Content 1. SAFETY REQUIREMENTS ..........................4 2. TRANSPORTATION ............................4 3. BRIEF DESCRIPTION OF THE UNIT ......................5 4. INSTALLATION ............................. 12 4.1. Condensate Drain Connections ....................... 16 4.1.1. Water trap installation for a unit section mounted on the suction side ........... 17 4.1.2.
1. SAFETY REQUIREMENTS • To avoid accidents and/or unit damage, only a trained technician must carry out the connection. • The appropriate Personal Protective Equipment (PPE) attire is worn relative to the operation being carried out. • Electrical equipment is rated, connected and earthed in accordance with CE regulations.
When unit is loaded or unloaded by crane, cargo rope is fastened in its designated places. Forklift truck or hand pallet truck can transport air handling unit as it is shown (2 a, b, c Pictures). Vertical and horizontal unit transportation by forklift truck, hand pallet truck or crane 2 a Picture 2 c Picture 2 b Picture...
Page 6
• To maintain a good indoor climate, comply with regulations and, to avoid condensation damage, the unit must never be stopped apart from during service/maintenance or in connection with an accident. • If the unit is placed in spaces with high humidity, condensation might occur on the surface of the unit when outdoor temperatures are very low.
Page 7
Suppose that supply air temperature is -25°C. Ambient air temperature, where air handling unit is installed, is +20°C. In this case, condensate may appear on the outer surfaces of the air handling unit when relative hu- midity in room is in range from 23% up to 100% (from point where curves of outside and inside air temperatures crosses till the maximum value).
Page 8
Air Handling Units Schemes DOMEKT R 200 V DOMEKT R 250 F C6 DOMEKT R 300 V DOMEKT R 400 V / DOMEKT R 450 V DOMEKT R 400 H DOMEKT R 400 F UAB AMALVA we reserve the right to make changes without prior notice...
Page 9
DOMEKT R 500 V** / DOMEKT R 700 V** DOMEKT R 500 H C6 DOMEKT R 600 H DOMEKT R 700 H DOMEKT R 700 F UAB AMALVA we reserve the right to make changes without prior notice D2-18-01...
Page 10
DOMEKT PP 300 V / 450 V DOMEKT CF 250 V DOMEKT CF 250 F DOMEKT CF 400 V UAB AMALVA we reserve the right to make changes without prior notice D2-18-01...
Page 11
DOMEKT CF 500 F DOMEKT CF 700 V DOMEKT CF 700 H DOMEKT S 650 F / 800 F 1. Rotary or plate heat exchanger 2. Electric or water air heater 3. Supply air filter 4. Exhaust air filter 5. Supply fan 6.
4. INSTALLATION It is recommended to install the air handling unit in a separate room or in the attic on a hard smooth surface insulated with a rubber mat. The minimum free space in front of the control panel should be not less than 700 mm.
Page 13
Inspection ceiling trapdoor 5 Picture UAB AMALVA we reserve the right to make changes without prior notice D2-18-01...
Page 14
DOMEKT R 400 V Unit brackets’ positions Ø125 Ø160 6 Picture DOMEKT R 450 V Unit brackets’ positions Ø125 Ø160 7 Picture UAB AMALVA we reserve the right to make changes without prior notice D2-18-01...
Page 15
Įrenginio DOMEKT CF 250 V Unit brackets’ positions view 8 Picture DOMEKT CF 250 F Unit brackets’ positions 9 Picture DOMEKT CF 400 V Unit brackets’ positions view 1 3 × 170 = 510 10 Picture UAB AMALVA we reserve the right to make changes without prior notice D2-18-01...
4.1.1. Water trap installation for a unit section mounted on the suction side Since the fans in most air handling units are last in the chain of functions and generate sub-atmospheric pres- sure inside the unit,it is very important to correctly install the water trap. Because of that reason condensate can be hardly eliminated from the air handling unit and the technical premise may get covered with condensate.
