INSTALLATION MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Komfovent DOMEKT R 200 VSO C8

  • Page 1 DOMEKT R 200 VSO C8 INSTALLATION MANUAL...
  • Page 3: Table Of Contents

    5.2. Control panel C6.2 ......................................27 5.3. Start-up of the unit using a computer ............................... 27 5.4. Quick check ......................................... 29 6. FILTER INSPECTION AND REPLACEMENT ..............................30 UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 4: Introduction

    For more information on how to dispose of such waste for further recycling, contact your city authorities, waste management organisations, approved WEEE systems or your household waste management bodies representatives. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 5: Design Of The Unit

    AHU may not reach the supply temperature setpoint if the actual room temperature differs a lot from the desired value, since in that case heat exchanger capacity will be low. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 6 If looking from the back side of the unit, this extract duct may be on the left or right side. All other unit components are the same. Domekt R 200 VSO R1 Domekt R 200 VSO R2 Fig. 2. Additional extract connection position according to AHU configuration UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 7 ETH** – By-pass extraction without heat recovery (Only R1 configuration) – Extract air filter – C8 contoller main board – Rotary heat exchanger – Air closing dampers – Extracted air regulation damper – Silencers UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 8: Unit Transportation And Storage

    After delivery of the air handling unit, carefully inspect its packaging for damage. If mechanical or other damage is visible (e.g., wet cardboard packaging), notify the carrier immediately. If the damage is significant, do not accept the unit. Inform the selling company or the representative of UAB KOMFOVENT within three business days about any damage detected during delivery.
  • Page 9: Mechanical Installation

    ≥300 mm ≥300 mm ≥750 mm ≥100 mm Fig. 5. Minimum space for maintenance UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 10: Unit Dimensions

    Bottom view / R2 con guration 1370 1443 Front view Side view Back view / R1 con guration Back view / R2 con guration 1712 UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 11 1072 2123 Fig. 6. Location of the mounting points UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 12: Unit Mounting At The Installation Place

    3. Unscrew 6 bolts and remove the duct connection cover 4. Put the main unit cabinet onto the bracket and fix it to the wall with 2 screws on top UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 13 7. Put the silencer box onto the holders and push it firmly to con- 8. Fix the silencer box to the ceiling with 3 suitable screws nect the ducts. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 14 It is forbidden to drill or screw into the casing of the unit, in places not provided for this purpose, as there is a danger of damaging cables or tubes inside the housing. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 15: Duct System Installation

    Domekt R 200 VSO C8 – Outdoor air – Supply air – Extract air – Exhaust air – By-pass extraction without heat recovery Fig. 7. Air duct marking UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 16: Connection Of External Heating/Cooling Units

    The sensor must be thermally insulated so that the room temperature does not distort water tempera- ture measurements. Fig. 8. Connecting the water heater/cooler hoses and installing the water temperature sensor Ordered separately. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 17: Electrical Installation

    • Check the insulation of the power cable or other cables for damage. • Locate the electrical diagram of the unit. It is recommended to use PPU made by Komfovent. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 18: Electrical Input Requirements

    • All external electrical elements must be connected strictly according to the electrical diagram of the unit. • Do not disconnect the connectors by pulling them on wires or cables. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 19: Connecting Electrical Components

    General Fire alarm Priority General Heating Cooling Air damper actuators ~230V Max 15W Fig. 11. Terminals for connecting external elements of C8 board UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 20 (NO) can be connected to the terminals. Optional fire damper controller must be configured and connected. Refer to Fire damper controller manual for more information. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 21: Control Panel Installation

    Do not use any other size or type of screws but those that are packed to gether for control panel mount- ing. Wrong screws may damage the panel’s electronics board. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 22 Fig. 15. Cable connection to the control panel Do not use sharp tools (e.g. screwdriver) to press on the control panel’s contacts. Pencil or ballpoint pen is best for this. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 23: Connecting The Unit To An Internal Computer Network Or The Internet

    Internet. The unit is controlled by a computer using a web browser, or a smartphone with a Komfovent Control app. The air handling unit is connected to the computer network with a CAT5 type cable (RJ45 connector;...
  • Page 24: Starting And Checking The Unit

    • The easiest way to manage your unit over the internet is to use a smartphone with the Komfovent Control app. Launch the app on your phone (the phone must have Internet access). When you connect for the first time, the app will ask you to scan the QR code at the front of the controller board (see Fig.
  • Page 25 100% Ventilation Pageidaujama Pageidaujama Pageidaujama Pageidaujama 100% intensity temperatūra temperatūra temperatūra temperatūra 20°C 20°C 20°C 20°C 20°C 20°C 20°C 20°C temperature Depends on your order. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 26: Control Panel C6.1

    To turn off the air handling unit and return to the home screen: 16:30 Menu Menu Menu Overview Overview Overview TURN OFF? Scheduling Planavimas Scheduling INTENSIVE Settings Settings Settings TURN OFF TURN TURN ON AUTO UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 27: Control Panel C6.2

    Should you forget a changed password, it can be reset to the initial “user”. To do this, you must restore the factory settings for the air handling unit using control panel. UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 28 АUТО AWAY NORMAL INTENSIVE BOOST AWAY NORMAL INTENSIVE BOOST KITCHEN FIREPLACE OVERRIDE HOLIDAYS MODIFY > MODIFY > KITCHEN FIREPLACE OVERRIDE HOLIDAYS MODIFY > MODIFY > UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 29: Quick Check

    The condensate easily flows from the unit and the drainage piping is watertight Other notes: Unit installed by Company Phone Date Signature UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 30: Filter Inspection And Replacement

    Contaminated filters increase pressure loss of the unit, reduce purification efficiency and increase power consumption. Domekt R 200 VSO UAB KOMFOVENT we reserve the right to make changes without prior notice DOMEKT C8_VSO_installation manual_23-09...
  • Page 32 SERVICE AND SUPPORT PARTNERS LITHUANIA J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at UAB KOMFOVENT Phone: +370 5 200 8000 Ventilair group www.ventilairgroup.com ACB Airconditioning www.acbairco.be service@komfovent.com www.komfovent.com REKUVENT s.r.o. www.rekuvent.cz SWEDEN Komfovent AB WESCO AG www.wesco.ch Ögärdesvägen 12A SUDCLIMATAIR SA www.sudclimatair.ch...