Section 4
IEC 60870-5-103 vendor specific implementation
4.3

Disturbance recorder file transfer

4.3.1

Disturbance recordings

The transfer functionality is based on the Disturbance recorder function. The analog and
binary signals recorded will be reported to the master by polling. The eight last
disturbances that are recorded are available for transfer to the master. A file that has
been transferred and acknowledged by the master cannot be transferred again.
The binary signals that are reported by polling are those that are connected to the
disturbance function blocks B1RBDR to B6RBDR. These function blocks include the
function type and the information number for each signal. For more information on the
description of the Disturbance report in the Technical reference manual. The analog
channels, that are reported, are those connected to the disturbance function blocks
A1RADR to A4RADR. The eight first ones belong to the public range and the remaining
ones to the private range.
The following elements are used in the ASDUs (Application Service Data Units) defined in the
standard.
Analog signals, 40-channels: the channel number for each channel has to be specified.
Channels used in the public range are 1 to 8 and with:
I
connected to channel 1 on disturbance function block A1RADR
L1
I
L2
I
L3
I
connected to channel 4 on disturbance function block A1RADR
N
V
L1E
V
L2E
V
L3E
V
EN
Channel number used for the remaining 32 analog signals are numbers in the private range 64
to 95.
Binary signals, 96-channels: for each channel the user can specify a FUNCTION TYPE and an
INFORMATION NUMBER.
For each input of the Disturbance recorder function there is a setting for the information
number of the connected signal. The information number can be set to any value between 0
and 255.
Furthermore, there is a setting on each input of the Disturbance recorder function for the
function type. Refer to description of Main Function type set on the local HMI.
Disturbance upload
All analog and binary signals that are recorded with disturbance recorder can be reported to
the master. The last eight disturbances that are recorded are available for transfer to the
master. A successfully transferred disturbance (acknowledged by the master) will not be
reported to the master again.
42
The current implementation of the IEC 60870-5-103 commands will reject any
new command if a previously issued command has not yet been completed.
connected to channel 2 on disturbance function block A1RADR
connected to channel 3 on disturbance function block A1RADR
connected to channel 5 on disturbance function block A1RADR
connected to channel 6 on disturbance function block A1RADR
connected to channel 7 on disturbance function block A1RADR
connected to channel 8 on disturbance function block A1RADR
© Copyright 2011 ABB. All rights reserved
1MRK 511 243-UEN A
M17109-111 v3
M11874-467 v3
M17109-141 v3
M11874-629 v3
IEC 60870-5-103, 650 series
Communication protocol manual