4. INSTALLATION

It is recommended to install the air handling unit in a separate room or in the attic on a hard smooth sur-
face insulated with a rubber mat. The minimum free space in front of the control panel should be not less than
700 mm. The free space over the top of the unit should be at least 300 mm (4 a, b Picture). Rubber vibration
absorbers must be used when unit is going to be mounted on the wall or ceiling.
The place for the unit must be selected with allowance for minimum access to the unit for maintenance or
service and must comply with safety requirements. Opening for inspection can not be smaller than dimensions
of the unit and unit itself must be mounted in a way, that if needed (for example in case of complicated repair)
it can be easily dismounted.
Minimum Maintenance Space for Horizontal
Units
4 a Picture
12
Minimum Maintenance Space for Vertical
Units
Unit Installation Scheme
2
3
2
4
5
1
1. Air handling unit
2. Air duct connections
3. Sound attenuator
4. Drain siphon (if provided)
5. Rubber vibration absorber (not included in unit set)
4
UAB KOMFOVENT we reserve the right to make changes without prior notice
4 b Picture
1
2
3
4 Picture
D_20-07