11. CONTROL AND SETTINGS. CONTROL PANEL C5.1 ..........................29 11.1. Parameter overview ....................................... 31 11.2. Turning on and selection of ventilation modes ........................... 32 11.3. Setting parameters of ventilation modes .............................. 33 UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 4
14.5. Direct evaporation cooler/heater (DX) ..............................57 14.6. Electrical heater ....................................... 57 15. TROUBLESHOOTING ......................................58 ANNEX 1. Filter inspection and replacement ............................... 61 UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
An air-handling unit is a device designed to ensure good ventilation in the premises. Air handling unit supplies filtered fresh air from outside. Domekt S and Verso Standard S – air handling units without heat exchangers, intended solely for air supply to the premises.
Use personal protective equipment. Even small units should be transported on a forklift, a trolley or carried by multiple persons. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 7
After delivery of the air handling unit, carefully inspect its packaging for damage. If mechanical or other damage is visible (e.g., wet cardboard packaging), notify the carrier immediately. If the damage is significant, do not accept the unit. Inform the selling company or the representative of UAB KOMFOVENT within three business days about any damage detected during delivery.
Domekt S and Verso Standard S units are usually attached to the ceiling, floor slab or other horizontal structures with the doors down. For this purpose, their housing has special brackets with integrated vibration absorbers. The brackets should be screwed to the supporting structure of the floor slab with threaded rods or anchor bolts.
Page 9
Domekt S 800 F Domekt S 1000 F Verso S 1300 F Ø 10,5 Unit Verso S 2100 F 1034 71,5 Verso S 3000 F 1049 1010 UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Most of the Domekt S and Verso Standard S units have seals on the side for routing cables of external compo- nents and sensors into the automation box.
Page 11
Round Verso S 1300 F Round 2100 F Rectangular 700 × 200 700 × 200 3000 F Rectangular 600 × 400 600 × 400 UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
(see section “Electrical installation”) that should be mounted on the surface of the heater. It is recommended to use PPU made by Komfovent. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Condensate collection location must be easily accessible for cleaning and disinfection. Fig. 8. Condensate drain connection to sewer system UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
• Inspect the power cable ant other wiring for damage in insulation. • Locate the wiring diagram for your unit according to the unit type. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Fig. 9. C5 controller main board 1 – control panel connection, 2 – Intranet or Internet connection, 3 – inner connections of components, 4 – terminals for external components UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 16
(i.e. to start the unit by closing contacts). OVR function settings are set via the control panel or computer. This function is active as long as terminals are closed. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 17
For the most accurate temperature measurement, sensor in a duct must be installed after all heating/cooling devices at least two duct diameters away from the nearest coil. >2D Fig. 13. Installation of a supply air temperature sensor UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 18
All wires to be connected to the main controller board shall be pulled through grommets (top or side of the air handling unit). Grommets are fastened to ensure tightness. If the DX device was not predefined in the controller software, these outputs will be inactive. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
150 m long. White Green LIN B Yellow LIN A +24V 4 x 0,22 mm 2 < 150 m Fig. 14. Control panel wiring diagram UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Internet. In case of a computer, the unit is controlled via a web browser, and in case of a smart phone - via the Komfovent app. Use CAT5 type cable to connect your AHU to the computer network (RJ45 connection;...
Page 21
An air handling unit connected to a network router can be controlled by a computer via wireless connection (Wi-Fi). The unit may also be controlled wirelessly in a local network using a smart phone with the Komfovent app. Once the unit is con- nected to the network router, you should assign a free IP address on the local network.
55% (F7) 858 × 287 × 46 3000 F Compact ePM1 55% (F7) × 2 450 × 480 × 96 Depends on the order. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
• The air handling unit shall not be turned on without installed and connected protective earthing. In case of any doubts, contact your installer or “Komfovent” representative to make sure that the unit is operational. 8.1. Quick Inspection...
