Emerson Bettis Q Series Reference Manual page 35

Foundation fieldbus control module
Table of Contents

Advertisement

Reference manual F
DOC.RM.BQC54.E Rev: 1
February, 2016
Table 4.3 Bettis Q-Series™ Alerts & recommended actions
Alerts
Parameter name
bad_position_sensor
bad_temperature_sensor
system_temperature_exceeded
software_error
travel_deviation
shutdown_is_set
pilot valve_error
Buttonboard_error
cm_life_exceeded
pm_life_exceeded
act_life_exceeded
valve_life_exceeded
time_in_position_exceeded
open_travel_time_exceeded
close_travel_time_exceeded
assembly_error
initialization_failed
Fieldbus Control module
OUNDATION
DeltaV text
Recommended actions
Position Sensor Error
Feedback problem, replace Control module when
possible
Temperature Sensor
Temperature sensor problem, replace Control
Error
module when possible
System Temperature
Take corrective actions to bring temperature
Exceeded
within specified range.
Software Error
Software error has been detected, replace
control module when possible.
Travel Deviation
Lost position, Check air pressure
Shutdown Is Set
Internal communications problem, check
shutdown configuration for restart, Replace
Control module.
Pilot valve error
Pilot valve number mismatch or pilot valve failure
has been detected
Buttonboard Error
Replace control module when possible
Control Module Life
Control module life cycle exceeded, replace
Cycle Exceeded
control module
Pneumatic Module Life
Pneumatic module life cycle exceeded, replace
Cycle Exceeded
pneumatic module.
Actuator Life Cycle
Actuator life cycle exceeded, replace actuator.
Exceeded
Valve Life Cycle
Valve life cycle exceeded,valve requires
Exceeded
maintenance.
Time in position
Time in position exceeded, take appropriate
exceeded
action.
Open travel timer
Open travel timer exceeded, check valve system.
exceeded
Close travel timer
Close travel timer exceeded, check valve system.
exceeded
Assembly error
Pneumatic function mismatch, check module and
actuator configuration
Initialization Failure
Device failed initialization; Check air pressure,
check actuator sizing, check valve system
Internal alerts
Counter alerts
Timer alerts
Initialization alert
Alert default setting
Advisory
Maintenance
n
n
y
y
n
n
y
y
n
n
y
y
n
n
n
n
n
n
n
n
n
n
n
n
n
n
y
y
n
n
y
y
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Fail
n
n
n
n
n
n
y
y
y
y
y
y
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
y
y
n
n
Page 35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qc54

Table of Contents