Observe the stipulations of the power supply company concerning energy fed into the
grid, emergency power mode and the operation of storage systems.
The Fronius Symo Hybrid is a grid-connected inverter with an emergency power function
– it is not a stand-alone inverter. The following restrictions must therefore be observed in
emergency power mode:
-
-
Choosing the loc-
ation of the
inverter
IP 66
6
Emergency power mode may be in operation for at least 1500 hours
Emergency power mode may be in operation for more than 1500 operating hours if
15% of the duration of the inverter's grid power feed operation is not exceeded at
the relevant time
The inverter is suitable for indoor installation.
The inverter is suitable for outdoor installation.
Because of its IP 65 protection class, the inverter is resistant to water
jets from any direction and can also be used in damp environments.
In order to minimise the heating up of the inverter, do not expose it to
direct insolation. Install the inverter in a protected location, e.g. in the
vicinity of the solar modules or beneath the eaves.
U
at an altitude of:
DCmax
0 to 2000 m = 1000 V
2000 to 2500 m = 900 V
2500 to 3000 m = 815 V
3000 to 3400 m = 750 V
IMPORTANT! The inverter must not be installed or used at altitudes
above 3400 m.
Do not install the inverter in:
NH
3
-
Areas where ammonia, corrosive vapours, acids or salts are
present
(e.g. fertiliser stores, ventilation openings from cattle sheds,
chemical plants, tanneries, etc.)
During certain operating phases the inverter may produce a slight
noise. For this reason it should not be installed in an occupied living
area.