Chapter 4 Parameters
VFD-EL-W
3. When MI3 (corresponds to bit2) is triggered, and the weight is 4, Pr.04-26=59 (63-4).
4. When MI4 (corresponds to bit3) is triggered, and the weight is 8, Pr.04-26=55 (63-8).
5. If more than one MI terminals are triggered, use 63 minus the weight that corresponds to the MI terminal.
For example, if you set MI2 and MI3 to ON, Pr.04.26 displays 57 (63-2-4=57, decimal)
Internal/External Multi-function Input Terminals Selection
04.27
Settings
Selects the terminals MI1–MI4 to be either internal terminal or external terminal. You can activate internal
terminals with Pr.04.28. A terminal cannot be both an internal terminal and an external terminal at the same
time.
When setting this parameter, convert Bit3–Bit0 that represent the status of MI4–MI1 from binary to decimal.
Set MI3 and MI4 as internal terminals; set MI1 and MI2 as external terminals. Pr.04-27 should be set to 12.
Internal Terminal Status
04.28
Settings
Sets the internal terminal action (ON/OFF) through the keypad or communication. And use this parameter
with Pr.04.27.
4-58
0–4095
0–4095
Unit: 1
Default: 0