Controller Communication Channel Troubleshooting - Allen-Bradley PLC-5 User Manual

Enhanced and ethernet plc-5 programmable controllers
Hide thumbs Also See for PLC-5:
Table of Contents

Advertisement

F-4
Troubleshooting
Indicator Color
A or B
Green
(steady)
Green
(blinking
rapidly or
slowly)
Red
(steady)
Red
(blinking
rapidly or
slowly)
Off
Publication 1785-UM012D-EN-P - July 2005

Controller Communication Channel Troubleshooting

Channel Mode
Description
Remote I/O Scanner Active Remote I/O link, all
adapter modules are
present and not faulted
Remote I/O Adapter Communicating with
scanner
DH+
Controller is transmitting or
receiving on DH+ link
Remote I/O Scanner At least one adapter is
faulted or has failed
DH+
No other nodes on network
Remote I/O Scanner
Hardware fault
Remote I/O Adapter
DH+
Remote I/O Scanner All adapters faulted
DH+
Bad communication on DH+ Duplicate
Remote I/O Scanner
Channel offline
Remote I/O Adapter
DH+
Probable Cause Recommended Action
Normal operation No action required
• Power off at
• Restore power to
remote rack
the rack
• Cable broken
• Repair cable
Hardware error
Turn power off, then on
Check that the software
configurations match the
hardware set-up
Replace the controller.
• Cable not
• Repair cable
connected or
broken
• Power off at
• Restore power to racks
remote racks
Correct station address
node detected
Channel is not
Place channel online
being used
if needed