature (°C)
  • Page 184 21.2.3 CS-Z35VKEW CU-Z35VKE CS-XZ35VKEW CU-Z35VKE Outdoor Air Temperature (°C) 4.50 4.00 3.50 3.00 2.50 Outdoor Air Temperature (°C) 3.00 2.80 2.60 2.40 2.20 2.00 1.80 1.60 1.40 1.20 Outdoor Air Temperature (°C)
  • Page 185 21.2.4 CS-Z42VKEW CU-Z42VKE Outdoor Air Temperature (°C) 7.00 6.50 6.00 5.50 5.00 4.50 4.00 Outdoor Air Temperature (°C) 3.40 3.20 3.00 2.80 2.60 2.40 2.20 2.00 1.80 1.60 Outdoor Air Temperature (°C)
  • Page 186 21.2.5 CS-Z50VKEW CU-Z50VKE CS-XZ50VKEW CU-Z50VKE 55.00 50.00 45.00 40.00 35.00 30.00 25.00 -16 -14 -12 -10 Outdoor Air Temperature (°C) 10.00 9.00 8.00 7.00 6.00 5.00 4.00 3.00 -16 -14 -12 -10 Outdoor Air Temperature (°C) 4.50 4.00 3.50 3.00 2.50 2.00 1.50...
  • Page 187 21.2.6 CS-Z71VKEW CU-Z71VKE 65.00 60.00 55.00 50.00 45.00 40.00 35.00 30.00 25.00 -16 -14 -12 -10 Outdoor Air Temperature (°C) 15.00 14.00 13.00 12.00 11.00 10.00 9.00 8.00 7.00 6.00 -16 -14 -12 -10 Outdoor Air Temperature (°C) 4.50 4.00 3.50 3.00 2.50...
  • Page 188: Piping Length Correction Factor

    21.3 Piping Length Correction Factor The characteristic of the unit has to be corrected in accordance with the piping length. 21.3.1 CS-Z20VKEW CU-Z20VKE CS-Z25VKEW CU-Z25VKE CS-Z35VKEW CU-Z35VKE CS-Z42VKEW CU-Z42VKE CS-XZ20VKEW CU-Z20VKE CS-XZ25VKEW CU-Z25VKE CS-XZ35VKEW CU-Z35VKE Cooling Capacity 1.02 1.0119 1.00 1.0000 0.98 0.9792...
  • Page 189 21.3.2 CS-Z50VKEW CU-Z50VKE CS-Z71VKEW CU-Z71VKE CS-XZ50VKEW CU-Z50VKE Cooling Capacity 1.03 1.0159 1.01 1.0000 0.9889 0.99 0.9800 0.97 0.9746 0.951634 0.95 10 12 14 16 18 20 22 24 26 28 30 32 Pipe Length (m) 1.01 Heating Capacity 1.01 1.0056 1.00 1.0000 1.00...
  • Page 190: Exploded View And Replacement Parts List

    22. Exploded View and Replacement Parts List 22.1 Indoor Unit 22.1.1 CS-Z20VKEW CS-Z25VKEW CS-Z35VKEW CS-Z42VKEW CS-XZ20VKEW CS-XZ25VKEW CS-XZ35VKEW CWH55025J CWH55051J Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 191 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z20VKEW CS-Z25VKEW REMARK CHASSIS COMPLETE ACXD50C00200 ← FAN MOTOR L6CBYYYL0175 ← CROSS-FLOW FAN COMPLETE CWH02C1076 ← BEARING ASSY CWH64K1010 ← SCREW - CROSS-FLOW FAN CWH551146 ← PARTICULAR PIECE CWD933067B ← EVAPORATOR ACXB30C12920 ACXB30C00920 FLARE NUT (LIQUID) CWT251048...
  • Page 192 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z20VKEW CS-Z25VKEW REMARK OPERATING INSTRUCTION ACXF55-22710 ← INSTALLATION INSTRUCTION ACXF60-34310 ← INSTALLATION INSTRUCTION ACXF60-34320 ← INSTALLATION INSTRUCTION ACXF60-34330 ← INSTALLATION INSTRUCTION ACXF60-34340 ← INSTALLATION INSTRUCTION ACXF60-34350 ← INSTALLATION INSTRUCTION ACXF60-34360 ← INSTALLATION INSTRUCTION ACXF60-34370 ←...
  • Page 193 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z35VKEW CS-Z42VKEW REMARK CHASSIS COMPLETE ACXD50C00200 ← FAN MOTOR L6CBYYYL0037 ← CROSS-FLOW FAN COMPLETE CWH02C1076 ← BEARING ASSY CWH64K1010 ← SCREW - CROSS-FLOW FAN CWH551146 ← PARTICULAR PIECE CWD933067B ← EVAPORATOR ACXB30C00920 ACXB30C11020 FLARE NUT (LIQUID) CWT251030...
