Allen-Bradley PLC-5 User Manual page 166

Enhanced and ethernet plc-5 programmable controllers
Hide thumbs Also See for PLC-5:
Table of Contents

Advertisement

10-16
Communicating with Devices on a Serial Link
Publication 1785-UM012D-EN-P - July 2005
To define a polling scheme using standard mode, you must specify the
following on the DF1 master configuration screen in your programming
software:
Configuration Parameter
Polling mode
Master message transmit
Normal poll file
Priority poll file
Normal poll group size
Active station file
The master station polls the slave station in the following a
definitive sequence:
1. All stations in the active priority poll file.
2. Specified stations in the active normal poll file. The number of stations
polled in this file is determined by the normal poll group size specified
on the configuration screen. If the group size was 3, for example, then
three stations would be polled in the normal file before the master
continues to the next step in the sequence.
3. One station in the inactive poll file after all active stations in the normal
poll file have been polled.
Definition
How you want the master to poll the station lists.
When you want the master to send messages.
An integer file in which you place the station addresses of
the remote stations.
The default size is 64 words.
An integer file in which you place the addresses of stations
from which you need to collect data more frequently.
The default size is 64 words.
The number of stations that the master polls before it polls a
station in the priority poll list.
A binary file that stores the station addresses of all active
stations on the link.
The default size is 18 words.
Both the normal poll list and the priority poll list can have
active and inactive stations. A station becomes inactive
when it does not respond to a master's request for data.