baltur TBG 80 LX ME /V Instruction Manual For Installation, Use And Maintenance page 60

Progressive/modulating two-stage gas burners
Table of Contents

Advertisement

Available languages

Available languages

ENGLISH
CAUTION / WARNINGS
The housings for the cables for the plugs are provided respecti-
vely for cable Ø 9.5÷10 mm and Ø 8.5÷9 mm, this ensures
the protection rating is IP 54 (Standard IEC EN60529) for the
electrical panel.
• To reclose the electrical panel lid, fix the screws (1) with a torque of
about 5 Nm to ensure the correct seal.
To access the control panel (8), loosen the screws (10), slide the
transparent door (7) for a short distance in the direction of the arrow
shown in the figure and separate it from the cover.
CAUTION / WARNINGS
Only professionally qualified personnel may open the burner
electrical switchboard.
• In case of phase-phase 230V electrical grids, if these latter are
unbalanced, the voltage between flame detection electrode and
ground can not be enough to ensure burner correct operation.
The problem is solved by using a type AR1 insulating transformer
cod.0005020028 connected as shown in the following diagram.
AR 1
Ph
L (1)
ION IN
Ph 230
IN (2)
ION PROBE
• To secure the transparent door on the panel properly, position the
hooks at their hooking points (9), slide the door in the direction
indicated by the arrow and tighten the screws again (10).
ION
0006081328_202001
9
9
14 / 44
9
9
10
8
7
10