  • Page 194 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z35VKEW CS-Z42VKEW REMARK OPERATING INSTRUCTION ACXF55-22710 ← INSTALLATION INSTRUCTION ACXF60-34310 ← INSTALLATION INSTRUCTION ACXF60-34320 ← INSTALLATION INSTRUCTION ACXF60-34330 ← INSTALLATION INSTRUCTION ACXF60-34340 ← INSTALLATION INSTRUCTION ACXF60-34350 ← INSTALLATION INSTRUCTION ACXF60-34360 ← INSTALLATION INSTRUCTION ACXF60-34370 ←...
  • Page 195 REF. SAFETY PART NAME & DESCRIPTION QTY. CS-XZ20VKEW CS-XZ25VKEW CS-XZ35VKEW REMARK CHASSIS COMPLETE CWD50C1605 ← ← FAN MOTOR L6CBYYYL0175 ← ← CROSS-FLOW FAN COMPLETE CWH02C1076 ← ← BEARING ASSY CWH64K1010 ← ← SCREW - CROSS-FLOW FAN CWH551146 ← ← PARTICULAR PIECE CWD933067A ←...
  • Page 196 REF. SAFETY PART NAME & DESCRIPTION QTY. CS-XZ20VKEW CS-XZ25VKEW CS-XZ35VKEW REMARK OPERATING INSTRUCTION ACXF55-22710 ← ← INSTALLATION INSTRUCTION ACXF60-34310 ← ← INSTALLATION INSTRUCTION ACXF60-34320 ← ← INSTALLATION INSTRUCTION ACXF60-34330 ← ← INSTALLATION INSTRUCTION ACXF60-34340 ← ← INSTALLATION INSTRUCTION ACXF60-34350 ← ←...
  • Page 197 22.1.2 CS-Z50VKEW CS-Z71VKEW CS-XZ50VKEW CWH55025J CWH55051J Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 198 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z50VKEW CS-Z71VKEW REMARK CHASSIS COMPLETE ACXD50C01590 ← FAN MOTOR L6CBYYYL0193 L6CBYYYL0194 CROSS-FLOW FAN COMPLETE CWH02C1136 ← BEARING ASSY CWH64K1010 ← SCREW - CROSS-FLOW FAN CWH551146 ← PARTICULAR PIECE CWD933067B ← EVAPORATOR ACXB30C02760 ACXB30C01700 FLARE NUT (LIQUID) CWT251030...
  • Page 199 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-Z50VKEW CS-Z71VKEW REMARK OPERATING INSTRUCTION ACXF55-22710 ← INSTALLATION INSTRUCTION ACXF60-34310 ← INSTALLATION INSTRUCTION ACXF60-34320 ← INSTALLATION INSTRUCTION ACXF60-34330 ← INSTALLATION INSTRUCTION ACXF60-34340 ← INSTALLATION INSTRUCTION ACXF60-34350 ← INSTALLATION INSTRUCTION ACXF60-34360 ← INSTALLATION INSTRUCTION ACXF60-34370 ←...
  • Page 200 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-XZ50VKEW REMARK CHASSIS COMPLETE ACXD50C01600 FAN MOTOR L6CBYYYL0193 CROSS-FLOW FAN COMPLETE CWH02C1136 BEARING ASSY CWH64K1010 SCREW - CROSS-FLOW FAN CWH551146 PARTICULAR PIECE CWD933067A EVAPORATOR ACXB30C02760 FLARE NUT (LIQUID) CWT251030 FLARE NUT (GAS) CWT251032 CONTROL BOARD CASING ACXH10-00720...
  • Page 201 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-XZ50VKEW REMARK OPERATING INSTRUCTION ACXF55-22710 INSTALLATION INSTRUCTION ACXF60-34310 INSTALLATION INSTRUCTION ACXF60-34320 INSTALLATION INSTRUCTION ACXF60-34330 INSTALLATION INSTRUCTION ACXF60-34340 INSTALLATION INSTRUCTION ACXF60-34350 INSTALLATION INSTRUCTION ACXF60-34360 INSTALLATION INSTRUCTION ACXF60-34370 INSTALLATION INSTRUCTION ACXF60-34380 INSTALLATION INSTRUCTION ACXF60-34390 INSTALLATION INSTRUCTION ACXF60-34400 INSTALLATION INSTRUCTION...
