Cleaning; Routine Maintenance - BYD Energy Pod Series User's Installation And Use Manual

Table of Contents

Advertisement

S/N
62
63
64
65
66
67
68
Emergency: In case of emergency, promptly cut off the power supply and
disconnect the circuit breaker.
3

Cleaning

Note: Please shut down prior to cleaning
It‟s recommended to clean and maintain the product irregularly. During cleaning,
please use the soft and dry cloth or the vacuum cleaner to remove the dust and stains
from the product, and especially clean the heat dissipation and ventilation vents on
both sides of the product. The organic solvents, corrosive liquids, etc. cannot be
used for cleaning the product.
4

Routine Maintenance

4.1 Requirement for recharging after normal storage
The storage temperature range of the battery is -10℃ ~ +45℃. As for the battery with
long-term storage, the routine maintenance is required. Please charge the battery to
40%SOC at a current of 0.2C according to the requirements in the table below.
Requirement for Recharging for Storage:
Ambient temperature
for storage
<-10℃
-10~25℃
25~35℃
35~45℃
Code
Fault Item
35105
Branch current 1 sampling failure
35106
Branch current 2 sampling failure
Input voltage sampling failure at the
35107
side of battery
35108
Output voltage sampling failure
Radiator temperature sampling
35109
failure
DC1 Inductor temperature sampling
35110
failure
DC2 Inductor temperature sampling
35111
failure
Relative humidity for
storage environment
/
5%~70%
5%~70%
5%~70%
Storage Time
SOC
Prohibited
/
≤12 months
30%≤SOC≤60%
≤6 months
30%≤SOC≤60%
≤3 months
30%≤SOC≤60%
Secret