Status Display Of The Control Panel; Warning And Fault Messages - ABB Fimer PVS980-58 Series Commissioning And Maintenance Manual

Central inverter
Hide thumbs Also See for Fimer PVS980-58 Series:
Table of Contents

Advertisement

Where
LED
Control unit BCU-12
BATT OK
PWR OK
FAULT
WRITE
AC500
PWR
RUN
ERR
MIRU-01
POWER
ERROR
STATUS
DISABLE
MGND-01
POWER
GROUNDING
STATUS
BAMU-11
POWER
LINK FAULT
U2 > 60V
U1 > 60V

Status display of the control panel

Refer to the Firmware manual.

Warning and fault messages

Refer to the Firmware manual.
22 Fault tracing
Color
Indication
Green
The battery voltage of the real-time clock is OK
(more than 2.8 V).
When the LED off:
• The battery voltage is less than 2.8 V
• The battery is missing
• The control unit is not powered
Green
The internal voltage is correct.
Red
The control program indicates that the equipment is
faulty.
Refer to the Firmware manual.
Yellow
Writing to SD card in progress.
Green
The AC500 unit is powered.
Green
The AC500 program is running.
Red
An error or warning detected by the AC500
firmware.
Green
The MIRU-01 unit is powered.
Red
An error detected by the MIRU-01 firmware.
Green
The status of the insulation resistance
measurement:
• Slow flash (once every 5 seconds):
Measurement ready
• Rapid flash (5 times per second):
Measurement not ready
Red
Insulation resistance measurement is disabled.
Green
The MGND-01 is powered.
Green
The grounding voltage is OK (<50 V DC).
Green
The BAMU-11 unit is powered.
Red
There is an error on the board or an error in the
PSL2 link.
Yellow
The input voltages (U2, V2 and W2) are more than
60 V.
Yellow
The input voltages (U1, V1 and W1) are more than
60 V.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents