TECHNICAL PASSPORT
AND INSTALLATION GUIDE
OF KLASIK AIR HANDLING UNITS

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KLASIK Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Komfovent KLASIK Series

  • Page 1 TECHNICAL PASSPORT AND INSTALLATION GUIDE OF KLASIK AIR HANDLING UNITS...
  • Page 3: Table Of Contents

    For more information about where you can drop off your waste equipment for recycling, please contact your local city office, waste authority, approved WEEE scheme or your household waste disposal service. UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 4: Equipment Series

    KLASIK units meets the tightness class A and its total heat transfer is T3 class. Easy to use door locks and handles ensure safe unit maintenance. UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 5 Air dampers Air shutters in ventilation units are made of aluminium blades provided with a rubber seal, to ensure tight- ness. UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 6: Filter Section

    1 – Filters section with compact filter, 2 – Filters section with pocket filter, 3 – Filters section with carbon filter, 4 – Filters section with HEPA filter. Unit weight is indicated in the technical offer, attached to the passport of the unit. UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 7 610×610×292 6 + 2 6 + 2 308×613×457 305×610×292 613×613×457 610×610×292 8 + 4 3 + 3 + 3 613×458×457 610×305×292 613×308×457 613×613×457 8 + 4 613×308×457 UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 8: Recirculation Section

    2310 1490 2000 1200 2000 700 1050 1185 2310 1570 2000 1300 2000 700 1050 1185 2590 1650 2200 1400 2200 800 1190 1295 2890 1830 2500 1600 2500 800 1190 1445 UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 9: Fan Section

    70%. stream of air. Fans with forward curved Fans with backward curved blades blades UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 10 At particular frequency, smaller than rated, vibration is possible. At frequencies, when vibration starts, the air handling unit can’t be exploitable. The unit must be grounded according to the grounding installation rules consistent with EN61557 BS 7671! UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 11: Rotary Heat Exchanger Section

    When the temperature after the heat exchanger is ≤ 0 °C, it is necessary to provide protection from freezing, for example, electric heater upstream the heat exchanger. UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 12: Plate Heat Exchanger Section

    When the temperature after the heat exchanger is ≤ 0°C, it is necessary to provide protection from freezing, for example, electric heater upstream the heat exchanger. When the air flow exceeds 2.5 m/s, the drop tray is recommended! UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 13: Counter-Fow Plate Heat Exchanger Section

    When the temperature after the heat exchanger is ≤ 0°C, it is necessary to provide protection from freezing, for example, electric heater upstream the heat exchanger. When the air flow exceeds 2.5 m/s, the drop tray is recommended! UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 14: Liquid Coupled Heat Exchanger Section

    For ventilation units operated outdoors when the ambient air temperature t < 0°C, it is necessary to use water-ethylene glycol mixture to prevent freezing of water and damage to the heat exchanger. UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 15: Cooler Section

    When the air flow exceeds 2.5 m/s, the drop tray is recommended! UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 16: Electric Heater Section

    1745 1905 1010 The inspection access length can be 300, 400, 500, 2140 1130 700, 800 mm. 2310 1265 2310 1490 2310 1570 2590 1650 2890 1830 UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 17: Sound Attenuator Section

    After washing, water is comp- letely drained from the drain bath. For air humidification with water, the must have a water preparation system! UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 18: Installation Guide

    If the ventilation unit has no factory automation control, the company installing the unit is responsible for its operation and reliability of guards. UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 19: Verso Air Handling Units Marking

    Air damper Air filter Air cooler Rotary heat exchanger Compressor Plate heat exchanger Noise attenuator Water air heater Inspection Electrical air heater UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 20: Unit Transportation

    KOMFOVENT UAB shall not be held liable for any damages cau- sed by the carrier during transportation or unloading. UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 21 Ventilation units are heavy, therefore from slipping out of place. care must be taken during lifting, carrying or moving operations. Use personal protection equipment. A - A ≥ L UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 22: Selection Of Mounting Location

    Deviations shall not exceed frame or height adjustable feet, it should be fixed to the 0.3mm for 1m in the longitudinal direction and 0.5mm for 1m in the transverse direction. UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 23 Lift corners with a long crowbar to 2. Place lifting straps under the section with a long bar remove inserted battens. or a hook. UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 24: Electrical Installation

    If the device is not equipped with factory installed control automation, the company which installed the automation is responsible for proper operation of the device as well as safety guards. UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 25: Connection Of Sections

    (supplied with the unit). Screws must be tightened so External tightening elements Išoriniai suveržimo elementai Adhesive gasket Klijuojama tarpinė Fig. A Adhesive Klijuojama gasket tarpinė Internal tightening Vidiniai suveržimo kampai corners Fig. B UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 26: Roof Installation

    Klasik 1-7 size ~ 350 mm ~ 350 mm ~ 350 mm ~ 350 mm UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 27 ~ 350 mm ~ 350 mm ~ 350 mm Pictures are for information only. Exact amounts and dimensions of roof parts are provided in the installation drawings. UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 28: Connection Of Water Heat Exchangers

    1. Electric drive fixed to the air handling unit installed in a building 2. Electric drive fixed, under the cap, to the air handling unit installed outdoors UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 29: Connection To The Air Duct

    1. Bolt 2. Connector 3. Flange 4. Air duct 5. Single-sided adhesive gasket 1. Bolt 2. C profile for flange connection 3. Single-sided adhesive gasket UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 30: Water Trap Installation

    Height H must be equivalent in mm to the negative pressure inside the device. Condensate Condensate 140-310 UAB KOMFOVENT we reserve the right to make changes without prior notice KBP2-18-10...
  • Page 32 J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at Tel. +370 5 277 9701 Mob. +370 685 44 658 Pacific HVAC www.pacifichvac.com el. p. info@komfovent.com Ventilair group www.ventilairgroup.com KAUNAS Taikos pr. 149, LT-52119 ACB Airconditioning www.acbairco.be Tel.: +370 37 473 153, +370 37 373 587 Mob.