Table 16: Building System Interface Board Field Terminal Points; Figure 8: Building System Interface Board - York Sun Premier GZA1M Series Start-Up & Operation

Rooftop units
Table of Contents

Advertisement

Table 16: Building System Interface Board Field Terminal Points

Callout
Name
1
EAD-REF
2
EF-REF
3
OAD-REF
4
ZN-H
5
ZN-T
6
HTGV-O
7
HUM-O
8
ADR-S
9
ISOD1-S
10
ISOD2-S
11
SAFETY1
12
SAFETY2
13
SAFETY3
14
G-FAN
15
Y1-LOWCOOL
16
Y2-HIGHCOOL
17
W1-LOWHEAT
18
W2-HIGHHEAT
19
HUMIDISTAT
20
ALARM1-C
21
ALARM2-C
22
HUM-C
23
ISOD-C
24
VAVHTG-C
8
9
10
11

Figure 8: Building System Interface Board

YORK
Description
Exhaust Air Damper Reference
Exhaust Fan Speed Reference
Outdoor Air Damper Reference
Zone Humidity
Zone Temperature
Heating Valve Output
Humidifier Output
Demand Shed Input
Isolation Damper 1 Status
Isolation Damper 2 Status
Local Safety Command Input 1
Local Safety Command Input 2
Local Safety Command Input 3
G Fan Thermostat Input
Y1 Low Cool Thermostat Input
Y2 High Cool Thermostat Input
W1 Low Heat Thermostat Input
W2 High Heat Thermostat Input
Humidistat Input
Alarm 1 Command
Alarm 2 Command
Humidifier Command
Isolation Damper Command
MZVAV Heat Command
6
7
20 21 22 23
14 15 16 17 18 19
12 13
Start-Up & Operation Guide | 5587001-YSG-A-520
IO Type
IO Number
AI
AI
AI
AI
AI
AO
AO
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BO
BO
BO
BO
BO
24
1
2
3
4
5
Pin
13
W8
14
W37
15
W6
17
W4
18
W45
1
W32
2
W30
1
W28
2
W27
3
W25
4
W24
5
W22
6
W21
7
W53
8
W55
9
W52
10
W51
11
W50
12
W49
6
W17
7
W16
8
W14
9
W13
10
W60
LD27997