Supervison Status For Iec 60870-5-103 I103Superv; Functionality; Function Block; Signals - ABB Relion 650 Series Communication Protocol Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 4
IEC 60870-5-103 vendor specific implementation
Info. no.
19
20
21
22
23
24
25
26
4.1.7

Supervison status for IEC 60870-5-103 I103SUPERV

4.1.7.1

Functionality

I103SUPERV is a function block with defined functions for supervision indications in monitor
direction. This block includes the
parameter is defined for each output signal.
4.1.7.2

Function block

BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
IEC10000293 V1 EN-US
Figure 12:
4.1.7.3

Signals

Table 21:
Name
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL
32
Message
LED reset
Monitor direction blocked
TestMode
Local Parameter setting
Setting group 1 active
Setting group 2 active
Setting group 3 active
Setting group 4 active
I103SUPERV
IEC10000293-1-en.vsd
I103SUPERV function block
I103SUPERV Input signals
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
© Copyright 2011 ABB. All rights reserved
Supported
Yes
No
No
Yes
Yes
Yes
Yes
Yes
FunctionType parameter, and the information number
Default
Description
0
Block of status reporting
0
Information number 32, measurand supervision of I
0
Information number 33, measurand supervision of U
0
Information number 37, I high-high back-up protection
0
Information number 38, fuse failure VT
0
Information number 46, group warning
0
Information number 47, group alarm
1MRK 511 243-UEN A
GUID-E7A28D8D-398E-437C-9B58-AE125BC38058 v1
GUID-69C2C974-2D64-4174-9F9A-15383C09050D v1
PID-2658-INPUTSIGNALS v2
IEC 60870-5-103, 650 series
Communication protocol manual