Section 3
3.1

IEC 60870-5-103 engineering in PCM600

The Application Configuration tool (ACT) and the Parameter Setting tool (PST) in PCM600 are
used to configure the communication for IEC 60870-5-103 protocol.
1.
Add the desired IEC 60870-5-103 function blocks to the application configuration in the
Application Configuration tool.
2.
Connect the outputs of desired protection and monitoring function in the application
configuration to the inputs of the corresponding IEC 60870-5-103 function block.
3.
Set the function type and desired information number, where an information number
must be supplied, for each IEC 60870-5-103 function block instance in the Parameter
Setting tool.
3.2

Specific IEC 60870-5-103 settings

Set parameter
Parameter
communication/1:IEC60870-5-103 in local HMI. The IED is automatically restarted when
parameter
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V1 EN-US
Figure 3:
The general settings for IEC 60870-5-103 communication are the following:
SlaveAddress and BaudRate : Settings for slave number and communication speed (baud
rate).
The slave number can be set to any value between 1 and 31. The communication speed, can
be set either to 9600 bits/s or 19200 bits/s.
RevPolarity : Setting for inverting the light (or not).
CycMeasRepTime : Setting for CycMeasRepTime must be coordinated with the xDbRepInt
and
I103MEAS function block for more information.
EventRepMode : Defines the mode for how events are reported. The event buffer size is
1000 events.
IEC 60870-5-103, 650 series
Communication protocol manual
IEC 60870-5-103 communication
engineering
Operation to On either in Parameter Setting tool or from the local HMI.
Operation is found under Main menu/Configuration/Communication/Station/
Operation is set.
Settings under IEC60870-5-103:1 in Local HMI
xAngDbRepInt reporting setting on the MMXU measurement function blocks. See
© Copyright 2011 ABB. All rights reserved

IEC 60870-5-103 communication engineering

GUID-284EB0BA-BC79-4B90-8B78-878BA225479E v1