Allen-Bradley PLC-5 User Manual page 136

Enhanced and ethernet plc-5 programmable controllers
Hide thumbs Also See for PLC-5:
Table of Contents

Advertisement

9-4
Communicating with Devices on a DH+ Link
This Field
Specifies
Diagnostic file
The file containing the channel's
status information
Baud rate
Communication rate for the current
channel
Node address
The station address of your controller If your DH+ channel is:
Link ID
The local link where the channel
resides
Publication 1785-UM012D-EN-P - July 2005
To configure a channel to support a DH+ link, use the DH+ configuration
screen in your programming software.
configure the channel
for DH+
Configure by Doing the Following
Enter an integer file number (10-999). The system creates an integer file
40 words long.
ATTENTION: Assign a unique diagnostic file to each channel. Do not
assign a diagnostic file that is the I/O status file you assigned or any
other used file. Unpredictable machine damage can result.
Important: You must define a diagnostics file for a channel configured for
anything but unused (even if you are not using the channel) if you want to
get status information for that channel.
If the DH+ channel is
channel 1A, specify the baud rate by setting SW1 (see chapter 23)
any other channel, select 57.6 kbps, 115.2 kbps, or 230.4 kbps through the
programming software
1A—specify the DH+ station number by setting SW1 on your controller
(see chapter 23).
anything other than 1A—cursor to Node Address field, enter a value of
0-77 octal, and press
Each station on a DH+ link must have a unique address.
If your DH+ link is bridged to another Data Highway network, cursor to the
field, type a decimal number to identify the protocol link to which the
channel is connected, and press
.
[Enter]
.
[Enter]