Table 4.2 Bettis Q-Series™ Transducer Block (continued)
Index
Name
No.
41
RECOMMENDED_ACTION
42
FAILED_PRI
43
FAILED_ENABLE
44
FAILED_MASK
45
FAILED_ACTIVE
46
FAILED_ALM
47
MAINT_PRI
48
MAINT_ENABLE
49
MAINT_MASK
50
MAINT_ACTIVE
51
MAINT_ALM
52
ADVISE_PRI
53
ADVISE_ENABLE
54
ADVISE_MASK
55
ADVISE_ACTIVE
56
ADVISE_ALM
57
HEALTH_INDEX
58
FF_COMM_STAT
59
PWA_SIMULATE
Page 34
Reference manual F
Description
Enumerated list of recommended actions of the device, displayed with a
device alert (can be multiple, see table 4.3)
Designates the alarming priority of the FAILED_ALM. Handling defined
by FF.
0: All FAILED alerts disabled
1: All failed alerts suppressed
2: Higher process failed alerts
See alert table 4.3
See alert table 4.3
See alert table 4.3
Alarm indicating a failure within a device which makes the device non-
operational.
UNACKNOWLEDGED:
0: Undefined, 1: Acknowledged, 2: Unacknowledged
ALARM_STATE
0:Undefined 0
1:Clear- Reported
2:Clear- Not reported
3:Active- Reported
4:Active- Not reported
TIME_STAMP
SUBCODE value should match alert as stated under FAILED_ENABLE
VALUE
See index 42 FAILED_PRI
See alert table 4.3
See alert table 4.3
See alert table 4.3
See index 46 FAILED_ALM
See index 42 FAILED_PRI
See alert table 4.3
See alert table 4.3
See alert table 4.3
See index 46 FAILED_ALM
Parameter representing the overall health of the device.
- 100 being perfect and 1 being non-functioning.
- No alerts -> 100
ADVISE_ACTIVE -> -10 per advice
MAINT_ACTIVE -> - 40 per advise
FAIL_ACTIVE -> = 10 (10 also lowest value)
Indicates quality of FF communications
FF_COMM_ATTEMPTS - States the number of attempts.
When at max, reset to 0 for timed out messages also!
FF_COMM_TIME_OUT - States how many of the attempts were timed
out
Password protected and off when power cycled! If this is set to 2 then all
the alert parameters are writable 1: simulate off, 2 simulate enabled
OUNDATION
Alerts
Others
Fieldbus Control module
DOC.RM.BQC54.E Rev: 1
February, 2016
Valid Range
Initial Value Permission
N/A
0
Read only
0 to 15
2
Read / Write
N/A
N/A
Read only
Read only
Read only
Read only
Read only
Read only
0 to 15
2
Read / Write
N/A
Read only
0 to 15
2
Read / Write
N/A
Read / write
Read / write
Read only
10 to 100
100
Read only
0 to 65535
0
Read only
0 to 65535
0
Read only
1 and 2
1
Read / Write