Section 4
IEC 60870-5-103 vendor specific implementation
Info. no.
48
49
50
51
52
4.1.5
Function status fault protection for IEC 60870-5-103
I103FLTPROT
4.1.5.1

Functionality

I103FLTPROT is used for fault indications in monitor direction. Each input on the function
block is specific for a certain fault type and therefore must be connected to a correspondent
signal present in the configuration. For example: 68_TRGEN represents the General Trip of the
device, and therefore must be connected to the general trip signal SMPPTRC_TRIP or
equivalent.
The delay observed in the protocol is the time difference in between the signal that is
triggering the Disturbance Recorder and the respective configured signal to the IEC
60870-5-103 I103FLTPROT.
4.1.5.2

Function block

BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
68_TRGEN
69_TRL1
70_TRL2
71_TRL3
72_TRBKUP
73_SCL
74_FW
75_REV
76_TRANS
77_RECEV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
84_STGEN
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FLTLOC
IEC10000291 V1 EN-US
Figure 10: I103FLTPROT function block
28
Message
Earth fault L1
Earth fault L2
Earth fault L3
Earth fault forward
Earth fault reverse
I103FLTPROT
IEC10000291-1-en.vsd
© Copyright 2011 ABB. All rights reserved
Supported
No
No
No
Yes
Yes
1MRK 511 243-UEN A
GUID-6D52F442-1592-4BA7-919C-0CD79046CAE5 v1
GUID-F0ED13B8-6B82-4CA7-8F22-C200C33EBB7E v1
IEC 60870-5-103, 650 series
Communication protocol manual