Signals; Settings - ABB Relion 650 Series Communication Protocol Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 243-UEN A
4.1.5.3

Signals

Table 17:
Name
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
68_TRGEN
69_TRL1
70_TRL2
71_TRL3
72_TRBKUP
73_SCL
74_FW
75_REV
76_TRANS
77_RECEV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
84_STGEN
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FLTLOC
4.1.5.4

Settings

Table 18:
I103FLTPROT Non group settings (basic)
Name
Values (Range)
FunctionType
IEC 60870-5-103, 650 series
Communication protocol manual
I103FLTPROT Input signals
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
REAL
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
1 - 255
-
© Copyright 2011 ABB. All rights reserved
Default
Description
0
Block of status reporting.
0
Information number 64, start phase L1
0
Information number 65, start phase L2
0
Information number 66, start phase L3
0
Information number 67, start residual current IN
0
Information number 68, trip general
0
Information number 69, trip phase L1
0
Information number 70, trip phase L2
0
Information number 71, trip phase L3
0
Information number 72, back up trip I>>
0
Information number 73, fault location in ohm
0
Information number 74, forward/line
0
Information number 75, reverse/busbar
0
Information number 76, signal transmitted
0
Information number 77, signal received
0
Information number 78, zone 1
0
Information number 79, zone 2
0
Information number 80, zone 3
0
Information number 81, zone 4
0
Information number 82, zone 5
0
Information number 84, start general
0
Information number 85, breaker failure
0
Information number 86, trip measuring system phase L1
0
Information number 87, trip measuring system phase L2
0
Information number 88, trip measuring system phase L3
0
Information number 89, trip measuring system neutral N
0
Information number 90, over current trip, stage low
0
Information number 91, over current trip, stage high
0
Information number 92, earth-fault trip, stage low
0
Information number 93, earth-fault trip, stage high
0
Autorecloser in progress (SMBRREC- INPROGR)
0
Faultlocator faultlocation valid (LMBRFLO-CALCMADE)
Step
Default
1
128
IEC 60870-5-103 vendor specific implementation
Description
Function type (1-255)
Section 4
PID-2656-INPUTSIGNALS v2
PID-2656-SETTINGS v2
29