Allen-Bradley PLC-5 User Manual page 169

Enhanced and ethernet plc-5 programmable controllers
Hide thumbs Also See for PLC-5:
Table of Contents

Advertisement

This Field
Specifies
User mode char.
The character for the mode attention
character (above)
Serial Settings
Baud rate
Communication rate for channel 0
Configure all devices in the system for
the same communication rate
Parity
Parity setting for channel 0
Parity provides additional message
packet error detection.
Bits per character
Select the number of bits that make up
a transmitted character.
Error detect
Whether you want error detection set
to BCC or CRC
Stop bits
Match the number of stop bits to the
device with which you are
communicating
Control line
Select the mode in which the driver
operates.
Option Settings
RTS send delay
The time delay between the time the
RTS is asserted and the beginning of
the message transmission
RTS off-delay
The time delay between the time the
end of the message transmission and
the RTS is de-asserted
Communicating with Devices on a Serial Link
Configure by Doing the Following
Enter a valid attention character. If the attention character you want to
use is a control character, specify the ASCII equivalent.
When the controller encounters the attention character and the user
mode character, the controller sets channel 0 communication to user
mode. The remote mode change option must be ENABLED.
Select 110, 300, 600, 1200, 2400, 4800, 9600, or 19.2k bps.
Select NONE or EVEN.
Select 7 or 8.
Select one of the following:
BCC: the controller sends and accepts messages that end with a BCC byte
for error checking. BCC is quicker and easier to implement in a computer
driver.
CRC: the controller sends and accepts messages with a 2-byte CRC for
error checking. CRC is more complete checking
Configure both stations to use the same type of error checking.
Select 1, 1.5, or 2.
Select a method appropriate for your system's configuration:
If you are not using a modem, choose NO HANDSHAKING.
If you are using a full-duplex modem, choose FULL-DUPLEX.
Enter a value between 0 and 255. Limits are defined in 20 ms intervals.
For example to wait 40 ms, type 2. The recommended time elapse is 0,
unless you are using a modem that automatically returns the CTS as soon
as it receives the RTS. If this is the case, enter a delay time to make sure
the modem is able to transmit before it attempts to send the message.
Enter a value between 0 and 255. Limits are defined in 20 ms intervals.
For example to wait 40 ms, type 2. The recommended time elapse is 0,
unless you are using a modem that automatically returns the CTS as soon
as it receives the RTS. If this is the case, enter a delay time to make sure
the modem is able to transmit before it attempts to send the message.
Publication 1785-UM012D-EN-P - July 2005