2.5
Pneumatic connections
IMPORTANT
1 The actuator/valve combination can move after connecting
the air supply.
2 Ensure that the QC54 control modules are mounted
properly to the actuator to achieve good functioning and
the required ingress protection, before connecting the air
supply.
3 Check that the maximum supply pressure
Pmax = 8bar/116Psi
4 Be sure that the minimum required supply pressure for the
application is available at the actuator.
5 Take appropriate measures to prevent condensation or
moisture to entering the actuator or the control module.
Condensation or moisture can damage these components
and can result in failures.
6 The exhaust ports Ra and Rb on the module (see figure
3.1) are shipped from the factory with transport protection.
7 If ingress protection IP66 or NEMA4X is required, appropri-
ate connections must be used in exhaust ports Ra & Rb.
2.5.1
Operating media :
* Air or inert gasses.
* Air filtered at 50 micron.
* Dew point 10 K below operating temperature.
* For subzero applications take appropriate mea-
sures.
2.5.2
Single acting (spring return) or
Double acting actuator :
1 Remove the transport sticker from the air supply
(Ps).
2 Connect air supply to port (Ps).
Single acting
Control
Module cover
Double acting
Fig. 2.4: Pneumatic connections
Fieldbus Control module
OUNDATION
Ra
Ps
1/4" BSP or 1/4" NPT
Ra
Rb
Ps
1/4" BSP or 1/4" NPT
2.6
Electric Connections
2.6.1
Electrical Input, Fieldbus Interface
Voltage range *
Maximum current
Reverse polarity pro-
tection
Required external
protection
Environmental conditions :
Temperature *
Humidity
Altitude
Use
* In case the Control module is used in Hazardous
locations, check the chapters 10, 11 or 12 of the in-
stallation guide DOC.IG.QC54.1 for the applicable
temperature or voltage range.
2.6.2
Electrical data for the hazardous area
executions
In case the control module is used in Hazardous loca-
tions, check the chapters 10, 11 or 12 of the installa-
tion guide DOC.IG.QC54.1 for detailed instructions.
Non Incendive/Non Sparking
- QC54 FF
Intrinsically safe
- QC54 FF
- QC54 FF (FISCO)
Fig. 2.5 Install drip loops
9 to 32 volts
18 mA
Unit is not polarity sensitive.
Restrict the power supply
current to <600mA.
-20°C to +50°C
(-4°F to +122°F)
0 to 85% at 25°C(+77°F)
de-rate to 50% above 40°C
(104°F) (non-condensing).
Operating full power avail-
able up to 2000 meter (6000
feet).
In- and outdoor.
Chapter 10
Chapter 11
Chapter 12
OK
Page 9