Electrical Connection - BÖWE P12 Installation Instructions Manual

Hide thumbs Also See for P12:
Table of Contents

Advertisement

7
Connection

7.3 Electrical Connection

Only trained electricians are permitted to work on the electrical system.
Caution
Note the supply voltage (on the nameplate). Connect L1 /L2 /L3, neutral and ground wires with the
appropriate cross section and fusing. Pass the cable into the switch panel through the PVC screwed
union provided and connect to terminal.
Main switch connection
The main switch must be connected at the customer with an approved cable. Strip the cable right before
the main switch only. Do not lay stripped cable in the cable trunking.
Ground-fault circuit interrupter at the customer
Ground-fault circuit interrupter at the customer
In case of a fault current breaker integrated in the building it is recommandable
to make sure, if it is applicable to the machine with variable speed drive.
P12 /P15 /P18
400 V, 50 Hz
Steam with distillation
Electric with distillation
Steam with distillation with Slimsorba
Electric with distillation with Slimsorba
P12 /P15 /P18
230 V, 60 Hz
Steam with distillation
Electric with distillation
Steam with distillation with Slimsorba
Electric with distillation with Slimsorba
44
Operating
Max. Current
load
A
kW
7.4
18
20.1
38
8.1
20
26.5
49
Operating
Max. current
load
A
kW
7.4
26
20.1
60
8.1
30
26.5
79
7
7.3
Fuse
A
25
50
25
63
Fuse
A
35
63
35
80
P12-P15-P18