Emerson QC54 FOUNDATION Installation Manual

Hide thumbs Also See for QC54 FOUNDATION:

Advertisement

Quick Links

Installation guide
DOC.IG.QC54.1 Rev.: 2
FieldQ Control Module
QC54 FOUNDATION™ Fieldbus
FieldQ
FieldQ
April 2017

Advertisement

Table of Contents
loading

Summary of Contents for Emerson QC54 FOUNDATION

  • Page 1 Installation guide FieldQ DOC.IG.QC54.1 Rev.: 2 April 2017 FieldQ Control Module QC54 FOUNDATION™ Fieldbus FieldQ...
  • Page 2: Applicable Modules

    * For mechanical installation of the module see installation instruction leaflet DOC.QC4.MTI.1, as shipped with the module. * If you have any questions regarding these instructions, contact your Emerson sales office before proceeding as shipped with the module. Control Module Type Label = QC54..WP.. = Foundation Fieldbus™...
  • Page 3 Installation guide FieldQ DOC.IG.QC54.1 Rev.: 2 April 2017 Mechanical alignment and mounting of the control module Alignment-edge The control module is equipped with an alignment- edge on top of the module. This allows easy align- Alignment-edge ment and mounting of the control module on to the actuator housing.
  • Page 4: Pneumatic Connections

    FieldQ Installation guide April 2017 DOC.IG.QC54.1 Rev.: 2 Pneumatic connections IMPORTANT Single acting 1 The actuator/valve combination can move after connecting the air supply. 2 Ensure that the QC54 control modules are mounted properly to the actuator to achieve good functioning and the required ingress protection, before connecting the air supply.
  • Page 5: Electric Connections

    Installation guide FieldQ DOC.IG.QC54.1 Rev.: 2 April 2017 Electric Connections Table 4.1 Electrical data QC54 - FF WARNING * Do not put the Control module and the Pneu- Voltage range * 9 to 32 volts matic module in direct contact with magnetic Maximum current 18 mA material.
  • Page 6 FieldQ Installation guide April 2017 DOC.IG.QC54.1 Rev.: 2 Procedure Terminal Control Module compartment Type Label 1. Remove control module cover (see figure 4.2) 2. Guide the cable(s) through the electrical Lockable entry(ies). Module cover - Use and mount cable glands as required by national or local legislation.
  • Page 7: Initial Setup

    Installation guide FieldQ DOC.IG.QC54.1 Rev.: 2 April 2017 Initial setup Initialization procedure Table 5.1 Status LED indications Initialization sets automatically the switch points for Status Status LED action the position feedback of the actuator (see fig. 5.2) OK (init successful) Constant on Additionally, initialization checks if the actuator Initializing...
  • Page 8: Maintenance

    FieldQ Installation guide April 2017 DOC.IG.QC54.1 Rev.: 2 Check functioning 5.3.1 “Factory default settings”, using the To perform a function test, please see chapter 3 of button board. Reference manual QC54, DOC.RM.QC54.E. To set the control module to its factory default set- After checking the functioning mount the control tings, do the following;...
  • Page 9: Optional Controls

    Installation guide FieldQ DOC.IG.QC54.1 Rev.: 2 April 2017 Optional Controls Manual Control options 8.1.2 Manual Control operation 1. The Manual Control has a “Push & Lock” func- (see figure 8.1) tion: For commissioning, emergency or maintenance To operate the Manual Control, use a screw purposes, the FieldQ can be supplied with one or two driver, push to activate and release to de- Manual Control options.
  • Page 10: Related Information

    These documents are available, in multiple For standard actuators, the top entry will languages, for download from throttle the closing stroke. www.emerson.com/fieldq For standard actuators, the bottom entry will throttle the opening stroke. Device driver For reverse acting actuators, the opposite The following DD drivers can be downloaded from strokes will be throttled.
  • Page 11: Eu Declaration Of Conformity

    We hereby declare, that the products specified below meet the basic health and safety requirements of the above mentioned European Directives. Product description: QC54 Foundation Fieldbus Control module Serial number: Each Control module has an identifiable serial number Year of Construction:...
  • Page 12: Product Marking

    10.2 ATEX/IECEx Intended use parts from Emerson else the suitability for Division 2 will be impaired. • The Control Module QC54..P4.. of the FieldQ pneumatic actuator is a Group II category Table 10.1 Wiring dimensions...
  • Page 13 Installation guide FieldQ DOC.IG.QC54.1 Rev.: 2 April 2017 10.4 Wiring instructions QC54 Non Incendive / Non Sparking Control Modules Electrical Input: Unclassified or Non Hazardous or Voltage level: 9 to 30 volts Hazardous Location Classified Location Current 18 mA maximum Cable range: Solid wire 2.5mm...
  • Page 14 FieldQ Installation guide April 2017 DOC.IG.QC54.1 Rev.: 2 11 Intrinsically safe installation instructions 11.1 Product marking atmospheres caused by mixtures of air and gases, vapours, mists or by air/dusts are likely to occur. Control Module Terminal The pneumatic actuator part, together with the Type Label compartment pneumatic module part of the FieldQ pneumatic...
  • Page 15: Dielectric Strength

    Installation guide FieldQ DOC.IG.QC54.1 Rev.: 2 April 2017 11.5 Wiring instructions QC54 - 11.4 Dielectric strength Protection level “ic” Control Module QC54 complies to the dielectric strength requirement according IEC 60079-11 Unclassified or Non Hazardous or Clas- Hazardous Location sified Location Table 11.1 Wiring dimensions Wire type Dimensions...
  • Page 16 FieldQ Installation guide April 2017 DOC.IG.QC54.1 Rev.: 2 12 FISCO Concept The QC54 module is suitable for use in a FISCO system in accordance with IEC 60079-11 : 2012 for use in Zone 1 and 2 locations. 12.1 Fieldbus Intrinsically Safe Concept The FISCO Concept allows the interconnection of intrinsically safe apparatus to associated apparatus not specifically examined in such combination.
  • Page 17 Installation guide FieldQ DOC.IG.QC54.1 Rev.: 2 April 2017...
  • Page 18 FieldQ Installation guide April 2017 DOC.IG.QC54.1 Rev.: 2...
  • Page 19 Installation guide FieldQ DOC.IG.QC54.1 Rev.: 2 April 2017...
  • Page 20 ©2017 Emerson. All rights reserved. T +27 11 451 3700 F +27 11 451 3800 No.1 Lai Yuan Road The Emerson logo is a trademark and service mark of Wuqing Development Area EUROPE Emerson Electric Co. FieldQ is a mark of the Emerson Tianjin 301700 family of companies.

Table of Contents