Panasonic CS-Z20XKEW Service Manual page 73

Hide thumbs Also See for CS-Z20XKEW:
Table of Contents

Advertisement

2. Cylinder without adjustment valve
nd
2
side gauge pressure is adjusted by the adjuster.
Check the both side valves of the torch and open the cylinder valve to check the remaining refrigerant in the
cylinder.
Caution: Do not attach oil component on the connection port of the adjuster.
Especially, use an oxygen cylinder adjuster which is no oil substance type. Do not dismantle or repair the
adjuster and pressure gauge.
13.7.3
Checking of gas provision
Checking there is no fire around the torch, and then confirm the provision of gas.
1. Slightly open the "propane valve" of the torch, and make sure the gas comes out from the torch crater and then
close the "propane valve".
2. Slightly open the "oxygen valve" of the torch and make sure the gas comes out from the torch crater and then
close the "oxygen valve".
Check there is no gas leakage around the hose connection.
13.7.4
Adjustment of flame
1. Slightly open the "propane valve" of the torch and lit with spark lighter.
This moment, the flame is only by propane and the color is red.
2. Gradually open the "oxygen valve" of the torch to mix oxygen, and adjust the amount of propane and oxygen with
the valve to make the flame suitable for brazing work.
If the white core flame splits into two, the torch crater might be clogged. In this case, remove the crater from the
torch and check.
Main valve
Fuel gauge
0~3 MPa
(0~30 kgf / cm²)
Main valve
Regulator
Propane tank
(Gray)
Oxygen valve
Nozzle
(0~250 kgf / cm²)
Oxygen tank
Orange hose
Oxygen (Black hose)
Propane valve
Propane (Orange hose)
73
Fuel gauge
0~25 MPa
Regulator
(Black)
Black hose