Allen-Bradley PLC-5 User Manual page 158

Enhanced and ethernet plc-5 programmable controllers
Hide thumbs Also See for PLC-5:
Table of Contents

Advertisement

10-8
Communicating with Devices on a Serial Link
This Field
Specifies
Stop bits
Match the number of stop bits to the
device with which you are
communicating
Control line
Select the mode in which the driver
operates.
Option Settings
Duplicate detect
Whether you want the controller to
detect and ignore duplicate messages
ACK timeout
The amount of time you want the
controller to wait for an
acknowledgment to its message
transmission
MSG appl
The number of seconds within which
timeout
the reply message must be received
before the error bit is set on the
message. The timer starts when the
ladder program first initiates the
message and is restarted if/when the
ACK is received
NAK receive
The number of NAKs your controller
can receive in response to a
transmitted message
DF1 ENQS
The number of enquiries (ENQs) that
you want the controller to send after
an ACK timeout
Publication 1785-UM012D-EN-P - July 2005
Configure by Doing the Following
Select 1, 1.5, or 2.
Select a method appropriate for your system's configuration:
If you are not using a modem, choose NO HANDSHAKING.
If you are using a full-duplex modem, choose FULL-DUPLEX.
Select the desired setting.
Enter a value 0-65535. Limits are defined in 20 ms intervals. For example
to wait 40 ms, type 2. The recommended time elapse is 1 second.
Specify 1 second by typing 50.
Enter one of the following values:
1:30-60 seconds
2:60-90 seconds
3:90-120 seconds
4:120-150 seconds
5:150-180 seconds
6:180-210 seconds
7:210-240 seconds
Enter a value 0-255. The recommended setting is 3.
Enter a value 0-255. The recommended setting is 3.