Table 4.2 Bettis Q-Series™ Transducer Block (continued)
Index
Name
No.
36
FUNCTION_MODULE_
COUNTER
37
PNEUMATIC_MODULE_
COUNTER
38
ACTUATOR_MODULE_
COUNTER
39
VALVE_MODULE_COUNTER Counts the end position cycles performed by the valve
40
TIMERS (units are seconds). TIME_IN_POSITION - Holds the time in current position Reset to zero
Fieldbus Control module
OUNDATION
Description
Diagnostic configuration
Counts the end position cycles performed by the control module.
FM_CNT_VALUE (read only)
FM_CNT_LIMIT
Counts the end position cycles performed by the pneumatic module
PM_CNT_VALUE
PM_CNT_LIMIT
Counts the end position cycles performed by the actuator
ACT_CNT_VALUE
ACT_CNT_LIMIT
VLV_CNT_VALUE
VLV_CNT_LIMIT
when power switched off
TIME_IN_POSITION_HI_LIM - Sets a limit for an alert for the time in
position
OPEN_TIMERAVEL_TIME Indicates time between: - Pilot position
change commanded and - Open trip position reached.
OPEN_TRAVEL_TIME_HI_LIM
OPEN_TRAVEL_TIME_LO_LIM
OPEN_TRAVEL_TIME_AVG (average of 30 strokes)
OPEN_TRAVEL_AVG_HI_LIM
OPEN_TRAVEL_AVG_LO_LIM
CLOSE_TRAVEL_T Indicates time between: - Pilot position change
commanded and - Close trip position reached.
CLOSE_TRAVEL_TIME_HI_LIM
CLOSE_TRAVEL_TIME_LO_LIM
CLOSE_TRAVEL_TIME_AVG (average of 30 strokes)
CLOSE_TRAVEL_AVG_HI_LIM
CLOSE_TRAVEL_AVG_LO_LIM
Valid Range
Initial Value
Permission
0 -
N/A
Read only
4294967295
[2] 0 -
1,000,000
Read / Write
4294967295
0 -
N/A
Read / Write
4294967295
[2] 0 -
1,000,000
Read / Write
4294967295
0 -
N/A
Read / Write
4294967295
[2] 0 -
1,000,000
Read / Write
4294967295
0 -
N/A
Read / Write
4294967295
[2] 0 -
1,000,000
Read / Write
4294967295
0 to
0
Read only
4294967295
[2] 0 to
0
read.write
4294967295
0 to 65536
0
Read only
[2] 0 to 65536
0
Read / Write
[2] 0 to 65536
0
Read / Write
0 to 65536
0
Read only
[2] 0 to 65536
0
Read / Write
[2] 0 to 65536
0
Read / Write
0 to 65536
0
Read only
[2] 0 to 65536
0
Read / Write
[2] 0 to 65536
0
Read / Write
0 to 65536
0
Read only
[2] 0 to 65536
0
Read / Write
[2] 0 to 65536
0
Read / Write