Outdoor unit:
(1) Capacitor charge fault (Fault with outdoor unit) (AP1 below refers to the outdoor control panel)
Main Check Points:
●Use AC voltmeter to check if the voltage between terminal L and N on the wiring board is within 210VAC~240VAC.
●Is the reactor (L) correctly connected? Is the connection loose or fallen? Is the reactor (L) damaged?
Fault diagnosis process:
Turn on the unit
and wait 1 minute
Use DC voltmeter
to measure the
voltage on the two
ends of electrolytic
capacitor
Voltage higher than 200V?
Measure the AC voltage between
terminal L and N on wiring board
XT(power supply)
Voltage within
210VAC~250VAC?
Shut down the power and wait 20 minutes;
or use DC voltmeter to measure the voltage
on the two ends of capacitor , until the
voltage is lower than 20V
Check the
connection of reactor
(L in the Electrical
Wiring Diagram)
If the wiring of
reactor L is normal?
Replace the control
panel AP1
End
Fault with the voltage
Yes
testing circuit on
control panel AP1
No
Shut down the power
and repair the power
No
supply to restore the
range
210VAC~250VAC
Yes
Connect the reactor
Laccording to Elec-
No
trical Wiring Diagr-
am correctly
Yes
Replace the control
panel AP1
power on and
restart the unit
No
Re-energize and
If the fault is
turn on the unit
eliminated?
No
Troubleshooting
If the fault is
Yes
eliminated?
Yes
43