Page 2
5.1. Control panel C6.1 ......................................32 5.2. Control panel C6.2 ......................................33 5.3. Start-up of the unit using a computer ............................... 33 5.4. Quick check ......................................... 35 UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 3
For more information on how to dispose of such waste for further recycling, contact your city authorities, waste management organisations, approved WEEE systems or your household waste management bodies representatives. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 4
Depends on the unit components. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 5
Fig. 2. Classification of units by inspection side Depends on your order. The exact duct location is shown in the following paragraphs: «Components», «Unit dimensions». UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 6
– electric heater – rotary heat exchanger – electric pre-heater – C6M controller main board – exhaust air – outdoor air filter – by-pass extraction without heat recovery UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 7
– electric heater – rotary heat exchanger – electric pre-heater – C6M controller main board – exhaust air – outdoor air filter – by-pass extraction without heat recovery UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 8
– air bypass damper – electric heater – rotary heat exchanger – electric pre-heater – C6M controller main board – outdoor air filter RIGHT INSPECTION SIDE LEFT INSPECTION SIDE UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 9
– electric heater – rotary heat exchanger – electric pre-heater – C6M controller main board – exhaust air – outdoor air filter – by-pass extraction without heat recovery UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 10
– electric heater – rotary heat exchanger – electric pre-heater – C6M controller main board – exhaust air – outdoor air filter – by-pass extraction without heat recovery UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 11
After delivery of the air handling unit, carefully inspect its packaging for damage. If mechanical or other damage is visible (e.g., wet cardboard packaging), notify the carrier immediately. If the damage is significant, do not accept the unit. Inform the selling company or the representative of UAB KOMFOVENT within three business days about any damage detected during delivery.
Page 12
Depends on your order. Only for units to be mounted on the wall or ceiling. 2, 3 Except for CF 150 F, CF 200 V, CF 300 V units. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 13
Some DOMEKT units can be suspended on the wall, and flat units can be attached to the ceiling. It is also necessary to use vibration absorbers for wall mounting to prevent the vibrations of the unit from being transmitted to the building structures. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 14
We recommend that you always keep the unit turned on and use it at minimum of 20% intensity even if no ventilation is required. This will ensure good indoor climate conditions and reduce condensation inside the unit, which might damage electronic components. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 15
(near hinges, locks or duct connections) some condensate may appear even with lower humidity in the instal- lation room, however it is irrelevant for AHU operation. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 16
Right – – Domekt CF 400 V Left – – Right 1144 1130 1020 – – Domekt CF 700 V Left 1144 1130 1020 – – UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 17
– Domekt CF 500 F Left 1430 1400 1045 1045 – – Right 1406 1365 – – Domekt CF 700 F Left 1406 1365 – – UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 18
Unit A, mm B, mm Domekt R 400 F 1100 Domekt R 700 F 1024 Domekt CF 500 F 1100 1096 Domekt CF 700 F 1100 UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 19
3 m Air exhaust vent min. 1 m Air intake vent min. 3 m min. 1,8 m min. 1,8 m UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 20
Spring return actuator with end position contacts (e.g. Belimo LF-230S) Air closing damper Additional extraction duct Air handling unit Fig. 9. Example of mounting of an additional air extraction duct UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 21
Such hood must be connected to a duct separated from the general ventilation system. The diameter of the ducts varies by unit model: Unit – – – UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 22
Ordered separately. It is recommended to use PPU made by Komfovent. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 23
The condensate collection point should be easy to clean and disinfect. Fig. 11b. Condensate drain connection to sewer system UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 24
Terminals for connection of external elements Controller board type and QR code Power supply for the Komfovent Control app connector Fig. 12. C6M controller main board UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 25
Connections for internal components Terminals for connection of external elements Controller board type and QR code Power supply for the Komfovent Cloud app connector UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 26
Fig. 15. Example of “Override” ventilation mode activation when using additional air extraction with a motorised damper (see Fig. 9). Only in CF 150 F, CF 200 V, CF 300 V units. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 27
Wrong screws may damage the panel’s electronics board. Optional fire damper controller must be configured and connected. Refer to Fire damper controller manual for more information. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 28
Fig. 17. Cable connection to the control panel Do not use sharp tools (e.g. screwdriver) to press on the control panel’s contacts. Pencil or ballpoint pen is best for this. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 29
Internet. The unit is controlled by a computer using a web browser, or a smartphone with a Komfovent Control app. The air handling unit is connected to the computer network with a CAT5 type cable (RJ45 connector;...
Page 30
• The easiest way to manage your unit over the internet is to use a smartphone with the Komfovent Control app. Launch the app on your phone (the phone must have Internet access). When you connect for the first time, the app will ask you to scan the QR code at the front of the controller board (see Fig.
Page 31
Vėdinimo intensyvumas 100% Ventilation Pageidaujama Pageidaujama Pageidaujama Pageidaujama 100% intensity temperatūra temperatūra temperatūra temperatūra 20°C 20°C 20°C 20°C 20°C 20°C 20°C 20°C temperature Depends on your order. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 32
To turn off the air handling unit and return to the home screen: 16:30 Menu Menu Menu Overview Overview Overview TURN OFF? Scheduling Planavimas Scheduling INTENSIVE Settings Settings Settings TURN OFF TURN TURN ON AUTO UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 33
Should you forget a changed password, it can be reset to the initial “user”. To do this, you must restore the factory settings for the air handling unit using control panel. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 34
АUТО АUТО AWAY NORMAL INTENSIVE BOOST AWAY NORMAL INTENSIVE BOOST KITCHEN FIREPLACE OVERRIDE HOLIDAYS MODIFY > MODIFY > KITCHEN FIREPLACE OVERRIDE HOLIDAYS MODIFY > MODIFY > UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 35
External devices connected operates correctly The condensate easily flows from the unit and the drainage piping is watertight Other notes: Unit installed by Company Phone Date Signature UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT_C6M_installation manual_23-02...
Page 36
SERVICE AND SUPPORT PARTNERS LITHUANIA J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at UAB KOMFOVENT Phone: +370 5 200 8000 Ventilair group www.ventilairgroup.com ACB Airconditioning www.acbairco.be service@komfovent.com www.komfovent.com REKUVENT s.r.o. www.rekuvent.cz SWEDEN Komfovent AB WESCO AG www.wesco.ch Ögärdesvägen 12A SUDCLIMATAIR SA www.sudclimatair.ch...