Industrial Electronic Devices
The data of the columns in the "SNMP
Write" have the following meanings:
If
the
field
"Enable"
checked,
the
SNMP
enabled;
In
the
field
"Community
Name"
the
name
Community is defined;
In the field "Type" the type of
data of the OID is defined
(Octet String or Integer);
In the field "Position" the starting byte of the internal memory array where mapping the data is defined;
In the field
"Start
Bit" the starting bit of the selected Position is defined;
In the field
"Num
Bits/Bytes" the dimension of the OID is defined. For 'Int' type the dimension is in bit, for 'String' type the
dimension is in bytes;
In the field "Description" the description/name of the OID is defined;
In the field "Mnemonic" a brief description of the OID is defined.
Note:
If the fields "On Change", "On CMD" and "On Timer" are disabled, the OID is readable using standard GET command. If one of these
fields is enabled, the OID is sent as Trap and it is readable by GET command too.
Note:
The field "Description" must start with lowercase letter and it cannot contain special chars (just letters and numbers). All the
"Description" fields must be different between them.
SNMP MIB (only if "Dynamic Map" is used):
By pressing the
"SNMP
MIB" button it is possible to save the MIB file for the SNMP Manager.
ADFweb.com S.r.l.
is
OID
is
of
the
Figure 5b: "Set SNMP Access -> SNMP Write" window
User Manual BACnet Master / SNMP Agent
Document code: MN67726_ENG
Revision 1.100
Page 27 of 42