Komfovent DOMEKT Series Installation Manual

Komfovent DOMEKT Series Installation Manual

Hide thumbs Also See for DOMEKT Series:

Advertisement

DOMEKT
Installation Manual
EN
C6M automation

Advertisement

Table of Contents
loading

Summary of Contents for Komfovent DOMEKT Series

  • Page 1 DOMEKT Installation Manual C6M automation...
  • Page 3: Table Of Contents

    5.1. Control panel C6.1 ......................................28 5.2. Control panel C6.2 ......................................29 5.3. Start-up of the unit using a computer ............................... 29 5.4. Quick check ......................................... 31 UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 4: Introduction

    This way the outdoor air passes around the recuperator and enters the premises directly. Air bypass Air lter Air ter Counter- ow heat Heater or exchanger cooler UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03 Air ter...
  • Page 5 Air duct to the premises Air duct to the premises Fig. 2. Classification of units by inspection side Depends on the unit components. Depends on your order. UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 6: Components

    – extract air fan – extract air filter – C6M controller main board E – additional extraction – electric heater – condensate drainage (air bypass without recuperation) UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 7: Vertical Units

    LEFT INSPECTION SIDE Domekt R 500 V - R 700 V Domekt CF 700 V RIGHT INSPECTION SIDE LEFT INSPECTION SIDE RIGHT INSPECTION SIDE LEFT INSPECTION SIDE UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 8: Flat Units

    – extract air fan – extract air filter – C6M controller main board E – additional extraction – electric heater – condensate drainage (air bypass without recuperation) UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 9 – extract air fan – extract air filter – C6M controller main board E – additional extraction – electric heater – condensate drainage (air bypass without recuperation) UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 10: Unit Transportation

    After delivery of the air handling unit, carefully inspect its packaging for damage. If mechanical or other damage is visible (e.g., wet cardboard packaging), notify the carrier immediately. If the damage is significant, do not accept the unit. Inform the selling company or the representative of UAB KOMFOVENT within three business days about any damage detected during delivery.
  • Page 11: Mechanical Installation

    Depends on your order. Only for units to be mounted on the wall or ceiling. 2, 3 Except for R 300 V and CF 150 F units. UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 12: Maintenance Area

    Some DOMEKT units can be suspended on the wall, and flat units can be attached to the ceiling. It is also necessary to use vibration absorbers for wall mounting to prevent the vibrations of the unit from being transmitted to the building structures. UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 13: Humidity In The Installation Room

    We recommend that you always keep the unit turned on and use it at minimum of 20% intensity even if no ventilation is required. This will ensure good indoor climate conditions and reduce condensation inside the unit, which might damage electronic components. UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 14 Fig. 7. Diagram of condensate formation on the exterior surfaces of the air handling unit Graph in Fig. 7 can be used to determine the conditions under which condensation may occur on the unit. UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 15: Unit Dimensions

    – Right – – Domekt CF 400 V Left – – Right 1146 1130 1020 – – Domekt CF 700 V Left 1146 1130 1020 – – UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 16: Horizontal Units

    – – Domekt CF 500 F Left 1430 1400 1045 1045 – – Right 1394 1365 – – Domekt CF 700 F Left 1394 1365 – – UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 17: Location And Dimensions Of Fixture Elements

    Domekt CF 150 F Domekt CF 250 F 1190 Domekt CF 150 F Domekt CF 500 F 1190 1096 Domekt CF 700 F 1190 Domekt CF 150 F UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 18: Duct System Installation

    The air ducts are fitted to the unit with self-tapping screws. Different airflow ducts are marked with stickers: outdoor intake air air supplied to the premises air extracted from the premises outdoor exhaust air Fig. 8. Air duct marking UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 19 100 % The diameter of the ducts varies by unit model: Unit ~230V Duct A Duct B Duct C Duct D Duct E – – – – UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 20: Connection Of External Heating/Cooling Units

    The condensate collection point should be easy to clean and disinfect. Ordered separately. UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 21: Electrical Installation

    Terminals for connection of external elements Controller board type and QR code Power supply for the Komfovent Control app connector Fig. 13. C6M controller main board UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 22 Komfovent Cloud app at a distance of at least two duct diameters from the nearest heat exchanger coil. connector Fig. 15b Duct mounted supply air temperature sensor UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 23 • S1 (41–42) – a water circulation pump used in conjunction with external water coils and is activated when required for heating/cooling. UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 24: Control Panel Installation

    The wire to C6M controller board is connected to a dedicated slot (RJ9 connector; see Fig. 13) or to the terminals for external connections. UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 25: Connecting The Unit To An Internal Computer Network Or The Internet

    Internet. The unit is controlled by a computer using a web browser, or a smartphone with a Komfovent Home or Komfovent Control app. The air handling unit is connected to the computer network with a CAT5 type cable (RJ45 connector;...
  • Page 26 • The easiest way to manage your unit over the internet is to use a smartphone with the Komfovent Control app. Launch the app on your phone (the phone must have Internet access). When you connect for the first time, the app will ask you to scan the QR code at the front of the controller board (see Fig.
  • Page 27: Starting And Checking The Unit

    Vėdinimo intensyvumas 100% Ventilation Pageidaujama Pageidaujama Pageidaujama Pageidaujama 100% intensity temperatūra temperatūra temperatūra temperatūra 20°C 20°C 20°C 20°C 20°C 20°C 20°C 20°C temperature Depends on your order. UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 28: Control Panel C6.1

    Scheduling INTENSIVE INTENSIVE TURN OFF TURN TURN ON AUTO Settings Settings Settings Settings Settings Settings TURN OFF TURN TURN ON TURN OFF TURN TURN ON AUTO AUTO UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 29: Control Panel C6.2

    Log in to the C6 controller user interface: enter the user name user, password user and press the “Login” button. user user Login Login If the password has been changed, use it. UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 30 OPERATION MODES АUТО AWAY NORMAL INTENSIVE BOOST АUТО AWAY NORMAL INTENSIVE BOOST KITCHEN FIREPLACE OVERRIDE HOLIDAYS MODIFY > MODIFY > KITCHEN FIREPLACE OVERRIDE HOLIDAYS MODIFY > MODIFY > UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 31: Quick Check

    External devices connected operates correctly The condensate easily flows from the unit and the drainage piping is watertight Other notes: Unit installed by Company Phone Date Signature UAB KOMFOVENT we reserve the right to make changes without prior notice C6M2-19-03...
  • Page 32 LITHUANIA PARTNERS UAB KOMFOVENT J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at TECHNINĖS PRIEŽIŪROS SKYRIUS / Ventilair group www.ventilairgroup.com SERVICE AND SUPPORT ACB Airconditioning www.acbairco.be Phone: +370 5 200 8000 Mobile: +370 652 03 180 REKUVENT s.r.o. www.rekuvent.cz Email: service@komfovent.com WESCO AG www.wesco.ch...