Allen-Bradley PLC-5 User Manual page 282

Enhanced and ethernet plc-5 programmable controllers
Hide thumbs Also See for PLC-5:
Table of Contents

Advertisement

B-8
Processor Status File
This
Fault
Code
Indicates this Fault
90
Sidecar module extensive memory test failed. Call your Allen-Bradley representative for
service
91
Sidecar module undefined message type
92
Sidecar module requesting undefined pool
93
Sidecar module illegal maximum pool size
94
Sidecar module illegal ASCII message
95
Sidecar module reported fault, which may be the result of a bad sidecar program or of a
hardware failure
96
Sidecar module not physically connected to the PLC-5 controller
97
Sidecar module requested a pool size that is too small for PC
98
Sidecar module first/last 16 bytes RAM test failed
99
Sidecar module-to-controller data transfer faulted
100
Controller-to-sidecar module transfer failed
101
Sidecar module end of scan transfer failed
102
The file number specified for raw data transfer through the sidecar module is an illegal value
103
The element number specified for raw data transfer through the sidecar module is an illegal
value
104
The size of the transfer requested through the sidecar module is an illegal size
105
The offset into the raw transfer segment of the sidecar module is an illegal value
106
Sidecar module transfer protection violation; for PLC-5/26, -5/46, and -5/86 controllers only
Publication 1785-UM012D-EN-P - July 2005
3
command (occurs at power-up)
And the Fault Is
Recoverable