Summary of Contents for Komfovent Domekt R 150 F

  • Page 1 DOMEKT C8 AUTOMATION INSTALLATION MANUAL...
  • Page 3: Table Of Contents

    5. STARTING AND CHECKING THE UNIT ..........................30 5.1. Control panel C6.1 .................................32 5.2. Control panel C6.2 .................................33 5.3. Start-up of the unit using a computer ..........................33 5.4. Quick check ....................................35 UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 4: Introduction

    For more information on how to dispose of such waste for further recycling, contact your city authorities, waste management organisations, approved WEEE systems or your household waste management bodies representatives. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 5: Design Of The Units

    If recuperation is not required, the rotation of the rotary heat exchanger is stopped. Air ter Air ter Air ter Rotary heat Heater or exchanger cooler Air ter Rotary heat Heater or exchanger cooler UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 6 For information on how to set a frost protection mode , see “Domekt User Manual”. Depends on the unit components. Only in CF units. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 7: Classification Of Units By Duct Connection Side

    Fig. 2. Classification of units by inspection side Depends on your order. The exact duct location is shown in the following paragraphs: «Components», «Unit dimensions». UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 8: Switching Inspection Side Of Domekt R 190 V T - R 200 V T

    Section 3.3.5.). In other cases, when the unit is mounted on a wall, you can remove these mounting plates and swap the front and back panels for the unit to look nicer. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 9: Components

    – by-pass extraction (without heat recovery – rotary heat exchanger – electric heater – kitchen hood connection (without heat recovery) – C8 controller main board – outdoor air filter UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 10: Flat Units

    – by-pass extraction (without heat recovery – rotary heat exchanger – electric heater – kitchen hood connection (without heat recovery) – C8 controller main board – outdoor air filter UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 11 – by-pass extraction (without heat recovery – rotary heat exchanger – electric heater – kitchen hood connection (without heat recovery) – C8 controller main board – outdoor air filter UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 12: Unit Transportation And Storage

    Use personal protective equipment. Even small units should be transported on a forklift, a trolley or carried by multiple persons. ≥L ≥L Fig. 4. Examples of transportation by crane, forklift and trolley UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 13 (e.g., wet cardboard packaging), notify the carrier immediately. If the damage is significant, do not accept the unit. Inform the selling company or the representative of UAB KOMFOVENT within three business days about any damage detected during delivery.
  • Page 14: Mechanical Installation

    Depends on your order. Only for units to be mounted on the wall or ceiling. 2, 3 UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 15: Maintenance Area

    Domekt CF 200 F 1100 1105 Domekt R 200 V T Domekt R 250 F Domekt R 300 F 1090 1095 Domekt R 300 V UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 16: Humidity In The Installation Room

    For this purpose, you can also use the “Humidity control function” (see “Domekt User Guide”). UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 17: Unit Dimensions

    615 615 605 515 195 330 115 330 102 290 102 102 Domekt R 300 V Left 615 615 605 515 195 330 115 330 102 290 102 102 UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 18: Flat Units

    In case of ceiling-mounted units, vibration absorbers are integrated in mounting brackets. The following are the types of mounting brackets and mounting dimensions. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 19 A, mm B, mm Domekt R 150 F Domekt R 250 F – Adhesive anti-vibration gasket Domekt R 300 F 1030 – Rubber vibration absorbers UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 20: Dimensions Of Domekt R 190 V T - R 200 V T With A Kitchen Hood

    The following are the dimensions of the unit and mounting dimensions for a kitchen hood. Dimensions with a kitchen hood 1224G-12 140 x 4 = 560 UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 21: Domekt R 190 V T - R 200 V T And Kitchen Hood Installation

    1224G-12 or 392-12 kitchen hoods are mounted at the bottom of the unit prior to the installation in the kitchen cabinet. In order to install a kitchen hood, remove a bottom cover of the unit by unscrewing the screws. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 22 4 – Kitchen hood 1224G-12 5 – Adapter for 392-12 kitchen hood 6 – Kitchen hood 392-12 7 – M4 screws for fixing the kitchen hood UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 23 Mounting plates are screwed to a furniture panel and then the panel can be hung on the front of the unit. Dimensions for mounting furniture panel 32.5 32.5 UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 24: Duct System Installation

