Information regarding the
system hydraulics
6
4. System hydraulics expansion vessels
The collectors can be operated with a high specific throughput (so-called High-
Flow). Advantages: The collector is well cooled = high collector efficiency level,
low heat losses at the flow line. Disadvantages: High pressure drop = powerful
pump, large pipe cross-sections.
Throughput: High-Flow (90 l/h x coll), ANRO (45/55) 20 °C
Solar line
Collector
length
number
(m)
20
2
2
70
15
3
3
45
10
4
4
30
4
75
20
5
5
45
15
6
6
35
6
100
30
7
7
70
20
8
8
60
9
15
9
45
9
120
28 x 1.5
10
25
10
90
28 x 1.5
All details are recommendations and may differ from system to system.
Therefore, the diaphragm expansion vessel must be sized specifically.
Solar
Pump
line
assembly
Ø (mm)
12 x 1
10
SEM-1-300
15 x 1
10
SEM-1-300
12 x 1
10
SEM-1-400
15 x 1
10
SEM-1-400
12 x 1
10
SEM-1-500
15 x 1
10
SEM-1-500
18 x 1
10
SEM-1-500
15 x 1
10
SEM-1-750
18 x 1
10
SEM-1-750
15 x 1
10
SEM-1-750
18 x 1
10
SEM-1-750
22 x 1
10
SEM-1-750
18 x 1
10
SEM-1-1000
22 x 1
10
SEM-1-1000
18 x 1
10
SEM-1-1000
22 x 1
10
SEM-1-1000
18 x 1
10
SEM-1-1000
22 x 1
10
SEM-1-1000
10
SEM-1-1000
22 x 1
10
SEM-1-1000
10
SEM-1-1000
Expansion
Cylinder
vessel 2.5 bar
12
12
12
18
18
18
25
25
25
25
25
35
35
35
35
35
35
50
50
50
50
3062815_0110