ADF Web HD67726-IP-A1 User Manual page 22

Bacnet master / snmp agent - converter

Advertisement

Industrial Electronic Devices
SET BACNET ACCESS:
By Pressing the
"Set BACnet Access
4).
Figure 4a: "Set BACnet Access
The window is divided in two parts, the
and
"BACnet
Write" that contains the BACnet objects that the converter writes into the BACnet slaves.
The means of the fields in the window (BACnet in Read) are the follows:
In the field
"IP Address /
In the field
"Object
Type" the object to be read is defined;
In the field "Instance" the instance number of the object is defined;
In the field "Property" the property to be read is defined;
In the field "NByte" the number of bytes reserved for saving the information on SNMP side is defined;
By checking the field
"En
Address (D Adr). These informations are used for make a request to other segments of network (through a BACnet router);
In the field
"D
Net" the destination network (from 1 to 65535) is defined;
In the field
"D
Len" the length of "D Add" field (1 or 2 or 6) is defined;
ADFweb.com S.r.l.
" button from the main window of SW67726 (Fig. 2), the window "Set BACnet Access" appears (Fig.
BACnet Read" window
"BACnet
Read" that contains the BACnet objects that the converter reads from the BACnet slaves;
ID" the IP address / ID of the slave that contains the data to be read is defined;
Dest" it is possible to enable the Destination Network (D Net), Destination Length (D Len) and Destination
User Manual BACnet Master / SNMP Agent
Document code: MN67726_ENG
Revision 1.100
Page 22 of 42