    The air ducts are fitted to the unit with self-tapping screws. Different air flow duct positions are marked on the sticker located on the AHU: UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 25 (e.g. Belimo LF-230S) Air closing damper Additional extraction duct Air handling unit Fig. 8. Example of mounting of an additional air extraction duct UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 26: Connection Of External Heating/Cooling Units

    Non-freezing water-glycol mixture must be used as heat medium in a water pre-heater. Ordered separately. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 27: Thermostat Function

    It is recommended to use PPU made by Komfovent. C8 controller software version must be C8_1_1_7_18 or later, and for control panel – C6_1_slim_1_1_4_39 or later. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 28: Connection Of Condensate Drain

    The condensate collection point should be easy to clean and disinfect. Fig. 10b. Condensate drain connection to sewer system UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 29: Electrical Installation

    All external electrical elements must be connected strictly according to the electrical diagram of the unit. • Do not disconnect the connectors by pulling them on wires or cables. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 30: Connecting Electrical Components

    1.3. The terminals of the external elements of the controller board are numbered and are used only to connect optional components and may remain empty if no additional features are required. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 31 Optional fire damper controller must be configured and connected. Refer to Fire damper controller manual for more information. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 32 To activate these modes, a switch, a motion detector or kitchen hood with normally open contacts (NO) can be connected to the terminals. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 33 FG1 (19–21) – terminals used to connect air damper actuators. 230 V power supply actuators with or without a spring return can be connected to them. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 34: Control Panel Installation

    +24V 4 x 0,22 mm 2 4 x 0,22 mm 2 < 150 m < 150 m Fig. 15. Control panel cable wiring diagram UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 35 Fig. 16. Cable connection to the control panel Do not use sharp tools (e.g. screwdriver) to press on the control panel’s contacts. Pencil or ballpoint pen is best for this. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 36: Connecting The Unit To An Internal Computer Network Or The Internet

    Internet. The unit is controlled by a computer using a web browser, or a smartphone with a Komfovent Control app. The air han- dling unit is connected to the computer network with a CAT5 type cable (RJ45 connector; see Fig. 11). The total cable length between the unit and the network router must not exceed 100 m.
  • Page 37: Starting And Checking The Unit

    Subsequent settings vary depending on whether the unit is controlled by a computer or a smartphone. • The easiest way to manage your unit over the internet is to use a smartphone with the Komfovent Con- trol app. Launch the app on your phone (the phone must have Internet access). When you connect for the first time, the app will ask you to scan the QR code at the front of the controller board (see Fig.
  • Page 38 Vėdinimo intensyvumas 100% Set temperature 20°C 20°C 20°C 20°C Pageidaujama Pageidaujama Pageidaujama Pageidaujama temperatūra temperatūra temperatūra temperatūra 20°C 20°C 20°C 20°C Depends on your order. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 39: Control Panel C6.1

    Afterwards a signal to the fans will be given and the unit will start operating in the last used ventilation mode. To change the ventilation mode: Operation modes 16:30 16:30 AWAY NORMAL INTENSIVE BOOST NORMAL INTENSIVE KITCHEN FIREPLACE AUTO AUTO OVERRIDE HOLIDAYS UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 40: Control Panel C6.2

    On/O will be lit next to the button. On/O button. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 41: Start-Up Of The Unit Using A Computer

    Should you forget a changed password, it can be reset to the initial “user”. To do this, you must restore the factory settings for the air handling unit using control panel. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 42 AWAY NORMAL INTENSIVE BOOST AWAY NORMAL INTENSIVE BOOST KITCHEN FIREPLACE OVERRIDE HOLIDAYS KITCHEN FIREPLACE OVERRIDE HOLIDAYS MODIFY > MODIFY > MODIFY > MODIFY > UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 43: Quick Check

    The condensate easily flows from the unit and the drainage piping is watertight Other notes: Unit installed by Company Phone Date Signature UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_ installation manual_24-01...
  • Page 44 SERVICE AND SUPPORT PARTNERS LITHUANIA J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at UAB KOMFOVENT Phone: +370 5 200 8000 Ventilair group www.ventilairgroup.com service@komfovent.com ACB Airconditioning www.acbairco.be www.komfovent.com REKUVENT s.r.o. www.rekuvent.cz FINLAND Komfovent Oy WESCO AG www.wesco.ch Muuntotie 1 C1 FI-01 510 Vantaa, Finland SUDCLIMATAIR SA www.sudclimatair.ch...