baltur TBG 80 LX ME /V Instruction Manual For Installation, Use And Maintenance page 50

Progressive/modulating two-stage gas burners
Table of Contents

Advertisement

Available languages

Available languages

ENGLISH
Special precautions when using gas.
• Check that the feed line and the train comply with current law and
regulations.
• Check that all the gas connections are properly sealed.
• Do not leave the equipment on when it is not in use and always
close the gas cock.
• If the user is absent for a prolonged period of time, close the main
gas feed tap to the burner.
• If you smell gas:
- do not operate electrical switches, phones or any other object
that may cause sparks;
- open immediately doors and windows to create a draught to
clear the air in the room;
- close the gas cocks;
- have professionally qualified personnel correct the fault.
• Do not obstruct ventilation openings in the room where there is
gas equipment. Otherwise, dangerous situations may arise with the
build up of toxic and explosive mixtures.
RESIDUAL RISKS
• Even though the product was designed in compliance with the obli-
gatory standards, residual risks may still be present during correct
operation. They are signalled on the burner through special Picto-
grams.
CAUTION
Moving mechanical organs.
CAUTION
Materials at high temperature.
CAUTION
Powered electric panel.
ELECTRIC SAFETY WARNINGS
• Check that the equipment has a suitable ground system, carried
out following safety standards in force.
• Have qualified personnel check that the electric system is adequate
to equipment maximum power consumption indicated on the plate.
• For the mains supply connection is required an omnipolar switch
with a contact opening gap equal or above 3 mm in accordance
with current safety regulations (condition of overvoltage category
III).
• Remove the external insulating seal of the supply pipe necessary
for the connection, preventing the cable to touch metal parts.
• The use of any electrically fed components entails complying with
certain fundamental rules, including the following:
- do not touch the equipment with parts of the body that are wet
or damp or with damp feet;
- do not pull on electrical cables;
- do not leave the equipment exposed to atmospheric agents
(such as rain or sun etc.) unless there is explicit provision for
this;
- do not allow the equipment to be used by children or inexpert
persons;
- The power supply cable for the equipment must not be replaced
by the user. In case of cable damage, turn the equipment off. To
replace it contact qualified personnel only;
- If you decide not to use the equipment for a certain period of
time it is advisable to switch off the electrical power supply to all
components in the system that use electricity (pumps, burner,
etc.).
• Use regulation-compliant flexible cables EN60335-1:EN 60204-1
- in case of PVC sheath, at least type H05VV-F;
- in case of rubber sheath, at least type H05RR-F; LiYCY
450/750V
- without any sheath, at least type FG7 o FROR, FG70H2R
• The electric equipment works correctly when the relative humidity
does not exceed the 50% at a maximum temperature of +40° C.
Higher relative humidity are allowed at lower temperatures(e.g. 90
% at 20° C)
• The electric equipment works correctly at altitudes of up to 1000 m
above the see level.
DECLARATION OF CONFORMITY
IMPORTANT
We hereby declare that our gas, liquid and mixed forced drau-
ght burners respect the minimum requirements of the Europe-
an Directives and Regulations and are compliant with Europe-
an standards.
A copy of the EC declaration of conformity is supplied with the
burner.
4 / 44
0006081328_202001

Advertisement

Chapters

Table of Contents
loading

Table of Contents