From the diagram in picture 3, it can be checked under what conditions condensate might appear on the
unit external surfaces.
80
75
70
65
60
55
50
45
40
35
30
25
20
15
12
14
Air temperature of the premises where the unit is mounted, °C
To minimize possibility of condensation on unit outer surfaces use following recommendations:
1) Maintain lower relative humidity in the room where air handling unit is mounted;
2) Preheater should be installed to increase the supply air temperature.
UAB KOMFOVENT we reserve the right to make changes without prior notice
D_20-07
1
2
16
18
20
22
24
It is recommended to keep air handling unit constantly running and in
cases when ventilation is not necessary, switch it to the minimum inten-
sity (20%). In that way, good indoor climate will be maintained and con-
densation inside of the unit will decrease, avoiding humidity damage to
electronic components.
3
26
28
30
32
Example No. 1
Temperature of the premises 20°C
Relative humidity of the premises
47%
Condensate will occur when outdoor
temperature is lower than +3°C
10
Example No. 2
Temperature of the premises 22°C
5
Outdoor temperature -5°C
0
Condensate will occur when relative
humidity of the premises will be
-5
higher than 37%
-10
-15
Example No. 3
-20
Relative humidity of the premises
-25
40%
Outdoor temperature 0°C
Condensate will occur when
temperature of the premises will be
higher than 24,5°C
7