Settings; Supported Information Types; Status For User Defined Signals For Iec 60870-5-103 I103Usrdef; Functionality - ABB Relion 650 Series Communication Protocol Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 243-UEN A
4.1.7.4

Settings

Table 22:
I103SUPERV Non group settings (basic)
Name
Values (Range)
FunctionType
4.1.7.5

Supported information types

Supervision indications in monitor direction, I103SUPERV
Number of instances: 1
Function type is selected with parameter
Information number is defined for output signals.
Info. no.
32
33
35
36
37
38
39
46
47
4.1.8
Status for user defined signals for IEC 60870-5-103
I103USRDEF
4.1.8.1

Functionality

I103USRDEF is a function blocks with user defined input signals in monitor direction. These
function blocks include the
the information number parameter for each input signal.
I103USRDEF can be used, for example in mapping the INF numbers not supported directly by
specific function blocks, like: INF17, INF18, INF20 or INF35. After connecting the appropriate
signals to the I103USRDEF inputs, the user must also set the
IEC 60870-5-103, 650 series
Communication protocol manual
Unit
1 - 255
-
Message
Measurand supervision I
Measurand supervision U
Phase sequence supervision
Trip circuit supervision
I>>back-up operation
VT fuse failure
Teleprotection disturbed
Group warning
Group alarm
FunctionType parameter for each block in the private range, and
© Copyright 2011 ABB. All rights reserved
Step
Default
1
1
FunctionType .
Supported Type
Yes
1
Yes
1
No
1
No
1
Yes
1
Yes
1
No
1
Yes
1
Yes
1
IEC 60870-5-103 vendor specific implementation
Description
Function type (1-255)
GI
COT
Y
1,7,9
Y
1,7,9
Y
1,7,9
Y
1,7,9
Y
1,7,9
Y
1,7,9
Y
1,7,9
Y
1,7,9
Y
1,7,9
GUID-DADC9CE4-2E80-426C-A3B6-A8E8C7AC3CD4 v1
InfNo_x values in the settings.
Section 4
PID-2658-SETTINGS v2
M11874-171 v2
33