For information on how to select an air flow control method see Chapter “Control and Settings”. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
OCV function has priority over AQC function. For information on how to activate this function and set temperature ranges see Chapter “Control and Settings”. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
For information on how to activate this function and set ON/OFF temperatures see Chapter “Control and Settings”. Is shown only if a room temperature sensor is connected (to be purchased separately). UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
25 °C. Water flow sensor may also be used as an additional frost protection (see Chapter “Water Flow Monitoring Function”). UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
This feature is pre-ordered and configured at the factory. Later, settings of this function may only be changed by a service representative. Sold separately. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
C5.1 panel has a colour touchscreen. If the unit is connected to the mains, the control panel will display the home screen or screen saver that you can switch off with a single tap. 16:30 21,9 °C Temperature ECONOMY 1 Sold separately. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 30
Air cooler operation „Override“ mode Fan operation Air humidifier operation Alarm signal Air flow increasing Summer night cooling by activated function mode (see chapter Functions) UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Operation counters 16,6 °C Overview Scheduling Water temperature Detailed information 25,3 °C Supply humidity 70 % Air quality 1600 ppm Functions Settings 1 / 3 UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
During the first minute of starting the unit, the unit automation checks the settings, automation components and opens air dampers. Later, a signal is released to the fans and the unit starts operating at a selected ventilation mode. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
SPECIAL Supply flow 680 m Setpoint 21 °C Heating Cooling Humidifying 1 / 2 UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Add new holiday Standby mode is optional. The device will only operate at a set time. The unit will automatically stop during unspecified periods. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
AHU and other detailed data. 21,9 °C Outdoor temperature 16,6 °C Water temperature 25,3 °C Supply humidity 70 % Air quality 1600 ppm 1 / 3 UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
“Minimum airflow”. Winter stop -15 °C Winter start 5 °C Summer start 25 °C Reset settings UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 37
COMFORT 1 COMFORT 1 Setpoint 2 Setpoint 2 30% RH 8 g/m3 Mode 2 Mode 2 ECONOMY 2 ECONOMY 2 Reset settings Reset settings UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 38
This function only runs when optional additional zone modules are connected. Is shown only if a room temperature sensor is connected (to be purchased separately). UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Temperature control Supply Room • Flow control The user can select a desired air flow control method (see Chapter “Air Flow Control”). Flow control UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 40
± 5 ° C and the humidity within ± 10% range. Panel sensor calibration Temperature correction Humidity correction Temperature correction 5,0 °C 10,0%RH °C Humidity correction 0,0%RH 0,0°C -5,0 °C -10,0%RH UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Brightness Panel temperature Row 1 Panel humidity Time Row 2 100% Supply temperature Panel temperature Row 3 Extract temperature Panel humidity 1 / 2 UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 42
(see Chapter “Control and settings. Computer”). Panel lock • Touch sounds You can turn on/off touch sounds. Two types of touch sounds are available. Touch sound Click Beep UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
If You forgot a changed password, it can be reset to the initial “user” from the control panel (Settings→Air handling unit→Reset settings). Displayed unit diagram depends on the unit type and ordered components. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
12.1.2. Flow control modes Selecting an air flow control method for controlling fan speed (see Chapter 2.2 “Air Flow Control”). FLOW CONTROL MODE Mode UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
OUTDOOR COMPENSATED VENTILATION (OCV) Enable Minimum airflow -40.0 Winter compensation stop °C Winter compensation start °C 20.0 °C Summer compensation start 50.0 Summer compensation stop °C UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
12.2.5. Operation on demand (OOD) Setting a critical air quality sensor value. The unit starts as soon as this value is exceeded. OPERATION ON DEMAND (OOD) Enable Setpoint UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Supply temperature °C Heating Cooling 0.0 % Displayed only when this function is pre-ordered. This function only works when optional additional zone modules are connected. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
ACTUAL ALARMS 21A: Electric heater overheat 3B: VAV calibration fail Reset Is shown only if a room temperature sensor is connected (to be purchased separately). UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
For detailed performance analysis, you may download a device logbook (Log) which contains weekly operation data. To open a logbook you will need a “Log plotter” app that you can download on the “Komfovent” website. This data can be useful in the event of a failure and may facilitate repair procedures, therefore, we recommend downloading an operation logbook and handing it over to the authorised service personnel.
Christmas holidays). HOLIDAYS Day - Month - Year Day - Month - Year Mode - 2019 - 2020 Special Standby Comfort1 Comfort2 Economy1 Economy2 Program UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Setting IP address, Modbus and BACnet or computer network parameters. CONNECTIVITY . 168 . 50 IP mask . 255 Modbus ID RS-485 19200 baud Modbus ID 47808 Modbus ID UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Write down the computer network parameters before restoring factory settings (see Menu “Connectivi- ty”), as these settings will also be reset and communication with the air handling unit may be lost until re-configuration. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
IP address is incorrect, set the IP address and IP mask (see the “Connectivity” menu). Connect your mobile device to the internal network via Wi-Fi and run the “Komfovent C5” app. Launched for the first time, “Komfovent C5” app will attempt connecting to default IP address (192.168.0.50) (if not changed);...
Page 54
Connectivity Default Default 192.168.0.50:502 192.168.0.50:502 Komfovent Komfovent 123.123.123:502 123.123.123:502 21,9 °C Connect to selected AHU? Temperature ECONOMY 1 Add new Delete Add new Delete UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
The inside of the air handling unit can be cleaned with a vacuum cleaner and/or a damp cloth. When cleaning, prevent water from entering electrical components of the unit. Make sure all surfaces are completely dry before starting the unit. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
(see Fig. 21). As soon as the differential pressure reaches the set limit, filter contamination message is displayed. Once the filters are replaced, clear the contaminated filter message on a control panel or computer. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Tubes must be cleaned with a damp cloth or compressed air. Wait for the tubes to dry completely before turning on the device. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Supply air temp. sen- Not connected or faulty supply 1A, 2A sor needs to be replaced, contact an authorized sor failure air temperature sensor. service representative. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 59
Look ing. for a yellow sticker with the word “Reset” inside the unit that marks an overheating protection fuse. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 60
1. Check connection of external devices or con- 126A Controller failure defective external devices. tact the representative of the installer. 2. Faulty C5 controller. 2. Contact authorised service. UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Layout of filters and components presented in the “Installation Manual”. Domekt S 650 F - S 800 F Domekt S 1000 F UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 62
Verso S 1300 F Verso S 2100 F Verso S 3000 F UAB KOMFOVENT we reserve the right to make changes without prior notice Domekt S_Verso Standard S_manual_23-04...
Page 64
SERVICE AND SUPPORT PARTNERS LITHUANIA J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at UAB KOMFOVENT Phone: +370 5 200 8000 Ventilair group www.ventilairgroup.com ACB Airconditioning www.acbairco.be service@komfovent.com www.komfovent.com REKUVENT s.r.o. www.rekuvent.cz SWEDEN Komfovent AB WESCO AG www.wesco.ch Ögärdesvägen 12A SUDCLIMATAIR SA www.sudclimatair.ch...