  • Page 202: Outdoor Unit

    22.2 Outdoor Unit 22.2.1 CU-Z20VKE CU-Z25VKE CU-Z35VKE Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 203 STRAINER CWB11094 ← ← EXPANSION VALVE CWB051078 ← ← WIRE NET ACXD04-00040A ← ← BAG - COMPLETE CWG87C900 ← ← PANASONIC BADGE CWE373439 ← ← INSTALLATION INSTRUCTION ACXF60-33670 ← ← INSTALLATION INSTRUCTION ACXF60-33680 ← ← INSTALLATION INSTRUCTION ACXF60-33690 ← ←...
  • Page 204 REF. SAFETY PART NAME & DESCRIPTION QTY. CU-Z20VKE CU-Z25VKE CU-Z35VKE REMARK INSTALLATION INSTRUCTION ACXF60-33700 ← ← INSTALLATION INSTRUCTION ACXF60-33710 ← ← INSTALLATION INSTRUCTION ACXF60-33720 ← ← INSTALLATION INSTRUCTION ACXF60-33730 ← ← INSTALLATION INSTRUCTION ACXF60-33740 ← ← INSTALLATION INSTRUCTION ACXF60-33750 ← ←...
  • Page 205 22.2.2 CU-Z42VKE Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 206 CABINET FRONT PLATE CO. ACXE06C02890 CABINET TOP PLATE ACXE03-02880 PLATE - C. B. COVER TERMINAL CWH131470 CONTROL BOARD COVER CO. CWH13C1253 STRAINER CWB11094 EXPANSION VALVE CWB051078 WIRE NET CWD041200A BAG - COMPLETE CWG87C900 PANASONIC BADGE CWE373439 INSTALLATION INSTRUCTION ACXF60-33670 INSTALLATION INSTRUCTION ACXF60-33680...
  • Page 207 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-Z42VKE REMARK INSTALLATION INSTRUCTION ACXF60-33690 INSTALLATION INSTRUCTION ACXF60-33700 INSTALLATION INSTRUCTION ACXF60-33710 INSTALLATION INSTRUCTION ACXF60-33720 INSTALLATION INSTRUCTION ACXF60-33730 INSTALLATION INSTRUCTION ACXF60-33740 INSTALLATION INSTRUCTION ACXF60-33750 INSTALLATION INSTRUCTION ACXF60-33760 INSTALLATION INSTRUCTION ACXF60-33770 ACXG86-03760 BASE BOARD - COMPLETE CWG62C1144 SHOCK ABSORBER - TOP RIGHT CWG713415...
  • Page 208 22.2.3 CU-Z50VKE Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 209 CABINET TOP PLATE ACXE03-00200 PLATE - C. B. COVER TERMINAL CWH131470 CONTROL BOARD COVER CO. ACXH13C00170 HANDLE CWE161010 STRAINER CWB11094 EXPANSION VALVE CWB051078 RECEIVER CWB14011 WIRE NET ACXD04-00130A BAG - COMPLETE CWG87C900 PANASONIC BADGE CWE373439 INSTALLATION INSTRUCTION ACXF60-33670 INSTALLATION INSTRUCTION ACXF60-33680...
  • Page 210 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-Z50VKE REMARK INSTALLATION INSTRUCTION ACXF60-33690 INSTALLATION INSTRUCTION ACXF60-33700 INSTALLATION INSTRUCTION ACXF60-33710 INSTALLATION INSTRUCTION ACXF60-33720 INSTALLATION INSTRUCTION ACXF60-33730 INSTALLATION INSTRUCTION ACXF60-33740 INSTALLATION INSTRUCTION ACXF60-33750 INSTALLATION INSTRUCTION ACXF60-33760 INSTALLATION INSTRUCTION ACXF60-33770 CWG861461 BASE BOARD-COMPLETE CWG62C1131 SHOCK ABSORBER - LEFT CWG713217...
  • Page 211 22.2.4 CU-Z71VKE Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 212 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-Z71VKE REMARK CHASSIS COMPLETE ACXD52K00280 FAN MOTOR BRACKET ACXD54-00140 SCREW - FAN MOTOR BRACKET CWH551217 FAN MOTOR L6CAYYYL0076 SCREW - FAN MOTOR MOUNT CWH551106J PROPELLER FAN ASSY ACXH03K00070 NUT - PROPELLER FAN CWH56053J COMPRESSOR 9KD240XBA21...
  • Page 213 SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CU-Z71VKE REMARK PANASONIC BADGE CWE373439 INSTALLATION INSTRUCTION ACXF60-33670 INSTALLATION INSTRUCTION ACXF60-33680 INSTALLATION INSTRUCTION ACXF60-33690 INSTALLATION INSTRUCTION ACXF60-33700 INSTALLATION INSTRUCTION ACXF60-33710 INSTALLATION INSTRUCTION ACXF60-33720 INSTALLATION INSTRUCTION ACXF60-33730 INSTALLATION INSTRUCTION ACXF60-33740 INSTALLATION INSTRUCTION ACXF60-33750...

Table of Contents