3.2.1
Initialization (calibration) using local
buttons
For "Initialization (calibration) using the local buttons"
digital communication is not required but power sup-
ply is necessary (9V to 32V DC).
1 Press and confirm press the "Status/Auto-Initializa-
tion" button
2 Status LED will blink.
3 Actuator will cycle 2 or 3 times.
4 At the end of the routine the Status LED switches
to constant on, meaning the initialization was suc-
cessful.
Table 3.1 Status LED indications
Status
OK (init successful)
Initializing
Init error
Init default
Identification
Remarks:
- If the button board does not work, check the mode
of Transducer Block, make it OOS (Out Of Ser-
vice). Make sure the button board is enabled in
OOS mode. (see §3.4.1).
- If the Open or Closed LED is flashing, the auto
initialization (calibration) routine has failed, see
§3.4.2.
- If the read out in the PLC or DCS is reversed,
see §3.4.3.
- If the device is in operation and after a while the
"Open" or "Closed" feedback is lost, see §3.4.4.
- If the initialization (calibration) can not be started
via the push buttons, see §3.4.5.
Table 3.2 Button board functionality
Action
Initialize
Set to factory default
Switch point re-adjust-
ment
Page 12
Reference manual F
Status LED action
Constant on
Blinking (see fig. 5.1)
Flashing (see fig. 5.1)
Flashing (see fig. 5.1)
Flashing for 300 sec.
Reassignment buttons
Press and confirm press the "Status/Auto-Initialization" button.
Push both reassignment buttons and hold while powering up.
Release buttons when Status LED is solid.
A new switch point can be set by pressing the corresponding "Open" or "Closed" button
(actuator will not cycle).
Fieldbus Control module
OUNDATION
Press and
confirm press
on
off
on
off
Time
The default setting of the reassignment buttons is: enabled when
the unit is in "Out of Service".
"Open" and "Closed" LED are disabled.
Fig. 3.2 Reassignment buttons (located behind front
cover of module).
DOC.RM.BQC54.E Rev: 1
February, 2016
Closed
reassignment
button
Status LED
Open
reassignment
button
LED = Flashing