Page 18
DOMEKT R 200V unit with kitchen hood Air handling unit DOMEKT R 200 V can be mounted with one of the two types of kitchen hoods (13, 14 Picture). Air handling unit DOMEKT R 200V 2. Kitchen hood adapter 392-12 3.
Page 19
Instalation scheme of DOMEKT R 200V unit with kitchen hood Before installing kitchen hood, bottom cover plate must be removed by remooving fixing screws (14a pic.) 14a Picture 5 (×10) 5 (×10) 4 (×4) Kitchen hood adapter 392-12 2. Standard kitchen hood 3.
Page 20
Dimensions for the DOMEKT R 200 V installation space 140 × 4 = 560 15 Picture. Dimensions with standard kitchen hood 140×4 = 560 16 Picture. Dimensions with kitchem hood 392-12 UAB AMALVA we reserve the right to make changes without prior notice...
Page 21
DOMEKT R 200 V Unit hanging scheme without kitchen hood 17 Picture View C: Brackets for hanging the furniture or decorative panel. Marking Description pcs. DOMEKT R 200 V -00.014 Mounting bracket Wall plug KWP (nylon) 8×50 + screw DOMEKT R 200 V -00.011 Unit bracket Self tapping screw 4,2×13...
4.2. Heating coil connection Pipe work should be connected in accordance with good engineering practice. All pipe work must be ad- equatelysupported to ensure that no additional load is stressing the unit. Mounting the pipes on the heating coil, tight the pipes with spanners. As shown in 20 Picture. Fitting Pipes Connection Sensors Installation 20 b Picture...
4.4. Final Inspection After installation of the unit, a thorough inspection should be carried out. This should include inspecting the inside of the unit and removing debris and tools, which may have been left behind by on site contractors. Re- place any panels, which may have been removed and close all access doors, ensuring that the door sealing gaskets have not been damaged.
Pressure sensor 21 Picture 7. Pressure sensor setting, which indicates impurity of filters. Pressure sensor is set according to EN 13779:2007 standard: 100 Pa for small systems, 150 Pa for big systems. Remove cover from the pressure sensor and turn the cursor due to proper position. The indicator will turn on when filters will be clogged. •...
Page 27
Parameters Dimensions Fans input Maximum Electric Ducts Supply power at Weight Operating heater connection Length, Height, voltage max. flow Width, W current capacity rate Type DOMEKT R (C4) 200 V 660/625 1~230 2*66 5×125 4×160, 250 F 830/790 1~230 2*98 1×125 4×160, 400 V...
Page 28
Parameters Fans input Dimensions Maximum Electric Ducts Supply power at Weight Operating heater connection voltage max. flow Length, Height, current capacity Width, W rate Type DOMEKT CF (C5) 700 V 1020 1145/1040 1~ 230 2*177 4×200 700 H 1540/1500 1~ 230 2*180 4×250 DOMEKT CF (C6)
Page 29
Dimensions of Ductwork Connection Parameter Type DOMEKT R (C4) 200 V 250 F 400 V 400 F 450 V 600 H DOMEKT R (C6) 250 F 300 V 400 V 400 F 400 H 450 V 500 H / 700 H 500 V / 700 V 600 H 700 F...
Page 30
Filters Overall dimensions Supply Exhaust Unit Type Width Height Length Length DOMEKT R 200 V KF5/KF7* 250 F KF5/KF7* 300 V KF5/KF7* 400 V KF5/KF7* 400 H KF5/KF7* 400 F KF5/KF7* 450 V KF5/KF7* 500 V/H KF5/KF7* 600 H KF5/KF7* 700 V/H KF5/KF7* 700 F...
Page 32
Nordisk Ventilator AB www.nordiskventilator.se Agregat d.o.o www.agregat.si TZB produkt, s.r.o. www.tzbprodukt.sk ООО «АМАЛВА-Р» Komfovent AB Komfovent GmbH Россия, Москва Ögärdesvägen 12B Konrad-Zuse-Str. 2a, 42551 Velbert, ул. Выборгская д. 16, 433 30 Partille, Sverige Deutschland стр. 1, 2 этаж, 206 офис...