Outlet Pipe; Connect The Pipe Of Indoor Unit; Install Drain Hose - Tadiran Telecom SMVH09A-2A1B1NA Service Manual

Table of Contents

Advertisement

Step 4: Outlet pipe
1.The pipe can be led out in the direction of right, rear right or left.
right
Step 5: Connect the pipe of indoor unit
1. Aim the pipe joint at the corresponding bellmouth.
2. Pretightening the union nut with hand.
3. Adjust the torque force by referring to the following sheet. Place the
open-end wrench on the pipe joint and place the torque wrench on the
union nut. Tighten the union nut with torque wrench.
Hex nut diameter
Ф 6
Ф 9.52
Ф 12
Ф 16
Ф 19
4. Wrap the indoor pipe and joint of connection pipe with insulating pipe,
and then wrap it with tape.
Step 6: Install drain hose
1. Connect the drain hose to the outlet pipe of indoor unit.
2. Bind the joint with tape.
drain hose

outlet pipe

tape
Note:
● Add insulating pipe in the indoor drain hose in order to prevent condensation.
● The plastic expansion particles are not provided.
Tightening torque (N·m)
15-20
30~40
45~55
60~65
70~75
drain hose
2.When select leading out the pipe from left or right, please cut
off the corresponding hole on the bottom case.
pipe joint
torque wrench
indoor pipe
insulating pipe
Installation Manual
cut off
the hole
pipe
union nut
open-end
wrench
union nut
pipe
insulating pipe
drain hose
outlet
pipe
21